2
443 06 2403 01
Specifications subject to change without notice.
INTRODUCTION
IMPORTANT
: Only the furnace sizes listed in Table 2 can be
twinned. Both furnaces must have the same product number,
including heating and cooling sizes, to achieve correct
operation.
This furnace twinning kit permits connection to the following
furnaces to operate as a single unit on the same duct work:
S
Two multipoise, 33.3 inch (846 mm), single
−
speed,
non
−
condensing furnaces (See Figure 1, Figure 2 and
S
Two multipoise, 33.3 inch (846 mm), two
−
stage,
non
−
condensing furnaces (See Figure 1, Figure 14, and
UNIT AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in unit and
property damage.
A non
−
condensing furnace shall NOT be twinned with a
condensing furnace. Two
−
stage condensing or
non
−
condensing furnaces shall not be twinned with any
single stage furnace. Do not twin furnaces that have a
different number of blower motor speed taps together.
Furnaces shall only be twinned in the positions shown.
Variable
−
speed furnaces shall not be twinned.
!
WARNING
DESCRIPTION AND USAGE
Refer to the appropriate section for your furnaces.
SECTION I
: Models N8MSN & N8MSL Multipoise
Single
−
Speed Non
−
Condensing HSI Furnaces
S
Single
−
Stage Heat with Single
−
Stage Gas
−
Heat Thermostat
S
Two
−
Stage Heat with Two
−
stage Gas
−
Heat Thermostat
Models F8MTL & G8MTL Multipoise Two
−
Stage
Non
−
Condensing HSI Furnaces
S
Two
−
Stage Heat with Single
−
Stage Gas
−
Heat Thermostat
S
Two
−
Stage Heat with Two
−
Stage Gas
−
Heat Thermostat
DUCT CONNECTIONS
All furnaces must have a common supply plenum attached to
the furnaces or evaporator coils prior to any branch supply
trunk or take
−
off. The height of the plenum should be at least
as high (upflow/downflow) or as long (horizontal) as the width
of one furnace. Supply air dampers, when used should be
installed in the branch ducts, not in the common plenum. Fire
or smoke dampers, when required by code may be installed in
the common plenum. Refer to the damper manufacturer’s
ratings installation instructions for proper application. The
damper should not create undue restriction in the open
position.
All furnaces must be installed to ensure sufficient return air to
both furnaces:
S
For upflow furnaces:
A combination of one full side of each
and bottom inlet plenum or bottom only inlet plenum shall be
used for return air to each furnace. The preferred method is
to have all return air brought into the bottom of the furnaces
through a common bottom plenum. The bottom return
−
air
plenum shall be at least as high as the width of the furnace
bottom return
−
air opening. When there are height limitations,
the bottom return
−
air plenum height can be reduced to 8 in.
minimum (203mm) if one entire side return
−
air opening of
each furnace is used in conjunction with the bottom return
opening. Rear inlet plenums shall not be used. (See
Figure 1) Connect all return trunks or branch return ducts to
common return plenum.
S
For downflow and horizontal furnaces:
All return air must
be brought into the bottom opening of the furnace through a
common return air plenum. The return
−
air plenum shall be at
least as long (horizontal) or tall (downflow) as the width of
the furnace return
−
air opening. (See Figure 2) Connect all
return trunks or branch return ducts to common return
plenum.
S
For all furnaces:
Fire or smoke dampers, when required by
code may be installed in the common return plenum. Refer
to the damper manufacturer’s ratings installation instructions
for proper application. The damper should not create undue
restriction in the open position.
FIRE HAZARD
Failure to follow this warning could result in improper
auxiliary limit operation, fire, personal injury or death.
Do not remove the center return
−
air partitions between
the furnaces.
!
WARNING
Staged heating operation is permitted only with this twinning
kit. With the single
−
speed, non
−
condensing furnaces, the
left
−
hand furnace is used for first
−
stage heat, and both
furnaces are used for second
−
stage heat. With the two
−
stage,
non
−
condensing furnaces, low
−
gas heat in both furnaces is
used for first
−
stage heat, and high
−
gas heat in both furnaces is
used for second
−
stage heat. This kit ensures both furnace
blowers operate simultaneously so air flows through the duct
work rather than recirculating in a loop between the furnaces.