WF-2000 Series AIO
User’s Manual (Ver. 1.2, May./2014) ------------- 32
Channel CJC Offset
Setting the CJC offset for the specific channel. The
behavior of the setting is the same as the CJC Offset, but
it only affects specific channel.
Note: The CJC offset can be any in the range of -30.00 to
+100.00 °C.
Filter Rejection
In order to remove the noise from the power supply, some
analog input modules feature build-in noise filter. Two
filters, 50Hz and 60Hz, are provided to remove noise
generated from power source.
Wire Detection
Enable / Disable the open-wire detection for thermocouple.
CJC Enable
Enable / Disable the CJC (Cold-Junction Compensation).
CJC Offset
Setting the CJC offset value for all AI channels. The offset
value is used to add or subtract the reading value.
Changing of this value will not affect calibration, but will
affect the reading value of temperature type.
Note: The CJC offset can be any in the range of -30.00 to
+100.00 °C.
Polling Interval
This value is the period to poll data to the WF-2000 I/O
module.