background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: (F/G)9MAE

Specifications  subject to change without notice.

34

440 04 4700 00

SEQUENCE OF OPERATION

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittent

unit operation.
Furnace control must be grounded for proper

operation or control will lock out.  Control is grounded

through green/yellow wire routed to gas valve and

manifold bracket screw.

CAUTION

!

Using the schematic diagram (See 

Figure 15

), follow the

sequence of operation through the different modes. Read and

follow the wiring diagram very carefully!!

NOTE

:  If a power interruption occurs during a call for heat

(W/W1 or W/W1-and-W2), the control will start a 90-second

blower-only ON period two seconds after power is restored, if

the thermostat is still calling for gas heating. The amber LED

light will flash code 1+2 during the 90-second period, after

which the LED flash a heartbeat (bright

dim), as long as no

faults are detected. After the 90-second period, the furnace will

respond to the thermostat normally.
The blower door must be installed for power to be conducted

through the blower door interlock switch ILK to the furnace

control CPU, transformer TRAN, inducer motor IDM, blower

motor BLWM, hot surface igniter HSI, and gas valve GV.

Communicating Control and Modulating Heating

(Adaptive Mode)

Best comfort will be attained when a communicating wall

control is used with this product. Wiring and setup instructions

are provided with the communicating control. See the furnace

data sheet accessory section for help in selecting the

appropriate communicating control for this furnace.
When a communicating control is used, the furnace will

modulate through its full operation range, or can be limited via

the minimum and maximum CFM capacity configurations.
Operation of the furnace at the beginning and end of each

heating cycle will be the same as detailed below in the

Single-Stage Thermostat section, EXCEPT that the

communicating control will send modulating rate command

signals through the communication bus rather than energizing

the 24

V thermostat terminals. Note that the R to W/W1 circuit

signal will be controlled by the COMMR relay on the furnace

control. See the wiring diagram in 

Figure 15

.

Single-Stage Thermostat and Modulating  Heating

(Adaptive Mode)

NOTE

:  Minimum-heat only switch SW1-2 selects the

minimum-heat only operation mode when ON.

Intermediate-heat only switch SW4-2 selects

intermediate-heat only operation mode when ON. If both

switches are ON the furnace control will default to

intermediate-heat. If either or both switches are ON, the furnace

control will operate at two-stages only as referenced in Two

Stage Thermostat section below. If both switches are OFF the

furnace control will operate in the adaptive heating mode in

response to a call for heat. (See

 Figure 15

) When the W2

thermostat terminal is energized it will always cause

maximum-heat operation as long as the R to W circuit is

closed, regardless of the setting of the minimum-heat or

intermediate-heat only switches.
This furnace can operate as a modulating furnace with a

single-stage thermostat because the furnace control CPU

includes a programmed adaptive sequence of controlled

operation, which selects a modulated rate between minimum-

and maximum-heat

.

 This selection is based upon the stored

history of the length of previous gas-heating periods of the

single-stage thermostat.

The furnace will start up in either intermediate-, or

maximum-heat.  The furnace will transition and operate at

minimum-heat or the calculated modulating rate after starting

and operating for 45 seconds at intermediate-heat.  The

furnace control CPU defaults to minimum-heat on the first

thermostat cycle and calculates the modulating rate that the

furnace should run at for 19 minutes on subsequent heat

cycles.
If the power is interrupted, the stored modulating rate is erased

and the furnace control will select intermediate-heat for 45

seconds, minimum-heat for 19 minutes and then switch to

maximum-heat, as long as the thermostat continues to call for

heat.  The furnace control CPU then uses this information to

calculate the modulating rate the furnace will operate at on the

next heating cycle.  If the calculated modulating rate is between

40% - 99% then the furnace control CPU will operate for 45

seconds at intermediate-heat, and then operate at the

calculated modulating rate for up to 19 minutes and then switch

to maximum-heat as long as the thermostat continues to call for

heat.  If the calculated modulating rate is 100% then the

furnace control will only operate at maximum-heat until the

thermostat is satisfied.
The wall thermostat ”calls for heat”, closing the R to W circuit.

The furnace control CPU performs a self-check, verifies the

low, medium, and high pressure switch contacts LPS,MPS, and

HPS are open, then de-energizes the PSR relay to close the

NC contact.

1.

Inducer Prepurge Period

 ­ 

The furnace control CPU

turns on inducer motor IDM and slowly increases the

inducer motor speed. After the low pressure switch LPS

closes the furnace control CPU continues to increase the

inducer motor speed until the medium pressure switch

MPS closes. When the medium pressure switch MPS

closes, inducer motor RPM is noted by the furnace

control CPU, and a 25-second prepurge period begins.

The RPM is used to evaluate vent system resistance.

This evaluation is then used to determine the required

RPM necessary to operate the inducer motor during

pre-purge, the first 45 seconds of intermediate-heat, or

any modulating rate that the furnace will transition to after

the blower on-delay is completed.

NOTE

:  The heat cycle can start in either intermediate- or

maximum-heat.  If a maximum-heat cycle is initiated, the

furnace control CPU will continue to increase the inducer

motor speed after the medium pressure switch MPS closes.

When the medium pressure switch closes, inducer motor RPM

is noted by the furnace control CPU, and a 25-second prepurge

period begins.  The RPM is used to evaluate vent system

restriction.  This evaluation is then used to determine the

required RPM necessary to operate the inducer motor in

maximum-heat pre-purge, or maximum-heat.  The high

pressure switch HPS should be closed before ignition but the

furnace control ignores this input until after ignition occurs.

2.

Igniter Warm-Up 

- At the end of the prepurge period, the

Hot-Surface Igniter HSI is energized for a 17-second

igniter warm-up period

3.

Trial-For-Ignition Sequence

 ­ 

When the igniter warm-up

period is completed the main gas valve relay contact

GVR closes to energize the gas valve solenoid GV. The

gas valve solenoid GV permits gas flow to the burners

where it is ignited.  Five seconds after the GVR closes, a

2-second Flame-Proving period begins.  The HSI igniter

will remain energized until flame is sensed or until the

2-second flame proving period begins.

4.

Flame-Proving

 - When the burner flame is proved at the

flame-proving sensor electrode FSE, the furnace control

CPU begins the blower-ON delay period and continues

to hold the gas valve GV open.  If the burner flame is not

proved within two seconds, the furnace control CPU will

Summary of Contents for (F/G)9MAE0601714A

Page 1: ...s and or pictures or product labels The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manua...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...nsate Drain Connected Condensate Drain Trapped Manual Gas Shut off Upstream of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Shade in Final Furnace Settings Bel...

Page 4: ...for the increased temperature in return air resulting from bypass NOTE If modulating dampers are used blower motor automatically compensates for modulating dampers Air Conditioning A C Setup Switches...

Page 5: ...2000 ft 610 M NOTICE The NATURAL GAS manifold pressure adjustments in Table 4 and Table 5 compensate for BOTH altitude AND gas heating value DO NOT apply an additional de rate factor to the pressures...

Page 6: ...e for altitude range NOTE For Canadian altitudes of 2000 to 4500 ft 610 to 1372 M use USA altitudes of 2001 to 3000 ft 610 to 914 M Check Inlet Gas Pressure The inlet gas pressure must be checked with...

Page 7: ...event gas leak WARNING 9 Remove manometer from the inlet pressure tap of the gas valve 10 Apply pipe dope sparingly to end of inlet gas pipe plug and re install in the gas valve 11 Re install cap over...

Page 8: ...for improved comfort Determine air temperature rise as follows 1 Place thermometers in return and supply ducts as near furnace as possible Be sure thermometers do not see heat exchanger so that radian...

Page 9: ...ve to prevent gas leak WARNING FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace life Recheck temperature rise It must be within limits specified on the rating pl...

Page 10: ...shooting assistance when R thermostat lead is disconnected Turn OFF when Self Test is completed Bl Off D l i dj bl d SW1 7 SW1 8 Blower OFF delay ON or OFF Blower Off Delay time adjustable 90 seconds...

Page 11: ...H POSITIONS 1600 2000 2100 2000 1000 800 1000 1200 1400 1600 2000 800 800 1000 1200 1400 2000 800 800 1000 1200 1400 1600 2000 2000 2000 800 800 1000 1200 1400 1600 2000 2000 1400 1400 1400 600 600 80...

Page 12: ...rmal circulation d Burners will re light when furnace cools down 2 Check Pressure Switch es This control proves operation of the draft inducer blower a Turn off 115 v power to furnace b Disconnect ind...

Page 13: ...43 3 8 0 60 42 3 2 0 50 850 44 3 8 0 60 43 3 5 0 55 43 3 6 0 55 43 3 7 0 60 875 44 3 6 0 60 44 3 7 0 60 43 3 4 0 55 43 3 5 0 55 4000 900 44 3 4 0 55 44 3 5 0 55 44 3 7 0 60 44 3 8 0 60 1219 925 44 3 2...

Page 14: ...750 44 3 5 0 55 44 3 7 0 60 44 3 8 0 60 43 3 4 0 55 8000 775 44 3 3 0 55 44 3 4 0 55 44 3 5 0 55 44 3 7 0 60 2438 800 45 3 8 0 60 44 3 2 0 50 44 3 3 0 55 44 3 4 0 55 825 46 3 7 0 60 46 3 8 0 60 45 3...

Page 15: ...3 2 0 50 42 3 3 0 50 850 43 3 4 0 55 43 3 5 0 55 43 3 6 0 55 43 3 8 0 60 875 44 3 7 0 60 44 3 8 0 60 43 3 4 0 55 43 3 6 0 55 4000 900 44 3 5 0 55 44 3 6 0 55 44 3 7 0 60 43 3 4 0 55 1219 925 44 3 3 0...

Page 16: ...0 44 3 6 0 55 44 3 7 0 60 43 3 4 0 55 43 3 5 0 55 8000 775 44 3 4 0 55 44 3 5 0 55 44 3 6 0 55 44 3 7 0 60 2438 800 44 3 2 0 50 44 3 3 0 50 44 3 4 0 55 44 3 5 0 55 825 46 3 8 0 60 45 3 7 0 60 44 3 2 0...

Page 17: ...70 1335 1300 1260 1225 1190 1155 Heating SW1 Maximum Heat Airflow 3 1075 1085 1095 1095 1090 1080 1065 1050 1035 1020 Intermediate Heat Airflow 3 535 515 505 515 495 See note 4 Minimum Heat Airflow 3...

Page 18: ...ating SW1 Maximum Heat Airflow 3 1520 1485 1450 1415 1375 1335 1300 1265 1225 1190 Intermediate Heat Airflow 3 755 745 755 755 765 See note 4 Minimum Heat Airflow 3 620 625 630 620 610 See note 4 Unit...

Page 19: ...745 740 705 680 See note 4 OFF ON OFF 930 925 915 900 885 See note 4 OFF ON ON 1095 1100 1110 1105 1085 See note 4 ON OFF OFF 1265 1255 1265 1280 1275 1285 1270 1260 1250 1230 ON OFF ON 1465 1455 1470...

Page 20: ...20 300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 4...

Page 21: ...component location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or...

Page 22: ...Status Code or 8th Code will be a heartbeat 6 Turn SW1 1 OFF 7 A heartbeat amber LED will appear and indicates proper operation 8 Release blower door switch install blower door and or refer to the SER...

Page 23: ...water leakage sagging pipes or broken fittings Have vent pipes vent system serviced by a qualified service agency 6 Inspect any accessories attached to the furnace such as a humidifier or electronic a...

Page 24: ...er reassembly d Remove screws securing cutoff plate and remove cutoff plate from housing e Remove bolts holding motor mounts to blower housing and slide motor and mounts out of housing f Remove blower...

Page 25: ...ing the mounting to the burner assembly Refer to Figure 9 1 Disconnect power at external disconnect fuse or circuit breaker 2 Turn off gas at external shut off or gas meter 3 Remove outer doors and se...

Page 26: ...iew L12F041 2 in 2 5 mm 3 8 in 3 16 in 0 8 1 5 mm 50 mm 9 6 mm 4 6 mm 1 10 in 1 32 1 16 in 16 Turn power on at external disconnect fuse or circuit breaker 17 Run the furnace through two complete heati...

Page 27: ...gasket from the collector box if it did not come off when the trap was removed 9 Discard the old trap gasket 10 Rinse condensate trap in warm water until trap is clean 11 Flush condensate drain lines...

Page 28: ...eat Exchangers The condensing side inside of the secondary heat exchanger CANNOT be serviced or inspected without complete removal of the heat exchanger assembly Detailed information on heat exchanger...

Page 29: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MAE Specifications subject to change without notice 440 04 4700 00 29 Figure 14 Service Label 338316 2 Rev I...

Page 30: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F G 9MAE Specifications subject to change without notice 30 440 04 4700 00 Figure 15 Wiring Diagram 338316 2 Rev I...

Page 31: ...hen done put setup switch SW1 1 in the OFF position Was there a previous status code other than the heartbeat Go to section below for the status code that was flashed Does the control respond to W W1...

Page 32: ...eck in maximum heat If burners will still not stay on replace control If burners operate in maximum heat then switch to intermediate heat check manifold pressure If OK check burner carryover and flame...

Page 33: ...d If you have a digital voltmeter with a bar graph it will show a large change in magnitude on the bar graph several times a second If you have a standard digital voltmeter it will show a brief fluctu...

Page 34: ...aximum heat The furnace will transition and operate at minimum heat or the calculated modulating rate after starting and operating for 45 seconds at intermediate heat The furnace control CPU defaults...

Page 35: ...gh pressure switch HPS should close Switching from Medium Range Input to Maximum Heat If the furnace control CPU switches from medium range input to maximum heat the furnace control CPU will increase...

Page 36: ...tarts the furnace blower motor BLWM at low cooling airflow which is the true on board CF selection as shown in Figure 4 Table 3 and Table 6 The R to Y1 and Y2 circuits start the outdoor unit on high c...

Page 37: ...ergized along with Y1 or Y Y2 the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow minimum heat airflow or the mid range airflow whichever is lowest The blow...

Page 38: ...odule when used Inducer motor capacitor when used Collector box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to fo...

Page 39: ...e stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard L Low Nox FEATURE 060 6...

Reviews: