Tiny Serial-to-Ethernet Device Server
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-78 -
The following are examples of pair-connection tests:
Pair-connection Settings:
Model
Port Settings
(default)
Pair-connection Settings
Baud
Rate
Data
Format
Application
Mode
Remote
Server IP
Remote TCP
Port
(default)
tDS-700 #1
115200
8N1
Client
IP Address of tDS-700 #2
10001
tDS-700 #2
115200
8N1
Server
-
-
Note
The Baud Rate and Data Format settings of the client and server (tDS-700 #1 and #2) depend on the COM
ports of the PC (or the connected device). The serial port settings between tDS-700 #1 and tDS-700#2 can be
different.
Ensure that the following items are available:
A DN-09-2F Terminal Board
http://www.icpdas.com/en/product/DN-09-2F
A I-7520 module
http://www.icpdas.com/en/product/I-7520
Step 1: Connecting to a network, PC and Power
1.
Confirm that the tDS-700/DS-2200 modules are functioning correctly. Refer to
Getting Started for tDS-700 series
Getting Started for DS-2200 series
for more
details.
2.
Use a DN-09-2F wiring terminal board to connect COM1 of the PC to COM1 of the tDS-700 #1,
information.
3.
Use an I-7520 module to connect COM2 of PC to COM1 of the tDS-700 #2, refer to
for RS-422/485 wiring details information.
※
Refer to Figure 6-1 for an illustration of how to perform the above steps.