SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: N9MSB

Specifications  subject to change without notice.

440 04 4413 00

19

5. Attach a funnel with a flexible tube to port on the collector

box.

6. Flush inside of collector box with water until discharge

water from condensate trap is clean and runs freely.

7. Repeat steps 4 through 6 with middle plug on upper

corner of collector box.

8. Remove the pressure switch tube from the collector box.

NOTE

:  Do 

NOT 

blow into tube with tube connected to the

pressure switch.

9. Clean pressure switch port on collect box with a small

wire. Shake any water out of pressure switch tube.

10. Reconnect tube to pressure switch and pressure switch

port.

11. Remove the relief tube from the port on the collector box

and the trap.

12. Clean the relief port on collect box and the trap with a

small wire. Shake any water out of the tube.

13. Reconnect relief tube to trap and collector box ports.

Cleaning Condensate Drain and Trap

NOTE

:  If the condensate trap is removed, a new gasket

between the trap and collector box is required. Verify a

condensate trap gasket is included in the service kit or obtain
one from your local distributor.

1. Disconnect power at external disconnect, fuse or circuit

breaker.

2. Turn off gas at external shut-off or gas meter.
3. Remove control door and set aside.
4. Turn electric switch on gas valve to OFF.
5. Disconnect external drain from condensate drain elbow

or drain extension pipe inside the furnace and set aside.

6. Disconnect the condensate trap relief hose from collector

box port and condensate trap.

NOTE

:  If condensate has a heat pad attached to the trap,

trace the wires for the pad back to the connection point and
disconnect the wires for the heat pad.

7. Remove the screw that secures the condensate trap to

the collector box, remove the trap and set aside.

8. Remove the trap gasket from the collector box if it did not

come off when the trap was removed.

9. Discard the old trap gasket.

10. Rinse condensate trap in warm water until trap is clean.

11. Flush condensate drain lines with warm water.

Remember to check and clean the relief port on the

collector box.

12. Shake trap dry.
13. Clean port on collector box with a small wire.

To re-install Condensate Drain and Trap:

1. Remove adhesive backing from condensate trap gasket
2. Install gasket on collector box
3. Align the condensate trap with the drain opening on the

collector box and secure the trap with the screw

4. Attach the relief hose to the relief port on the condensate

trap and collector box.

5. Secure tubing to prevent any sags or traps in the tubing.
6. Connect condensate drain elbow or drain extension

elbow to the condensate trap

7. Connect the leads of the condensate heat pad (if used)
8. Connect external drain piping to the condensate drain

elbow or drain extension pipe.

9. Turn gas on at electric switch on gas valve and at

external shut-off or meter

10. Turn power on at external disconnect, fuse or circuit

breaker.

11. Run the furnace through two complete heating cycles to

check for proper operation

12. Install control door when complete.

Checking Heat Pad Operation (If Applicable)

In applications where the ambient temperature around the

furnace is 32

_

F (0

_

C) or lower, freeze protection measures are

required. If this application is where heat tape has been

applied, check to ensure it will operate when low temperatures

are present.

NOTE

:  The Heat Pad, when used, should be wrapped around

the condensate drain trap. There is no need to use heat tape

within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of
the tape. Check the following:

1. Check for signs of physical damage to heat tape such as

nicks, cuts, abrasions, gnawing by animals, etc.

2. Check for discolored heat tape insulation. If any damage

or discolored insulation is evident, replace heat tape.

3. Check that heat tape power supply circuit is on.

Cleaning Heat Exchangers

The following items must be performed by a qualified service

technician.

Primary Heat Exchangers

If the heat exchangers get an accumulation of light dirt or dust

on the inside, they may be cleaned by the following procedure:

NOTE

:  If the heat exchangers get a heavy accumulation of

soot and carbon, both the primary and secondary heat
exchangers should be replaced rather than trying to clean them

thoroughly due to their intricate design. A build

up of soot and

carbon indicates that a problem exists which needs to be
corrected, such as improper adjustment of manifold pressure,

insufficient or poor quality combustion air, improper vent
termination, incorrect size or damaged manifold orifice(s),
improper gas, or a restricted heat exchanger (primary or

secondary). Action must be taken to correct the problem.

1. Turn off gas and electrical supplies to furnace.
2. Remove control door.
3. Disconnect wires or connectors to flame rollout switch,

gas valve, igniter, and flame sensor.

4. Using backup wrench, disconnect gas supply pipe from

furnace gas control valve.

5. Remove two screws attaching top filler plate and rotate

upwards to gain access to screws attaching burner

assembly to cell panel.

6. Remove screws attaching burner assembly to cell panel.

(See 

Figure 9

)

NOTE

:  Burner cover, manifold, gas valve, and burner

assembly should be removed as one assembly.

7. Clean heat exchanger openings with a vacuum and a

soft brush. (See 

Figure 12

)

Summary of Contents for N9MSB0401410C

Page 1: ...The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for pe...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...am of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5...

Page 4: ...is energized whenever blower operates HUM 24vac terminal is only energized the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follo...

Page 5: ...has the correct orifice installed At higher altitudes or different gas heat contents it may be necessary to change the factory orifice to a different orifice Tables have been provided in the furnace S...

Page 6: ...rewdriver counterclockwise out to decrease input rate or clockwise in to increase input rate NOTICE DO NOT set low heat manifold pressure less than 2 8 in w c 697 Pa or more than 3 8 in w c 947 Pa for...

Page 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 115 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Page 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Page 9: ...42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219...

Page 10: ...ding Leaving blower door off will result in incorrect temperature measurements due to possible changes in duct static pressure and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may resu...

Page 11: ...e terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base te...

Page 12: ...2 5 394 1030 1025 1030 1010 985 940 905 855 805 735 801716C SIDE BOTTOM Black 4 0 389 1650 1620 1640 1605 1555 1495 1425 1345 1255 1165 Yellow 3 5 381 1420 1425 1400 1370 1335 1290 1230 1170 1095 1015...

Page 13: ...nominal break point of each switch is shown on the label below the reference location in inches of water column W C The maximum and minimum break point of the switch is 0 05 inches of water column fro...

Page 14: ...LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time except the gas v...

Page 15: ...rvice as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspe...

Page 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Page 17: ...old or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and el...

Page 18: ...ck for proper operation 18 Install control door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Fig...

Page 19: ...6 Connect condensate drain elbow or drain extension elbow to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or...

Page 20: ...ratures may be 32_ F 0_ C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate...

Page 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 440 04 4413 00 21 Figure 14 Service Label 338310 2 Rev F...

Page 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 22 440 04 4413 00 Figure 15 Wiring Diagram 339241 2 Rev A...

Page 23: ...quence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individual...

Page 24: ...onent test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTR...