Printed in U.S.A.
441 01 2613 06
July 2010
INSTALLATION INSTRUCTIONS
80% Single Stage, Category I, Gas Furnace
N8MPN, N8MPL, C8MPN, H8MPN, T8MPN,
C8MPL, H8MP
L
, T8MPL
(Upflow/Downflow/Horizontal)
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words
DANGER, WARNING
,
CAUTION
,
and
NOTE
are used to identify levels of hazard
seriousness. The signal word
DANGER
is only used
on product labels to signify an immediate hazard.
The signal words
WARNING
,
CAUTION
, and
NOTE
will be used on product labels and throughout this
manual and other manual that may apply to the
product.
DANGER
−
Immediate hazards which will result in
severe personal injury or death.
WARNING
−
Hazards or unsafe practices which
could result in severe personal injury or death.
CAUTION
−
Hazards or unsafe practices which may
result in minor personal injury or product or property
damage.
NOTE
−
Used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
!
WARNING
Signal Words in Manuals
The signal word
CAUTION
is used throughout
this manual in the following manner:
!
CAUTION
Signal Words on Product Labeling
Signal words are used in combination with
colors and/or pictures or product labels.
The signal word
WARNING
is used throughout
this manual in the following manner:
Safety
−
alert symbol
When you see this symbol on the unit and in
instructions or manuals, be alert to the
potential for personal injury.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
2
. . . . . . . . . . . . . . . . . . .
Safe Installation Requirements
4
. . . . . . . . . . . . . . . . . .
INSTALLATION
5
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Side Venting
9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Combustion & Ventilation Air
10
. . . . . . . . . . . . . . . . . . . .
Gas Vent Installation
13
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Venting (Horizontal)
14
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Masonry Chimney Venting (Chimney Adapter)
16
. . . .
Gas Supply and Piping
19
. . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Wiring
22
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ductwork and Filter
23
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checks and Adjustments
28
. . . . . . . . . . . . . . . . . . . . . . .
Furnace Maintenance
33
. . . . . . . . . . . . . . . . . . . . . . . . . .
Sequence of Operation & Diagnostics
34
. . . . . . . . . . . .
Technical Support Manual
36
. . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram
43
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
International Comfort Products, LLC
Lewisburg, TN 37091 U.S.A.
!
WARNING
PERSONAL INJURY, AND/OR PROPERTY
DAMAGE HAZARD
Failure to carefully read and follow this warning could
result in equipment malfunction, property damage,
personal injury and/or death.
Installation or repairs made by unqualified persons
could result in equipment malfunction, property
damage, personal injury and/or death.
The information contained in this manual is intended for
use by a qualified service technician familiar with safety
procedures and equipped with proper tools and test
instruments.
Installation must conform with local building codes and
with the Natural Fuel Gas Code (NFCG) NFPA 54/ANSI
Z223.1, and National standards of Canada
CAN/CSA
−
B149.1 and .2 Natural Gas and Propane
Installation Codes.
INSTALLER:
Affix these instructions on or adjacent to the
furnace.
CONSUMER:
Retain these instructions for future refer-
ence.
Portions of the text and tables are reprinted from NFPA 54 /ANSI Z223.1
−
2009
©
, with permission of National Fire Protection Association, Quincy, MA 02269 and American Gas Association, Washington,
DC 20001. This reprinted material is not the complete and official position of the NFPA or ANSI, on the referenced subject, which is represented only by the standard in its entirety.