Installation
iDRY iRDP CT 20-500
25
9.5 Electrical
connections
Danger
!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the type plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
iDRY iRDP CT 20-500 dryers are supplied with a power cord and safety plug (two-pole and earth connection). or with
a junction box on the back plate.
Make sure that suitable fuses or circuit breakers in accordance with the indications on the type plate are available.
A residual-current device (RCD) with I
n =0.03A is suggested. The cross-section of the power supply cable must
correspond to the power consumption of the dryer. In this respect, the ambient temperature, the cable laying
conditions, the length of the cables and the requirements of the local electricity supplier need to be considered.
Danger!
Supply voltage and missing earth connection!
Important: ensure that the plant is connected to earth-ground.
Do not use plug adapters at the power plug.
Possible replacement of the power plug must only be carried out by a qualified electrician.
9.6 Condensate
drain
Danger
!
Compressed air and condensate under pressure!
The condensate is discharged at system pressure.
The drain pipe needs to be secured.
Never direct the condensate drain pipe at persons.
The dryer is delivered with an already integrated electronically level-controlled iMAT condensate drain. Connect the
condensate drain with a collection system or container by properly screwing it on.
Do not connect the drain with pressurised plants.
Do not discharge the condensate into the environment.
The condensate accumulating in the dryer contains oil particles which were released into the air by the
compressor.
Dispose of the condensate in accordance with the local provisions.
It is advisable to install a water-oil separator, to which the total amount of condensate from the
compressors, dryers, tanks, filters etc. is supplied.
We recommend ÖWAMAT oil-water separators for dispersed compressor condensate and BEKOSPLIT
emulsion-splitting plants for emulsified condensate.
Summary of Contents for iDRY iRDP CT 100
Page 29: ...Technical data iDRY iRDP CT 20 500 29 11 2 Technical data iDRY iRDP CT 20 500 2 1 230 60...
Page 38: ...Maintenance troubleshooting spare parts and dismantling 38 iDRY iRDP CT 20 500...
Page 39: ...Maintenance troubleshooting spare parts and dismantling iDRY iRDP CT 20 500 39...
Page 42: ...Appendices 42 iDRY iRDP CT 20 500 13 1 2 Dryer dimensions iDRY iRDP CT 75...
Page 43: ...Appendices iDRY iRDP CT 20 500 43 13 1 3 Dryer dimensions iDRY iRDP CT 100 150...
Page 44: ...Appendices 44 iDRY iRDP CT 20 500 13 1 4 Dryer dimensions iDRY iRDP CT 200 250...
Page 45: ...Appendices iDRY iRDP CT 20 500 45 13 1 5 Dryer dimensions iDRY iRDP CT 300 350...
Page 46: ...Appendices 46 iDRY iRDP CT 20 500 13 1 6 Dryer dimensions iDRY iRDP CT 400 500...
Page 47: ...Appendices iDRY iRDP CT 20 500 47 13 1 7 Dryer dimensions iDRY iRDP CT 200 250 3phase...
Page 48: ...Appendices 48 iDRY iRDP CT 20 500 13 1 8 Dryer dimensions iDRY iRDP CT 300 350 3phase...
Page 49: ...Appendices iDRY iRDP CT 20 500 49 13 1 9 Dryer dimensions iDRY iRDP CT 400 500 3phase...
Page 51: ...Appendices iDRY iRDP CT 20 500 51 13 2 2 Exploded diagram iDRY iRDP CT 20 30...
Page 52: ...Appendices 52 iDRY iRDP CT 20 500 13 2 3 Exploded diagram iDRY iRDP CT 50...
Page 53: ...Appendices iDRY iRDP CT 20 500 53 13 2 4 Exploded diagram iDRY iRDP CT 75...
Page 54: ...Appendices 54 iDRY iRDP CT 20 500 13 2 5 Exploded diagram iDRY iRDP CT 100...
Page 55: ...Appendices iDRY iRDP CT 20 500 55 13 2 6 Exploded diagram iDRY iRDP CT 125 150...
Page 56: ...Appendices 56 iDRY iRDP CT 20 500 13 2 7 Exploded diagram iDRY iRDP CT 200 250...
Page 57: ...Appendices iDRY iRDP CT 20 500 57 13 2 8 Exploded diagram iDRY iRDP CT 300 350...
Page 58: ...Appendices 58 iDRY iRDP CT 20 500 13 2 9 Exploded diagram iDRY iRDP CT 400 500...
Page 59: ...Appendices iDRY iRDP CT 20 500 59 13 2 10 Exploded diagram iDRY iRDP CT 200 250 3phase...
Page 60: ...Appendices 60 iDRY iRDP CT 20 500 13 2 11 Exploded diagram iDRY iRDP CT 300 350 3phase...
Page 61: ...Appendices iDRY iRDP CT 20 500 61 13 2 12 Exploded diagram iDRY iRDP CT 400 500 3phase...