440 01 4201 03
35
Specifications subject to change without notice.
Venting Systems
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined in Locating the Vent
Termination for each appliance being placed into operation
could result in carbon monoxide poisoning or death.
For all venting configurations for this appliance and other gas
appliances placed into operation for the structure, provisions for
adequate combustion, ventilation, and dilution air must be
provided in accordance with:
U.S.A. Installations:
Section 9.3 NFPA 54/ANSI Z223.1
1
−
2009, Air for Combustion and Ventilation and applicable
provisions of the local building codes.
Canadian Installations:
Part 8 of CAN/CSA
−
B149.1
−
10.
Venting Systems and Air Supply for Appliances and all
authorities having jurisdiction.
NOTICE
RECOMMENDED SUPPORT FOR VENT TERMINATIONS
It is recommended that sidewall vent terminations of over 24
inches (0.6 M) in length or rooftop vent terminations of over
36 inches (1 M) in length be supported by EITHER the fact-
ory accessory vent termination kit or field-supplied brackets
or supports attached to the structure. A factory accessory
vent termination kit may be used for direct vent terminations.
Termination kits are available for 2-in. or 3-in. pipe. See
for available options.
A factory accessory concentric vent termination kit is available
for direct vent terminations. Concentric vent termination kits are
available for 2
−
in. and 3
−
options.
Table 12
Vent Termination Kit for Direct
Vent (2
−
pipe) Systems
Direct Vent (2
−
pipe)
Termination Kit
Termination
System
Diam. Of
Combustion Air
and Vent Pipes
in.(mm)
2
−
in (51 mm) Concentric
Vent Kit
Single Penetration
of Wall or Roof
1, 1
−
1/2, 2, or 2
−
1/2
(25, 38, 51, 64 mm)
3
−
in (76 mm) Concentric
Vent Kit
Single Penetration
of Wall or Roof
2
−
1/2, 3 or 4
(64, 76, 102 mm)
2
−
in (51 mm) Termination
Bracket Kit
2
−
Pipe
Termination
System
1, 1
−
1/2, 2, or 2
−
1/2
(25, 38, 51, 64 mm)
3
−
in (76 mm) Termination
Bracket
2
−
Pipe
Termination
System
2
−
1/2, 3 or 4
(64, 76, 102 mm)
Direct Vent / 2
−
Pipe System
In a direct vent (2
−
pipe) system, all air for combustion is taken
directly from outdoor atmosphere, and all flue products are
discharged to outdoor atmosphere. Combustion-air and vent
pipes must terminate together in the same atmospheric
pressure zone, either through the roof (preferred) or a sidewall.
for references to clearances required by
National code authorities.
NOTICE
OPTIONAL CONFIGURATION FOR COMBUSTION AIR
INLET PIPE
In applications where there is a risk of excessive moisture
entering the combustion air inlet pipe, a moisture trap may be
added to the inlet pipe to help prevent moisture from entering
the furnace from the combustion air inlet pipe. See
When sizing venting systems, the equivalent length of the
optional inlet pipe moisture trap must be taken into account.
Ventilated Combustion Air Systems
In a ventilated combustion air option, the vent terminates and
discharges the flue products directly to the outdoors similar to a
direct vent system. See
required by National code authorities.
All air for combustion is piped directly to the furnace from a
space that is well ventilated with outdoor air (such as an attic or
crawl space) and the space is well isolated from the living
space or garage. Combustion air requirements for this option
are the same as the requirements for providing outside air for
combustion for a single pipe vent system. Refer to the “Air For
Combustion and Ventilation Section.”
NOTICE
OPTIONAL VENTING BELOW THE FURNACE
The venting system may be positioned below the furnace
ONLY IF the factory accessory External Vent Trap Kit is used.
The External Vent Trap Kit is only approved for PVC/ABS
DWV venting systems.
CAREFULLY FOLLOW THE INSTRUCTIONS PROVIDED
WITH THE EXTERNAL VENT TRAP KIT FOR LAYING OUT
THE VENTING SYSTEM AND THE DRAIN SYSTEM.
The
instructions included with this furnace DO NOT APPLY to
vent systems that are located below the furnace
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined in Locating the Vent
Termination for each appliance being placed into operation
could result in carbon monoxide poisoning or death.
The instructions included with this furnace DO NOT APPLY
to vent systems that are located below the furnace.
CARE-
FULLY FOLLOW THE INSTRUCTIONS PROVIDED WITH
THE EXTERNAL VENT TRAP KIT FOR LAYING OUT THE
VENTING SYSTEM AND THE DRAIN SYSTEM when all or
part of the venting system is placed below the furnace.
Proper configuration of the venting and drain system is critic-
al when placing all or part of the venting system below the
level of the furnace. VENT GASSES COULD BE RELEASED
FROM THE DRAINAGE SYSTEM, if the instructions
provided with the External Vent Trap Kit are not followed.