background image

INSTALLATION INSTRUCTIONS

R

410A Split System Air Conditioner

421 01 5104 02

5

Specifications subject to change without notice.

Install Liquid Line Filter Drier Indoor

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Installation  of filter  drier  in liquid line is  required.

Filter drier must be wrapped in a heat

sinking material

such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1. Braze 5 in. (127 mm) liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5 in. (127 mm) liquid  tube.

Flow arrow must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter

drier.

Figure 3

Liquid Line Filter Drier

Refrigerant Tubing Connection Outdoor

Connect vapor tube to fitting on outdoor unit vapor service

valves (see Table 2.)  Connect and braze the 3/8” coupling

(provided with the filter drier) to the liquid service valve and

connect and braze the liquid tubing to the other end of this

coupling.  Use refrigerant grade tubing.

Sweat Connection

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat

sinking

material such as a wet cloth.

Service valves are closed from factory and ready for brazing.

After wrapping service valve with a wet cloth, braze sweat

connections using industry accepted methods and materials.

Consult local code requirements. Refrigerant tubing and

indoor coil are now ready for leak testing. This check should

include all field and factory joints.

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using

the recommended deep vacuum method of 500 microns. An

alternate triple evacuation method may be used.  See triple

evacuation method in Service Manual.

IMPORTANT

: Always break a vacuum with dry nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable

of pulling a vacuum of 500 microns and a vacuum gage

capable of accurately measuring this vacuum depth. The

deep vacuum method is the most positive way of assuring a

system is free of air and liquid water. (See Fig. 4)

Figure 4

Deep Vacuum Graph

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MICRONS

2500

3000

3500

4000

4500

5000

A95424

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both

indoor and outdoor unit has not shifted during shipment.
Ensure tubes are not rubbing against each other or any

sheet metal. Pay close attention to feeder tubes, making sure
wire ties on feeder tubes are secure and tight.

Make Electrical Connections

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Do not supply power to unit with compressor terminal box

cover removed.

Be sure field wiring complies with local and national fire,

safety, and electrical codes, and voltage to system is within

limits shown on unit rating plate. Contact local power

company for correction of improper voltage. See unit rating

plate for recommended circuit protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate.
Do  not install unit in system where voltage may fluctuate
above or below permissible limits.

NOTE

: Use copper wire only between disconnect switch and

unit.

NOTE

: Install branch circuit disconnect of adequate size per

NEC to handle unit starting current. Locate disconnect within

sight from and readily accessible from unit, per Section
440

14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend

wires from disconnect through power wiring hole provided

and into unit control box.

Summary of Contents for CSA6

Page 1: ...ility or operation Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety Labeling and Signal Words CAUTION WARNING TABLE OF CONTENTS Safety C...

Page 2: ...ee Fig 1 6 Avoid direct tubing contact with water pipes duct work floor joists wall studs floors and walls 7 Do not suspend refrigerant tubing from joists and studs with a rigid wire or strap which comes in direct contact with tubing See Fig 1 8 Ensure that tubing insulation is pliable and completely surrounds vapor tube 9 When necessary use hanger straps which are 1 in 25 4 mm wide and conform to...

Page 3: ...operating ambient in cooling mode is 125 F 51 67_C Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Use all service ports and open all flow control devices including solenoid valves CAUTION UNIT DAMAGE HAZARD Failur...

Page 4: ...ng line sets between 80 and 200 ft 24 38 and 60 96 m and or 20 ft 6 09 m vertical differential refer to Long Line Applications Guideline Table 2 Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters In UNIT SIZE LIQUID RATED VAPOR up to 80 ft 24 38 m Connection and Tube Diameter Connection Diameter Rated Tube Diameter 18 24 30 3 8 3 4 3 4 36 42 48 3 8 7 8 7 8 60 3 8 7 8 1 1 8 Uni...

Page 5: ...using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum metho...

Page 6: ...ired Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set thermostat to OFF and clos...

Page 7: ...ommunicating mode make sure that indoor airflow is set to efficiency during charging If conditions are favorable check system charge by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable...

Page 8: ... will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The crankcase ...

Page 9: ...RUCTIONS R 410A Split System Air Conditioner 421 01 5104 02 9 Specifications subject to change without notice terminals For operation in non communicating mode wire solenoid valve kit NASA401LS across C and Y terminals ...

Page 10: ... outdoor fan is turned off If the call for cooling continues the control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the thermal cutout trips for three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SH...

Page 11: ...il Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sensors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive seconds while cooling demand exists Possible causes are internal compressor overload trip or ...

Page 12: ...INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner 12 421 01 5104 02 Specifications subject to change without notice Figure 9 Single Stage Control Board ...

Page 13: ...ite Red R Wall Control Variable Speed Furnace Fan Coil Outdoor Green Yellow White Red LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION C DX DX R Figure 11 Non Communicating Standard Thermostat 3 Wire 24V Circuit Connections See Thermostat Installation Instructions for Specific Unit combinations LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION ELECTRICAL OPERAT...

Page 14: ...OM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN LEGEND 24V FACTORY WIRING 24V FIELD WIRING FIELD SPLICE CONNECTION NOTE Wiring must conform to NEC or local codes Figure 13 Non Communicating Indoor with Observer Communicating Wall Control NAXA00101DB Green Yellow White Red OAT Sensor Communicating Outdoor W2 C Y R C R Wall Control OAT DX R C DX Y G O C Y Y2 R W2 G DX R C DX Non Communicating Indoor NOTE Th...

Page 15: ...as with other HFC refrigerants is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressures less than 600 psig Do not install a suction line filter drier in liquid line POE oils absorb moisture rapidly Do not expose oil to atmosphere POE oils may cause damage to certain plastics and roofing materials Wrap all filt...

Reviews: