SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: F9MES

Specifications  subject to change without notice.

440 04 4900 02

11

Change the blower speed taps as required to maintain proper

temperature rise for Heating and Cooling as described above.

To change blower motor speed selections for heating mode,

remove blower motor lead from control HEAT terminal(s). (See

Figure 4

) Select desired blower motor speed lead(s) from the

other motor leads and relocate it/them to HEAT (heating blower

tap) terminal(s). Reconnect original lead on SPARE terminal.

Adjust Blower Off Delay (Heat Mode)

If desired, the main blower off time delay period may be

lengthened or shortened when operating in the heating mode

to provide greater comfort. For position and location of jumpers

on control center. (See 

Figure 4

 and 

Figure 15

)

The blower off-delay has four adjustable settings from 108 sec

to 216 sec. (See 

Table 4

) To change the blower off delay

setting, move the jumper from one set of pins on the control to

the pins used for the desired blower off delay. Factory blower

off-delay setting is 144 sec.

Table 4

Blower Off Delay Jumper Positions

PINS

1 AND 2

2 AND 3

3 AND 4

4 AND 5

Control

(swtich setting)

90

120

150

180

Time (in sec.)

108

144

180

216

Adjust Cooling Airflow

The cooling airflow can be set from the remaining blower speed

taps. Refer to the Air Delivery Tables in these instructions.

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reduced furnace

life.
Recheck temperature rise. It must be within limits specified

on the rating plate. Recommended operation is at the

mid--point of rise range or slightly above.

CAUTION

!

Adjust Thermostat Heat Anticipator

Mechanical thermostat:

 Set thermostat heat anticipator to

match the amp. draw of the electrical components in the R-W

circuit. Accurate amp. draw readings can be obtained at the

wires normally connected to thermostat sub-base terminals, R

and W. The thermostat anticipator should NOT be in the circuit

while measuring current.

1. Remove thermostat from sub-base or from wall.
2. Connect an amp. meter across the R and W sub-base

terminals or R and W wires at wall.

3. Record amp. draw across terminals when furnace is in

low heat and after blower starts.

4. Set heat anticipator on thermostat per thermostat

instructions and install on sub-base or wall.

5. Install blower access door.

Electronic thermostat:

 Set cycle rate for 3 cycles per hr.

Figure 5

Amp. Draw Check with Ammeter

A96316

R Y W G

10 TURNS

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

(ANITICIPATOR, CLOCK, ETC.,

MUST BE OUT OF CIRCUIT.)

HOOK-AROUND

AMMETER

EXAMPLE: 5.0 AMPS ON AMMETER

10 TURNS AROUND JAWS

 

=  0.5 AMPS FOR THERMOSTAT

     ANTICIPATOR SETTING

FROM UNIT 24-V

CONTROL TERMINALS

Check Safety Controls

The flame sensor, gas valve, and pressure switch were all

checked in the Start

up procedure section as part of normal

operation.

1. Check Main Limit Switch 

This control shuts off combustion system and energizes

air

circulating blower motor, if furnace overheats. By

using this method to check the temperature limit control,

it can be established that the limit is functioning properly

and that the limit will operate if there is a restricted

return

air supply or motor failure. If the limit control does

not function during this test, the cause must be

determined and corrected.

a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of

cardboard or sheet metal until the limit trips.

c. Unblock return air to permit normal circulation.

d. Burners will re

light when furnace cools down.

2. Check Pressure Switch(es) 

This control proves operation of the draft inducer blower.
a. Turn off 220

V 50Hz power to furnace.

b. Disconnect inducer motor lead wires from wire

harness.

c. Turn on 220

V 50Hz power to furnace.

d. Set thermostat to “call for heat” and wait 1 minute.

When low pressure switch is functioning properly, hot

surface  igniter should 

NOT 

glow and control

diagnostic light flashes a status code 3.  If hot

surface igniter glows when inducer motor is

disconnected, shut down furnace immediately.

e. Determine reason low pressure switch did not

function properly and correct condition.

f. Turn off 220

V 50Hz power to furnace.

g. Reconnect inducer motor wires, replace  door, and

turn on 220

V 50Hz power.

h. Blower will run for 108 seconds before beginning the

call for heat again.

i. Furnace should ignite normally.

Summary of Contents for F9MES Series

Page 1: ...this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used through...

Page 2: ...d result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which w...

Page 3: ...d ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 Position Time Off Position Time Off 90 108 120...

Page 4: ...ates HUM 220vac terminal is only energized when the draft inducer is energized in heating HUM 24vac terminal is only energized on a call for heat W and the LPS is closed Prime Condensate Trap with Wat...

Page 5: ...ific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find inst...

Page 6: ...r natural gas If required manifold pressure is outside this range change main burner orifices h When correct input is obtained replace cap that conceal gas valve regulator adjustment screw Main burner...

Page 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 220 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 220 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Page 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Page 9: ...CE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 9 Table 3 Orifice Size and Manifold Pressure in w c for Gas Input Rate Single Stage L12...

Page 10: ...ometers in return and supply ducts as close to furnace as possible Be sure thermometers do not see heat exchangers so that radiant heat does not affect thermometer readings This is particularly import...

Page 11: ...sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and...

Page 12: ...1955 1905 1850 1795 1740 1685 1630 1575 Yellow 4 0 1755 1710 1660 1610 1565 1515 1465 1415 1365 1310 Orange 5 3 5 1590 1540 1495 1450 1400 1355 1310 1260 1205 1145 Red 5 3 5 1450 1400 1355 1310 1265...

Page 13: ...t location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring Pressure Switches Each pressure switch is labeled with the reference location noted as COLLECTOR BOX LPS o...

Page 14: ...interpret the LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time ex...

Page 15: ...connections for tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust I...

Page 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Page 17: ...ld or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and ele...

Page 18: ...ontrol door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas...

Page 19: ...to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas on at electric switch on...

Page 20: ...C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 21 Figure 14 Service Label 339462 2 Rev A...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 22 440 04 4900 02 339542 2 Rev A...

Page 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 23 Figure 15 Wiring Diagram 339462 2 Rev A...

Page 24: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 24 440 04 4900 02 339542 2 Rev A...

Page 25: ...equence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individua...

Page 26: ...onent test Does the igniter glow orange white by the end of the 18 second warm up period Unplug igniter harness from control and repeat component test Check for 220V between connector P2 HSI and NEUTR...

Page 27: ...the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermos...

Page 28: ...injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may...