background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: F9MES

Specifications  subject to change without notice.

12

440 04 4900 02

Checklist

1. Put away tools and instruments. Clean up debris.

2. Verify that the jumper is removed from the TEST/TWIN

terminal. Verify that there is nothing plugged into the PLT

connector.

NOTE

:  If there is a jumper connector plugged into PLT, remove

it and discard. (See 

Figure 4

)

3. Verify that the Blower/Heat Off Delay jumpers are set as

desired. (See 

Figure 4

 and 

Figure 15

)

4. Verify that the blower (lower door in upflow position) and

control (“Main” or upper door in upflow position) doors

are properly installed.

5. Verify that the Status LED has heartbeat (bright

dim). If

not, check that the power supply is energized and that

the blower door is secure. See 

Figure 14 

to interpret

diagnostic codes

.

6. Cycle test furnace with room thermostat to be sure that it

operates properly with the room thermostat. Check all

modes including Heat, Cool and Fan.

7. Check operation of accessories per manufacturer’s

instructions.

8. Review Home Owner’s Information with owner.

9. Attach entire literature packet to furnace.

Table 5

COOLING AIR DELIVERY - CFM and L/s (with filter

 

1

)

UNIT SIZE

RETURN-AIR-

CONNECTION

WIRE COLOR

COOLING

TONS

AIRFLOW DELIVERY @ EXTERNAL STATIC PRESSURE (in. w.c.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

CFM

1002120

BOTTOM or

TWO-SIDES 

3,4

Black

5.0

2260

2215

2165

2115

2065

2010

1950

1890

1825

1750

Blue

5.0

2140

2100

2050

2005

1960

1915

1855

1800

1740

1680

Yellow

4.0

1815

1775

1735

1690

1645

1600

1545

1490

1420

1405

Orange

3.5

1665

1625

1575

1535

1495

1455

1410

1355

1300

1245

Red

3.5

1515

1475

1435

1390

1350

1310

1260

1210

1160

1110

1202420

BOTTOM or

TWO-SIDES 

3,4

Black

5.0

2215

2160

2105

2050

1990

1925

1855

1785

1720

1655

Blue

5.0

2070

2020

1975

1920

1860

1800

1735

1675

1615

1560

Yellow

4.0

1770

1725

1680

1630

1570

1520

1465

1420

1370

1315

Orange

3.5

1595

1550

1505

1455

1410

1365

1315

1270

1215

1170

Red 

5

3.5

1460

1415

1365

1315

1270

1230

1180

1130

1075

1015

1402420

BOTTOM or

TWO-SIDES 

3,4

Black

5.0

2195

2145

2090

2035

1980

1915

1855

1795

1735

1675

Blue

5.0

2055

2005

1955

1905

1850

1795

1740

1685

1630

1575

Yellow

4.0

1755

1710

1660

1610

1565

1515

1465

1415

1365

1310

Orange 

5

3.5

1590

1540

1495

1450

1400

1355

1310

1260

1205

1145

Red 

5

3.5

1450

1400

1355

1310

1265

1220

1175

1120

1060

1015

UNIT SIZE

RETURN-AIR-

CONNECTION

WIRE COLOR

COOLING

TONS

AIRFLOW DELIVERY @ EXTERNAL STATIC PRESSURE (in. w.c.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

L/s

1002120

BOTTOM or

TWO-SIDES

3,4

Black

5

1065

1045

1020

995

970

945

920

890

860

825

Blue

5

1005

990

965

945

925

900

875

845

820

790

Yellow

4

855

835

815

795

775

755

725

700

670

660

Orange

3.5

785

765

740

720

705

685

665

635

610

585

Red

3.5

715

695

675

655

635

615

590

570

545

520

1202420

BOTTOM or

TWO-SIDES

3,4

Black

5

1045

1015

990

965

935

905

875

840

810

780

Blue

5

975

950

930

905

875

845

815

790

760

735

Yellow

4

835

810

790

765

740

715

690

670

645

620

Orange

3.5

750

730

710

685

665

640

620

595

570

550

Red 

5

3.5

685

665

640

620

595

580

555

530

505

475

1402420

BOTTOM or

TWO-SIDES

3,4

Black

5

1035

1010

985

960

930

900

875

845

815

790

Blue

5

965

945

920

895

870

845

820

795

765

740

Yellow

4

825

805

780

755

735

715

690

665

640

615

Orange 

5

3.5

750

725

705

680

660

635

615

590

565

540

Red 

5

3.5

680

660

635

615

595

575

550

525

500

475

NOTE

:  

1. A filter is required for each return

air inlet. Airflow performance includes a 3/4 in. (19 mm) washable filter media such as contained in

factory

authorized accessory filter rack. See accessory list. To determine airflow performance without this filter, assume an additional 0.1 in. w.c.

available external static pressure.

2. Blower speed taps are not always in the same order. Factory Default blower connections are as follows:

Heating airflow 

 BLUE  (also used for Continuous Fan)

Cooling airflow 

 BLACK  (enabled when the Y terminal is energized)

ADJUST THE BLOWER SPEED TAPS AS NECESSARY FOR THE PROPER AIR TEMPERATURE RISE FOR EACH INSTALLATION.

3. Airflows over 1800 CFM require bottom return, two

side return, or bottom and side return. A minimum filter size of 20” x 25” (508 x 635 mm) is

required.

4. For upflow applications, air entering from one side into both the side of the furnace and a return air base counts as a side and bottom return.

5. Highlighted areas indicate that this airflow range is beyond the range allowed for heating. 

THESE AIRFLOW RANGES MAY ONLY BE USED

FOR COOLING.

Summary of Contents for F9MES Series

Page 1: ...this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used through...

Page 2: ...d result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which w...

Page 3: ...d ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 Position Time Off Position Time Off 90 108 120...

Page 4: ...ates HUM 220vac terminal is only energized when the draft inducer is energized in heating HUM 24vac terminal is only energized on a call for heat W and the LPS is closed Prime Condensate Trap with Wat...

Page 5: ...ific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find inst...

Page 6: ...r natural gas If required manifold pressure is outside this range change main burner orifices h When correct input is obtained replace cap that conceal gas valve regulator adjustment screw Main burner...

Page 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 220 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 220 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Page 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Page 9: ...CE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 9 Table 3 Orifice Size and Manifold Pressure in w c for Gas Input Rate Single Stage L12...

Page 10: ...ometers in return and supply ducts as close to furnace as possible Be sure thermometers do not see heat exchangers so that radiant heat does not affect thermometer readings This is particularly import...

Page 11: ...sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and...

Page 12: ...1955 1905 1850 1795 1740 1685 1630 1575 Yellow 4 0 1755 1710 1660 1610 1565 1515 1465 1415 1365 1310 Orange 5 3 5 1590 1540 1495 1450 1400 1355 1310 1260 1205 1145 Red 5 3 5 1450 1400 1355 1310 1265...

Page 13: ...t location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring Pressure Switches Each pressure switch is labeled with the reference location noted as COLLECTOR BOX LPS o...

Page 14: ...interpret the LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time ex...

Page 15: ...connections for tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust I...

Page 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Page 17: ...ld or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and ele...

Page 18: ...ontrol door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas...

Page 19: ...to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas on at electric switch on...

Page 20: ...C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 21 Figure 14 Service Label 339462 2 Rev A...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 22 440 04 4900 02 339542 2 Rev A...

Page 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 23 Figure 15 Wiring Diagram 339462 2 Rev A...

Page 24: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 24 440 04 4900 02 339542 2 Rev A...

Page 25: ...equence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individua...

Page 26: ...onent test Does the igniter glow orange white by the end of the 18 second warm up period Unplug igniter harness from control and repeat component test Check for 220V between connector P2 HSI and NEUTR...

Page 27: ...the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermos...

Page 28: ...injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may...

Reviews: