background image

2

443 06 2403 01

Specifications  subject to change without notice.

INTRODUCTION

IMPORTANT

: Only the furnace sizes listed in Table 2 can be

twinned. Both furnaces must have the same product number,

including heating and cooling sizes, to achieve correct

operation.
This furnace twinning kit permits connection to the following

furnaces to operate as a single unit on the same duct work:

S

Two multipoise, 33.3 inch (846 mm), single

speed,

non

condensing furnaces (See Figure 1, Figure 2 and

Table 2)

S

Two multipoise, 33.3 inch (846 mm), two

stage,

non

condensing furnaces (See Figure 1, Figure 14, and

Table 2)

UNIT AND PROPERTY DAMAGE HAZARD

Failure to follow this warning could result in unit and

property damage.
A non

condensing furnace shall NOT be twinned with a

condensing furnace.  Two

stage condensing or

non

condensing furnaces shall not be twinned with any

single stage furnace.  Do not twin furnaces that have a

different number of blower motor speed taps together.

Furnaces shall only be twinned in the positions shown.

Variable

speed furnaces shall not be twinned.

!

WARNING

DESCRIPTION AND USAGE

Refer to the appropriate section for your furnaces.

SECTION I

: Models N8MSN & N8MSL Multipoise

Single

Speed Non

Condensing HSI Furnaces

S

Single

Stage Heat with Single

Stage Gas

Heat Thermostat

S

Two

Stage Heat with Two

stage Gas

Heat Thermostat

Models F8MTL & G8MTL Multipoise Two

Stage

Non

Condensing HSI Furnaces

S

Two

Stage Heat with Single

Stage Gas

Heat Thermostat

S

Two

Stage Heat with Two

Stage Gas

Heat Thermostat

DUCT CONNECTIONS

All furnaces must have a common supply plenum attached to

the furnaces or evaporator coils prior to any branch supply

trunk or take

off. The height of the plenum should be at least

as high (upflow/downflow) or as long (horizontal) as the width

of one furnace. Supply air dampers, when used should be

installed in the branch ducts, not in the common plenum. Fire

or smoke dampers, when required by code may be installed in

the common plenum. Refer to the damper manufacturer’s

ratings installation instructions for proper application. The

damper should not create undue restriction in the open

position.

All furnaces must be installed to ensure sufficient return air to

both furnaces:

S

For upflow furnaces:

 A combination of one full side of each

and bottom inlet plenum or bottom only inlet plenum shall be

used for return air to each furnace. The preferred method is

to have all return air brought into the bottom of the furnaces

through a common bottom plenum. The bottom return

air

plenum shall be at least as high as the width of the furnace

bottom return

air opening. When there are height limitations,

the bottom return

air plenum height can be reduced to 8 in.

minimum (203mm) if one entire side return

air opening of

each furnace is used in conjunction with the bottom return

opening. Rear inlet plenums shall not be used. (See

Figure 1) Connect all return trunks or branch return ducts to

common return plenum.

S

For downflow and horizontal furnaces:

 All return air must

be brought into the bottom opening of the furnace through a

common return air plenum. The return

air plenum shall be at

least as long (horizontal) or tall (downflow) as the width of

the furnace return

air opening. (See Figure 2) Connect all

return trunks or branch return ducts to common return

plenum.

S

For all furnaces:

  Fire or smoke dampers, when required by

code may be installed in the common return plenum. Refer

to the damper manufacturer’s ratings installation instructions

for proper application. The damper should not create undue

restriction in the open position.

FIRE HAZARD

Failure to follow this warning could result in improper

auxiliary limit operation, fire, personal injury or death.
Do not remove the center return

air partitions between

the furnaces.

!

WARNING

Staged heating operation is permitted only with this twinning

kit. With the single

speed, non

condensing furnaces, the

left

hand furnace is used for first

stage heat, and both

furnaces are used for second

stage heat. With the two

stage,

non

condensing furnaces, low

gas heat in both furnaces is

used for first

stage heat, and high

gas heat in both furnaces is

used for second

stage heat. This kit ensures both furnace

blowers operate simultaneously so air flows through the duct

work rather than recirculating in a loop between the furnaces.

Summary of Contents for NAHA00601WK

Page 1: ...d safety codes In some instances these instructions exceed certain local codes and ordinances especially those that may not have kept up with changing residential construction practices We require the...

Page 2: ...ion The damper should not create undue restriction in the open position All furnaces must be installed to ensure sufficient return air to both furnaces S For upflow furnaces A combination of one full...

Page 3: ...nnot obstruct access to either furnace Example 2 8 MIN Common Return Air Plenum Return Air Plenum Return Air Plenum Twinned Furnace Common Supply Air Plenum A02223 Figure 2 Downflow Horizontal Ductwor...

Page 4: ...al CAUTION 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a clean un...

Page 5: ...le Stage and Two Stage with PSC Blower Model Numbers A B C D FLUE CABINET WIDTH in mm OUTLET WIDTH in mm TOP AND BOTTOM FLUE COLLAR in mm BOTTOM INLET WIDTH in mm FLUE COLLAR in mm SHIP WT KG 0451408...

Page 6: ...approximately 1 in 25 mm below discharge flange from inside top of discharge opening and through both furnaces See Figure 6 Drill two 1 8 in holes approximately 1 in 25 mm below return air flange from...

Page 7: ...10 Drive 1 factory supplied No 6 X 3 4 in LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 11 Connect return and supply air ducts to f...

Page 8: ...drawing of twinned furnaces and their connection locations 1 Select 2 identical heating and airflow furnaces See Table 2 2 Remove outer door and blower access door 3 Remove bottom closure panels from...

Page 9: ...ace from left hand side to right hand side if required Refer to furnace installation instructions for complete details 13 Go to PROCEDURE 2A for Single Stage Furnaces or PROCEDURE 2B for Two Stage Fur...

Page 10: ...recommended for wood trusses unless approved by the truss manufacturer or other approved engineering methods 1 Furnaces may be suspended using two 2 pieces of 1 1 2 in x 1 1 2 in x 1 4 in thick cold r...

Page 11: ...e no connections between the R 24 vac connector in 1 furnace and the R 24 vac connector in other furnace WARNING See Electrostatic Discharge Precaution Section The twinning kit can be used for single...

Page 12: ...e Extension Harness 4 Install Auxiliary Limit Switch ALS S on Secondary furnace a Drill 1 8 in hole in blower housing 12 in 305 mm below blower shelf See Figure 13 b Position ALS S with terminals faci...

Page 13: ...16 B All Two Stage Models F8MTL G8MTL Two Speed Non Condensing HSI Furnaces with PSC Motors See Electrostatic Discharge Precaution Section The twinning kit can be used for single stage or two stage he...

Page 14: ...de by side route loose ends of 4 wire harness from Secondary furnace to Main furnace through snap bushings previously installed between furnaces f Connect Secondary 4 wire harness into 4 wire Main har...

Page 15: ...s the furnaces allowing them to operate as a single furnace The L1 black connection to each furnace must be connected to circuit breakers connected to the same service panel 115 vac phase leg On singl...

Page 16: ...6 101 on outside of blower access door of RH furnace blower door 5 Turn on power and gas to both furnaces 6 Reinstall blower access doors on both furnaces 7 Operate furnaces through 2 cycles in each m...

Page 17: ...443 06 2403 01 Specifications subject to change without notice Figure 16 Single Stage Furnace and A C Two Stage Thermostat Figure 17 Two Stage Furnaces and 1 Stage A C Unit One or Two Stage Thermosta...

Page 18: ...INALS HUM XFMR HUMIDIFIER TERMINAL 115 VAC 120 180 90 150 SPARE2 J2 JUMPER J2 HUM 24VAC BLW SPARE1 SPARE2 L2 NEUTRAL EAC 1 AMP IND HSI P2 L1 Figure 19 Two Stage Furnace Control SETUP SWITCHES THERMOST...

Page 19: ...t disconnect TKR yellow wire labeled TEST from LH furnace control TEST TWIN terminal After removing yellow wire component test can be initiated on each furnace individually as stated in Installation S...

Page 20: ...20 443 06 2403 01 Specifications subject to change without notice Figure 20 Wiring Diagram for Single Stage Non Condensing Furnaces...

Page 21: ...21 443 06 2403 01 Specifications subject to change without notice Figure 21 Wiring Diagram for Two Stage Non Condensing Furnaces...

Page 22: ...22 443 06 2403 01 Specifications subject to change without notice Copyright 2018 International Comfort Product S PO Box 128 S Lewisburg TN 37091 USA...

Reviews: