background image

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

13

Part Number 670 01 1001 00

Table 5

Pipe capacity for 0.60 specific gravity natural gas

4

Install gas piping

Natural Gas:

1. See Table 5 for pipe length and diameter. Base on rated

boiler input (divide by 1,000 to obtain cubic feet per hour).
Table 5 is only for gas with specific gravity 0.60, with a
pressure drop through the gas piping of 0.30" w.c. For
additional gas pipe sizing information, see ANSI Z223.1
(B149.1 or B149.2 for Canadian installations).

2. Inlet pressure required at gas valve inlet:

Maximum: 13" w.c.

Minimum:  5" w.c.

Manifold gas pressure: 3.5" w.c.

3. Install 100% lockup gas pressure regulator in supply line if

inlet pressure exceeds 13" w.c. Adjust for 13" w.c. maximum.

Propane Gas:

1. Contact gas supplier to size pipes, tanks and 100% lockup

gas pressure regulator.

2. Adjust propane supply regulator provided by gas supplier

for 13" w.c. maximum pressure.

3. Inlet pressure required at gas valve inlet:

Maximum: 13" w.c.

Minimum:  11" w.c.

Manifold gas pressure: 10" w.c.

Gas pipe

length

(feet)

Capacity of pipe for pipe size of:

(

Capacity in standard cubic feet gas per hour

)

½"

¾"

1"

1¼"

1½"

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

860

40

63

130

245

500

760

50

56

115

215

440

670

75

45

93

175

360

545

100

38

79

150

305

460

150

31

64

120

250

380

1. Remove jacket front panel and see Figure 10 to pipe gas to

boiler.
a. Install drip leg at inlet of gas connection to boiler. Where

local utility requires drip leg to be extended to the floor, use
appropriate length of nipple between cap and tee.

b.

Install ground joint union for servicing, when required.

c. Install manual shutoff valve in gas supply piping outside

boiler jacket when required by local codes or utility
requirements.

d. In Canada — When using manual main shutoff valve, it must

be identified by the installer.

2. Support piping with hangers, not by boiler or its accessories.

3. Purge all air from gas supply piping.

4. Before placing boiler in operation, check boiler and its gas

connection for leaks.
a. Close manual main shutoff valve during any pressure

testing at less than 13" w.c.

b.

Disconnect boiler and gas valve from gas supply piping
during any pressure testing greater than 13" w.c.

Do not check for gas leaks with an open flame —
Use bubble test. Failure to use bubble test or check
for gas leaks can cause severe personal injury, death
or substantial property damage.

5. Use pipe dope compatible with propane gases. Apply sparingly

only to male threads of pipe joints so that pipe dope does not
block gas flow.

Failure to apply pipe dope as described in this manual
can result in severe personal injury, death or
substantial property damage.

Connecting gas supply piping to boiler

Figure 10

Gas supply piping

GWA

 

Gas-Fired Water Boilers – 

Boiler Manual

24

Part Number 670 01 1001 00

The boiler should be inspected and started annually,
at the beginning of the heating season, only by a
qualified service technician. In addition, the
maintenance and care of the boiler designated in
Table 6, page 22  and explained on the following pages
must be performed to assure maximum boiler
efficiency and reliability. Failure to service and
maintain the boiler and system could result in
equipment failure.
Electrical shock hazard — Turn off power to the boiler
before any service operation on the boiler except as
noted otherwise in this manual. Failure to turn off
electrical power could result in electrical shock,
causing severe personal injury or death.

The boiler contains ceramic fiber and fiberglass
materials. Use care when handling these materials
per instructions on page 23 of this manual. Failure to
comply could result in severe personal injury.

Inspect . . . . . . . . . .

Reported problems

Inspect any problems reported by owner and correct before
proceeding.

Boiler area

1. Verify that boiler area is free of any combustible materials,

gasoline and other flammable vapors and liquids.

2. Verify that boiler area (and air intake) is free of any of the

contaminants listed in Table 2 on page 5 of this manual. If any of
these are present in the boiler intake air vicinity, they must be
removed. If they cannot be removed, install combustion air piping
to the boiler in accordance with national, provincial or local
codes.

Air openings

1. Verify that combustion and ventilation air openings to the boiler

room and/or building are open and unobstructed. Check
operation and wiring of automatic combustion air dampers, if
used.

2. Verify that boiler vent discharge and air intake are clean and

free of obstructions.

Flue gas vent system

1. Visually inspect entire flue gas venting system for blockage,

deterioration or leakage. Repair any joints that show signs of
leakage in accordance with vent manufacturer’s instructions.

2. Verify that masonry chimneys are lined, lining is in good

condition, and there are not openings into the chimney.

Failure to inspect for the above conditions and have
them repaired can result in severe personal injury or
death.

Pilot and main burner flames

1. Visually inspect pilot burner and main burner flames as directed

under Section 6, page 17 of this manual.

10 Service and maintenance 

continued

Water piping

1. Check the boiler interior piping and all system piping for signs

of leaks.

2. Repair any leaks before proceeding.

Do not use petroleum-based cleaning or sealing
compounds in boiler system. Severe damage to boiler
will occur, resulting in substantial property damage.

Eliminate all system or boiler leaks. Continual fresh
makeup water will reduce boiler life. Minerals can
build up in sections, reducing heat transfer,
overheating cast iron, and causing section failure.
Leaking water may also cause severe property
damage.

Inspect . . . . . . . . . .

Boiler heating surfaces

1. Disconnect the vent pipe at the boiler draft hood and remove

draft hood after turning off power to the boiler.

2. Use a bright light to inspect the boiler flue collector and heating

surfaces.

3. If the vent pipe or boiler interior surfaces show evidence of

soot, follow “Cleaning boiler heating surfaces” in this manual
section, page 26. Remove the flue collector and clean the boiler
if necessary after closer inspection of boiler heating surfaces.

4. If there is evidence of rusty scale deposits on boiler surfaces,

check the water piping and control system to make sure the
boiler return water temperature is properly maintained (per this
manual).

5. Reconnect vent and draft hood. Replace all boiler components

before returning to service.

6. Check inside and around boiler for evidence of any leaks from

the boiler. If found, locate source of leaks and repair.

Burners and base

1. After turning off power to the boiler, remove the jacket door and

base access panel (Figure 17, item 4, page 30).

2. Inspect burners and all other components in the  boiler base.

3. If burners must be cleaned, raise rear of each burner to release

from support slot, slide forward and remove. Then brush and
vacuum the burners thoroughly, making sure all ports are free
of debris. Carefully replace all burners, making sure burner with
pilot bracket is replaced in its original position and all burners
are upright (ports up).

4. Inspect the base insulation.

The boiler contains ceramic fiber and fiberglass
materials. Use care when handling these materials
per instructions on page 23 of this manual. Failure to
comply could result in severe personal injury.

a. Verify that the insulation is intact and secure against all four

sides of the base.

If insulation is damaged or displaced, do not operate
the boiler. Replace or reposition insulation as
necessary. Failure to replace damaged insulation can
result in a fire hazard, causing severe personal injury,
death or substantial property damage.

Summary of Contents for GWA 245

Page 1: ...Hazards that will or can cause minor personal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property...

Page 2: ......

Page 3: ...ation dimensions Residential garage installation Take the following special precautions when installing the boiler in a residential garage If the boiler is located in a residential garage per ANSI Z22...

Page 4: ......

Page 5: ...n 12 inches of the ceiling the other within 12 inches of the floor as shown in the table illustrations Provide adequate combustion and ventilation air to assure proper combustion and reduce the risk o...

Page 6: ......

Page 7: ...ded with boiler 7 Temporarily plug the air elimination tapping next to supply tapping 2 Prepare boiler continued Pressure test Fill and pressure test 1 Open the shutoff valves you installed on supply...

Page 8: ......

Page 9: ...the damper blade 3 Install damper harness between damper actuator and hole in jacket left side panel See Figure 3 page 8 Use strain relief connectors and locknuts to secure both ends of damper harnes...

Page 10: ......

Page 11: ...ation Failure to prevent low return water temperature to the boiler could cause corrosion of the boiler sections or burners resulting in severe personal injury death or substantial property damage Ins...

Page 12: ......

Page 13: ...8 79 150 305 460 150 31 64 120 250 380 1 Remove jacket front panel and see Figure 10 to pipe gas to boiler a Install drip leg at inlet of gas connection to boiler Where local utility requires drip leg...

Page 14: ......

Page 15: ...ragm type or bladder type expansion tank systems only one turn 5 Open other vents a Starting on the lowest floor open air vents one at a time until water squirts out b Repeat with remaining vents 6 Re...

Page 16: ......

Page 17: ...to verify operation 5 Return thermostat to normal setting 6 Set thermostat heat anticipator setting indicated on wiring diagram Check venting system operation 1 With boiler firing hold a candle or mat...

Page 18: ......

Page 19: ...d on boiler Vent damper will remain closed until a call for heat 2 Call for heat When thermostat circuit closes the boiler circulator and vent damper are energized The vent damper drives open When the...

Page 20: ......

Page 21: ...inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Stop Read the safety information above on this label 2 Set the thermostat to lowes...

Page 22: ......

Page 23: ...lace it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fre...

Page 24: ......

Page 25: ...tomatic air vents in systems with closed type tanks The air will escape from the system instead of returning to the tank Eventually the tank will waterlog and no longer control pressurization The boil...

Page 26: ......

Page 27: ...ow Lighting Instructions pages 20 and 21 If gas is available and you cannot obtain a pilot flame try purging the gas line and cleaning pilot and pilot gas tubing Follow Lighting Instructions again If...

Page 28: ......

Page 29: ...2 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 450021270WT 450021271WT 450021272WT 450021273WT 450021274WT 450021275WT 450021276WT Item number Description International Comfort Products part number 4 Hig...

Page 30: ......

Page 31: ...T 4 Jacket panel door GWA052 GWA070 GWA105 GWA140 GWA175 GWA210 GWA245 431223450WT 431223451WT 431223452WT 431223453WT 431223454WT 431223455WT Item number Description International Comfort Products pa...

Page 32: ......

Page 33: ...rt number Standing pilot Natural gas components 1 Gas valve 1 2 x 1 2 GWA052 through GWA175 Gas valve 3 4 x 3 4 GWA210 and GWA245 Honeywell Robertshaw Honeywell VR8200A2116 7200ER VR8300C4050 51104436...

Page 34: ......

Page 35: ...after the model number designates natural gas The letter after the N designates the pilot ignition system S for standing pilot or I for spark ignited pilot For example a suffix NS means a natural sta...

Page 36: ......

Reviews: