background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: F9MES

Specifications  subject to change without notice.

4

440 04 4900 02

START

UP, ADJUSTMENT, AND SAFETY

CHECK

NOTICE

IMPORTANT INSTALLATION AND START

UP

PROCEDURES

Failure to follow this procedure may result in a nuisance smoke

or odor complaint.

The manifold pressure, gas rate by meter clocking, temperature

rise and operation must be checked after installation. Minor

smoke and odor may be present temporarily after start

up from

the manufacturing process. Some occupants are more

sensitive to this minor smoke and odor. It is recommended that

doors and windows be open during the first heat cycle.

General

1. Furnace must have a 220

V 50Hz power supply properly

connected and grounded.

NOTE

:  Proper polarity must be maintained for 220

V 50Hz

wiring. Control status indicator light flashes code 10 and

furnace does not operate if polarity is incorrect or if the furnace

is not grounded.

2. Thermostat wire connections at terminals R, W, G, and Y

must be made at 24-v terminal block on furnace control.

3. Natural gas service pressure must not exceed 0.5 psig

(14- in. w.c., 1125 Pa), but must be no less than 0.16

psig (4.5-in. w.c., 350 Pa).

4. Blower door must be in place to complete 220

V 50Hz

electrical circuit and supply power to the furnace

components.

UNIT OPERATION HAZARD

Failure to follow this caution may result in intermittent unit

operation or performance satisfaction.

These furnaces are equipped with a manual reset limit

switch in burner assembly.  This switch opens and shuts off

power to the gas valve if an overheat condition (flame

rollout) occurs in the burner assembly/enclosure.  Correct

inadequate combustion

air supply, improper gas pressure

setting, improper burner or gas orifice positioning, or

improper venting condition before resetting switch.  DO

NOT jumper this switch.

CAUTION

!

Before operating furnace, check flame rollout manual reset

switch for continuity. If necessary, press button to reset switch.
EAC

1 (220vac) terminal is energized whenever blower

operates. HUM (220vac) terminal is only energized when the

draft inducer is energized in heating.
HUM (24vac) terminal is only energized on a call for heat (W)

and the LPS is closed.

Prime Condensate Trap with Water

CARBON MONOXIDE POISONING HAZARD

Failure to follow these warnings could result in personal

injury or death.
Failure to use a properly configured trap or NOT

water-priming trap before operating furnace may allow

positive pressure vent gases to enter the structure through

drain tube. Vent gases contain carbon monoxide which is

tasteless and odorless.

!

WARNING

1. Remove upper and middle collector box drain plugs

opposite of the condensate trap.   (See 

Figure 1

)

2. Connect field-supplied 5/8-in. (16 mm) ID tube with

attached funnel (see 

Figure 1

) to upper collector box

drain connection.

3. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

4. Remove funnel; replace collector box drain plug.
5. Connect field-supplied 5/8-in. (16 mm) ID tube to middle

collector box drain port.

6. Pour one quart (liter) of water into funnel/tube. Water

should run through collector box, overfill condensate

trap, and flow into open field drain.

7. Remove funnel and tube from collector box and replace

collector box drain plug.

Figure 1

Priming Condensate Drain

L11F065

Representative drawing only, some models may vary in appearance.

Purge Gas Lines

If not previously done, purge the lines after all connections

have been made and check for leaks.

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
Never purge a gas line into a combustion chamber. Never

test for gas leaks with an open flame. Use a commercially

available soap solution made specifically for the detection

of leaks to check all connections.  A fire or explosion may

result causing property damage, personal injury or loss of

life.

!

WARNING

Adjustments

FIRE HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.

This can result in unregulated manifold pressure and result

in excess overfire and heat exchanger failures.

!

WARNING

Summary of Contents for F9MES Series

Page 1: ...this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used through...

Page 2: ...d result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which w...

Page 3: ...d ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 Position Time Off Position Time Off 90 108 120...

Page 4: ...ates HUM 220vac terminal is only energized when the draft inducer is energized in heating HUM 24vac terminal is only energized on a call for heat W and the LPS is closed Prime Condensate Trap with Wat...

Page 5: ...ific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find inst...

Page 6: ...r natural gas If required manifold pressure is outside this range change main burner orifices h When correct input is obtained replace cap that conceal gas valve regulator adjustment screw Main burner...

Page 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 220 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 220 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Page 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Page 9: ...CE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 9 Table 3 Orifice Size and Manifold Pressure in w c for Gas Input Rate Single Stage L12...

Page 10: ...ometers in return and supply ducts as close to furnace as possible Be sure thermometers do not see heat exchangers so that radiant heat does not affect thermometer readings This is particularly import...

Page 11: ...sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and...

Page 12: ...1955 1905 1850 1795 1740 1685 1630 1575 Yellow 4 0 1755 1710 1660 1610 1565 1515 1465 1415 1365 1310 Orange 5 3 5 1590 1540 1495 1450 1400 1355 1310 1260 1205 1145 Red 5 3 5 1450 1400 1355 1310 1265...

Page 13: ...t location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring Pressure Switches Each pressure switch is labeled with the reference location noted as COLLECTOR BOX LPS o...

Page 14: ...interpret the LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time ex...

Page 15: ...connections for tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust I...

Page 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Page 17: ...ld or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and ele...

Page 18: ...ontrol door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas...

Page 19: ...to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas on at electric switch on...

Page 20: ...C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 21 Figure 14 Service Label 339462 2 Rev A...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 22 440 04 4900 02 339542 2 Rev A...

Page 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 23 Figure 15 Wiring Diagram 339462 2 Rev A...

Page 24: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 24 440 04 4900 02 339542 2 Rev A...

Page 25: ...equence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individua...

Page 26: ...onent test Does the igniter glow orange white by the end of the 18 second warm up period Unplug igniter harness from control and repeat component test Check for 220V between connector P2 HSI and NEUTR...

Page 27: ...the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermos...

Page 28: ...injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may...

Reviews: