background image

13

443 06 2403 01

Specifications  subject to change without notice.

Figure 13 

 

Auxiliary Door Switch

Two

Stage Heat with Two

stage Gas

Heat Thermostat

(Field Supplied)
NOTE

:  ALL thermostat connections are to be made to LH

furnace control ONLY. (See Figure 16)

NOTE

:  This application allows only the LH furnace to operate

for first

stage heat mode or both furnaces to operate for

second

stage heat mode as determined by a two

stage

thermostat. See furnace Installation, Start

Up, and Operating

Instructions for further details on this heating mode.
To operate furnaces in two

stage heating mode when a

two

stage thermostat controls the staging, install twinning kit

as described in Single

Stage Heat with Single

Stage Gas

Heat Thermostat, then modify TKR wiring as follows:

a. Disconnect TKR white wire labeled W from the LH

furnace control thermostat connection W.

b. Cut off terminal of TKR white wire labeled W and

strip 1/4 in. (6 mm).

c. Connect two

stage thermostat W2 connection to

TKR white wire labeled W.

PERSONAL INJURY HAZARD

Failure to follow this caution could result in intermittent

furnace operation and unit damage.
Supply

air temperature will be uneven left

to

right

when only main system is operating.

CAUTION

!

NOTE

:  ALL other two

stage thermostat connections are to be

made to LH furnace control ONLY. (See Figure 16)

B. All Two

Stage Models: F8MTL & G8MTL Two

Speed

Non

Condensing HSI Furnaces with PSC Motors

See Electrostatic Discharge Precaution Section.
The twinning kit can be used for single

stage or two

stage

heating operation. There are 3 harness assemblies included in

this kit. If the furnaces are side

by

side, only 2 harness

assemblies are required. If the furnaces are installed

back

to

back, all 3 harness assemblies included in the kit

must be used.

FIRE HAZARD

Failure to follow this warning could result in fire,

personal injury or death.
Make no connections between the R 24

vac connector

in 1 furnace and the R 24

vac connector in other

furnace.

!

WARNING

1. Remove outer doors and blower access doors from both

furnaces.

2. If furnaces are installed back

to

back in any orientation,

the external Extension Harness must be used. The

harness consists of:
a. 54

1/2

in.  of 1/2

in. flexible steel conduit

b. (2) 90

_

 conduit connectors

c. (2) 4 wire polarized wiring harness

d. (2) 2 wire polarized wiring harness

3. Install the Extension Harness as follows:

a. Remove lock nuts from the end of each conduit

connector.

b. Route the end of the harness labeled “Twinning Kit

Harness” that mates to the TKR relay harness from

the outside of the furnace through the 7/8

in.

knock

out in the casing to the blower compartment.

c. Route the end of the harness that mates to the

4

wire harness through the outside of the furnace

through the 7/8

in. knockout in the casing to the

blower compartment.

d. Install the lock nuts on the 90

_

 conduit connectors.

Summary of Contents for NAHA00601WK

Page 1: ...d safety codes In some instances these instructions exceed certain local codes and ordinances especially those that may not have kept up with changing residential construction practices We require the...

Page 2: ...ion The damper should not create undue restriction in the open position All furnaces must be installed to ensure sufficient return air to both furnaces S For upflow furnaces A combination of one full...

Page 3: ...nnot obstruct access to either furnace Example 2 8 MIN Common Return Air Plenum Return Air Plenum Return Air Plenum Twinned Furnace Common Supply Air Plenum A02223 Figure 2 Downflow Horizontal Ductwor...

Page 4: ...al CAUTION 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a clean un...

Page 5: ...le Stage and Two Stage with PSC Blower Model Numbers A B C D FLUE CABINET WIDTH in mm OUTLET WIDTH in mm TOP AND BOTTOM FLUE COLLAR in mm BOTTOM INLET WIDTH in mm FLUE COLLAR in mm SHIP WT KG 0451408...

Page 6: ...approximately 1 in 25 mm below discharge flange from inside top of discharge opening and through both furnaces See Figure 6 Drill two 1 8 in holes approximately 1 in 25 mm below return air flange from...

Page 7: ...10 Drive 1 factory supplied No 6 X 3 4 in LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 11 Connect return and supply air ducts to f...

Page 8: ...drawing of twinned furnaces and their connection locations 1 Select 2 identical heating and airflow furnaces See Table 2 2 Remove outer door and blower access door 3 Remove bottom closure panels from...

Page 9: ...ace from left hand side to right hand side if required Refer to furnace installation instructions for complete details 13 Go to PROCEDURE 2A for Single Stage Furnaces or PROCEDURE 2B for Two Stage Fur...

Page 10: ...recommended for wood trusses unless approved by the truss manufacturer or other approved engineering methods 1 Furnaces may be suspended using two 2 pieces of 1 1 2 in x 1 1 2 in x 1 4 in thick cold r...

Page 11: ...e no connections between the R 24 vac connector in 1 furnace and the R 24 vac connector in other furnace WARNING See Electrostatic Discharge Precaution Section The twinning kit can be used for single...

Page 12: ...e Extension Harness 4 Install Auxiliary Limit Switch ALS S on Secondary furnace a Drill 1 8 in hole in blower housing 12 in 305 mm below blower shelf See Figure 13 b Position ALS S with terminals faci...

Page 13: ...16 B All Two Stage Models F8MTL G8MTL Two Speed Non Condensing HSI Furnaces with PSC Motors See Electrostatic Discharge Precaution Section The twinning kit can be used for single stage or two stage he...

Page 14: ...de by side route loose ends of 4 wire harness from Secondary furnace to Main furnace through snap bushings previously installed between furnaces f Connect Secondary 4 wire harness into 4 wire Main har...

Page 15: ...s the furnaces allowing them to operate as a single furnace The L1 black connection to each furnace must be connected to circuit breakers connected to the same service panel 115 vac phase leg On singl...

Page 16: ...6 101 on outside of blower access door of RH furnace blower door 5 Turn on power and gas to both furnaces 6 Reinstall blower access doors on both furnaces 7 Operate furnaces through 2 cycles in each m...

Page 17: ...443 06 2403 01 Specifications subject to change without notice Figure 16 Single Stage Furnace and A C Two Stage Thermostat Figure 17 Two Stage Furnaces and 1 Stage A C Unit One or Two Stage Thermosta...

Page 18: ...INALS HUM XFMR HUMIDIFIER TERMINAL 115 VAC 120 180 90 150 SPARE2 J2 JUMPER J2 HUM 24VAC BLW SPARE1 SPARE2 L2 NEUTRAL EAC 1 AMP IND HSI P2 L1 Figure 19 Two Stage Furnace Control SETUP SWITCHES THERMOST...

Page 19: ...t disconnect TKR yellow wire labeled TEST from LH furnace control TEST TWIN terminal After removing yellow wire component test can be initiated on each furnace individually as stated in Installation S...

Page 20: ...20 443 06 2403 01 Specifications subject to change without notice Figure 20 Wiring Diagram for Single Stage Non Condensing Furnaces...

Page 21: ...21 443 06 2403 01 Specifications subject to change without notice Figure 21 Wiring Diagram for Two Stage Non Condensing Furnaces...

Page 22: ...22 443 06 2403 01 Specifications subject to change without notice Copyright 2018 International Comfort Product S PO Box 128 S Lewisburg TN 37091 USA...

Reviews: