background image

441 01 2314 06

Specifications are subject  to change without notice.

10

CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each

appliance connected to the venting system being placed

into operation, could result in carbon monoxide

poisoning or death:
The following steps shall be followed for each appliance

connected to the venting system being placed into

operation, while all other appliances connected to the

venting system are not in operation:

1.Seal any unused openings in the venting system.
2.Inspect the venting system for proper size and horizontal

pitch, as required in the 

National Fuel Gas Code, ANSI

Z223.1/NFPA 54 

or 

CSA B149.1, Natural Gas and Propane

Installation Code

 and these instructions. Determine that

there is no blockage or restriction, leakage, corrosion and

other deficiencies which could cause an unsafe condition.

3.As far as practical, close all building doors and windows and

all doors between the space in which the appliance(s)  

connected to the venting system are located and other

spaces of the building.

4.Close fireplace dampers.
5.Turn on clothes dryers and any appliance not connected to

the venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they are operating

at maximum speed. Do not operate a summer exhaust fan.

6.Follow the lighting instructions. Place the  appliance being

inspected into operation. Adjust the thermostat so 

appliance is operating continuously.

7.Test for spillage from draft hood equipped appliances at the

draft hood relief opening after 5 minutes of main burner 

operation. Use the flame of a match or candle. (

Figure 4

)

8.If improper venting is observed, during any of the above

tests, the venting system must be corrected in accordance

with the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54

and/or 

CSA B149.1, Natural Gas and Propane Installation

Code

.

9.After it has been determined that each appliance connected

to the venting system properly vents when tested as out-

lined above, return doors, windows, exhaust fans, fireplace

dampers and any other gas

fired burning appliance to their

previous conditions of use.

!

WARNING

Venting to Existing Masonry Chimney

Dedicated venting of one fan assisted furnace into any ma-

sonry chimney is restricted

.  A chimney must first be lined with

either Type B vent sized in accordance with NFGC tables 13.1 or

13.2 or a listed metal lining system, sized in accordance with the

NFGC Section 13.1.7 for a single appliance or 13.2.20 for multiple

appliances, or NSCNGPIC Appendix C, Section 10. (See 

Masonry

Chimney Venting

 of these instructions.)

Listed, corrugated metallic chimney liner systems in masonry

chimneys shall be sized in the U.S. by using 

NFGC

 tables per

13.1.7 for dedicated venting and per 13.2.20 for common venting

with the maximum capacity reduced by 20% (0.80 X maximum ca-

pacity) and the minimum capacity as shown in the applicable table.

Corrugated metal vent systems installed with bends or offsets re-

quire additional reduction of  5% of the vent capacity for each bend

up to 45

°

 and 10% of the vent capacity for each bend from 45

°

up to

90

°

. In Canada, use the 

NSCNGPIC

.

NOTE

: Two(2) 45

°

 elbows are equivalent to one (1) 90

°

 elbow.

Combined Venting into a Masonry Chimney

Venting into a masonry or concrete chimney is only permitted

as outlined in the NFGC or NSCNGPIC

 

 venting tables. 

Follow

all safe venting requirements.

Note: 

See section “

Masonry Chimney Venting

”.

5.  Horizontal Venting

Category 

Furnaces With External Power

Venters

In order to maintain a Category 

I

 classification of  fan

assisted fur-

naces when vented horizontally with sidewall termination, a power

venter is 

REQUIRED

 to maintain a negative pressure in the vent-

ing system.

In the U.S.

: Per the NFGC, a listed power venter may be used,

when approved by the authority having jurisdiction.

In Canada:

 Only power venters approved by the power venter

manufacturer and where allowed by the authority having jurisdic-

tion may be used.
Please consult the Fields Controls Co. or Tjernlund Products, Inc.

for power venters certified for use with this furnaces.

Vent Termination

Venting Through a Non-Combustible and
Combustible Wall

Consult External Power Venter manufacturer instructions.

Select the power venter to match the Btuh input of the furnace be-

ing vented.  Follow all of the power venter manufacturer’s installa-

tion requirements included with the power venter for:

venting installation,

vent terminal location,

preventing blockage by snow,

protecting building materials from degradation by flue gases,

s

ee 

Figure 5

 for required vent termination.

NOTE: 

It is the responsibility of the installer to properly terminate

the vent and provide adequate shielding. This is essential in order

to avoid water/ice damage to building, shrubs and walkways.

Summary of Contents for C8DNL

Page 1: ...injury TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 Safe Installation Requirements 3 INSTALLATION 4 Combustion Ventilation Air 6 Gas Vent Installation 9 Venting Horizonta 10 Venting Chimney Adapter 12 Ga...

Page 2: ...nformation This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNIN...

Page 3: ...e ON setting ____ Fan Time OFF Setting ___ Manual Gas Shut Off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Calculated Firing Rate See Checks and A...

Page 4: ...around supply and return air ducts Install correct filter type and size Unit MUST be installed so electrical components are pro tected from direct contact with water Safety Rules Your unit is built to...

Page 5: ...ible material See Ductwork and Filter Sub base for Com bustible Floors 6 Maintain clearance for fire safety and servicing A front clear ance of 24 609 6mm required and 30 762mm recommen ded for access...

Page 6: ...ion Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket and building joists studs or framing DIMENSIONAL INFORMATION Unit Capacity Cabinet Top...

Page 7: ...gens that will result in safety and performance related problems and may harm the furnace These instances must use only out door air for combustion The following areas or types of structures may cont...

Page 8: ...Not less than the sum of the areas of all vent connectors in the space The opening shall commence within 12 304 8mm of the top of the enclosure Appliances shall have clearances of at least 1 25 4mm f...

Page 9: ...0 20 3 150 88 2 4 200 117 6 5 250 147 3 750 105 5 625 157 5 7 500 210 9 375 262 5 11 250 316 0 10 6 300 176 4 8 400 235 2 10 500 294 7 500 210 11 250 315 15 000 420 18 750 525 22 500 632 0 00 NP NP NP...

Page 10: ...pipe as per mitted by the National Fuel Gas Code Code ANSI Z223 1 NFPA 54 2009 Sections 12 and 13 venting requirements in the United States or the National Standard of Canada Natural Gas and Pro pane...

Page 11: ...st be lined with either Type B vent sized in accordance with NFGC tables 13 1 or 13 2 or a listed metal lining system sized in accordance with the NFGC Section 13 1 7 for a single appliance or 13 2 20...

Page 12: ...dryer or water heater vent or other appliance s direct vent intake or exhaust N Clearance to the vent terminal of a dryer vent water heater vent or other appliances direct vent intake or exhaust O Cle...

Page 13: ...s are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate WARNING If a clay tile lined masonry chimney is being used and it is exposed to the outdoors bel...

Page 14: ...vent in a chase If a metal liner or Type B vent is used to line a chimney no other appliance shall be vented into the annular space between the chimney and the metal liner APPLIANCE APPLICATION REQUI...

Page 15: ...anufacturer s installation instructions CHIMNEY INSPECTION CHART For additional requirements refer to the National Fuel Gas Code ANSI Z223 1 NFPA 54 2009 and ANSI NFPA 211 2006 Chimneys Fire places Ve...

Page 16: ...ose to the furnace as possible where it is readily ac cessible Refer to Figure 7 FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Use wrench to h...

Page 17: ...rnace Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 50 8mm outside furnace WARNING Additional Propane Piping Requirements Have a licensed Propane gas de...

Page 18: ...Box to alternate location and attach using two self tapping screws from bag 5 A wire tie may need to be cut for additional wire length 6 Apply two hole plugs from bag at left J Box location 7 Positio...

Page 19: ...trical shorts of 24V wiring during installation service or maintenance may cause fuse to blow If fuse replacement is required use only a fuse of identical size 5 amp FUSE 25 24 98 Diagnostic Light Jum...

Page 20: ...er is in the full heat or cool position Installation of locking type dampers is recommended in all branches or in individual ducts to balance system s air flows Non combustible flexible duct connector...

Page 21: ...15 381 221 2 571 5 Subbase for Coil Box NAHH004SB 153 4 25 4 209 16 522 3 149 16 369 9 161 16 408 161 4 412 8 145 8 371 5 15 381 131 2 342 9 15 381 131 2 342 9 NAHH005SB 193 8 181 1 209 16 522 3 183...

Page 22: ...e return air plenum above the furnace A filter rack is supplied with each furnace See Figure 17 Use either filter type Washable high velocity filters are based on a maximum air flow rating of 600 FPM...

Page 23: ...d pull straight down at side of blower Pull out through right door opening 4 Vacuum clean or wash with warm water and dry thoroughly be fore replacing NOTE If filters are only suitable for heating app...

Page 24: ...rol Remove manometer connection from manifold pressure tap and replace plug in gas valve 7 Check for leaks at plug Typical Gas Control Valve Figure 19 Regulator Adjustment Under Cap Inlet Pressure Tap...

Page 25: ...in accordance with the Manufacturer s instructions and all applicable codes and requirements or in the absence of local codes the applicable national codes WARNING MANIFOLD PRESSURE AND ORIFICE SIZE F...

Page 26: ...e burner compartment 2 Disconnect gas line from gas control valve so manifold can be removed 3 Disconnect wiring at gas control valve Be sure to note the proper location of all electrical wiring befor...

Page 27: ...ply and return air registers as close to furnace as possible avoiding direct radiant heat from heat exchangers 2 Operate furnace for 10 minutes with all the registers and duct dampers open by using a...

Page 28: ...he continuous fan option This connection is intended for the low speed motor tap and has a lower contact rating 8 amps than the heat and cool taps When the low speed blower lead is connected to this t...

Page 29: ...continuously while there are no other blower demands from furnace control Fan demands from furnace control for heat cool or G will override hard wired speed tap NOTE 3 EAC is NOT active for hard wired...

Page 30: ...c Codes See Figure 25 OFF 24VAC or 115VAC is off fuse is open Heartbeat Normal operation or no previous Diagnostic Code ON SOLID Soft Lockout Furnace Control Error 1 hr delay If code repeats immediate...

Page 31: ...ubject to change without notice Save This Manual For Future Reference Downflow Models 8DNL050B12B2 8DNL075B12B2 8DNL075F16B2 8DNL100F14B2 8DNL100L20B2 8DNL125L20B2 Denotes Brand International Comfort...

Page 32: ...han 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC 4 480oF 264oC Limits Controls Thermal Sensor oF oC Limit Control 300 149 See Parts List 300 149 See Parts List 300 149 See Par...

Page 33: ...Liters per second Filter required for each return air inlet Airflow performance includes 1 25 4mm washable 600 FPM 3 0 m s max filter media See Table for bellyband location on motor 8DNL100F14 1 Exter...

Page 34: ...441 01 2314 06 Specifications are subject to change without notice 33 Wiring Diagram 8DNL...

Page 35: ...njury or property damage Consult a qualified installer service agency local gas supplier or your distributor or branch for information or assistance The qualified installer or agency must use only fac...

Reviews: