background image

7

443 06 2403 01

Specifications  subject to change without notice.

opening in appropriate side of each furnace. (See

Figure 2)

UNIT DAMAGE AND FIRE HAZARD

Failure to follow this warning could result in unit

damage, fire, personal injury or death.
DO NOT use the side of the furnace for return

air duct

connections, as limit cycling will occur.

!

WARNING

b. For downflow applications:

Return air can only be connected to bottom opening

of furnace. A common return air plenum is required

for proper auxiliary limit switch operation. (See

Figure 3)

5. Apply 2 factory

supplied foam strips to the back of each

furnace. Locate strips equal distance from top and

bottom as shown in Figure 5. Trim off excess material.

6. Determine which side of furnace will be used to route

external extension harness. Remove 7/8

in. diameter

accessory hole knockouts in blower compartment side

selected to attach harness to. (See Figure 3)

7. Bend or remove the supply flanges as required for

upflow or downflow installation. Refer to the furnace

installation instructions for complete details.

8. Position furnaces back

to

back on return

air plenum,

supply air plenum or evaporator coil casing. Adjust and

shim each furnace to align both furnaces.

NOTE

:  External extension harness cannot be used on the

same side of the furnace that the return air ducts connect to.
Locate harness on opposite side of furnace when side return

air is used.

9. Drill two 1/8

in. holes, approximately 1 in. (25 mm)below

discharge flange, from inside top of discharge opening

and through both furnaces. (Similar to Figure 6) Drill two

1/8

in. holes, approximately 1 in. (25 mm)below return

air flange, from inside top of return air opening and

through both furnaces. (Similar to Figure 7)

10. Drive 1 factory

supplied No. 6 X 3/4

in. LG screw

through each hole and tighten until furnaces are secure

and foam strips have sealed gap between furnaces.

11. Connect return

 and supply

air ducts to furnaces. Seal

duct connections to prevent air leakage.

A02219

Figure 7 

 

Attaching Furnaces Together at Return Air

Opening

12. Move 115

v junction box JB in either furnace from

left

hand side to right

hand side if required. Refer to

furnace installation instructions for complete details.

13. Go to Step 2A for Single Stage Furnaces or Step 2B for

Two

Stage Furnaces.

C. Horizontal, Back

to

Back Position

When twinning furnaces in the horizontal position,

consideration must be made to the type of building

construction. Attic floors should be constructed to support

normal live and dead loads of the furnaces and the person(s)

servicing them.
Trusses, wood and metal are engineered for specific

applications, and may not support the weight of two (2)

furnaces suspended from the top chords or the bottom chords

of the trusses. Long horizontals spans may flex or sag,

resulting in damage to the building. Contact the truss

manufacturer for additional design and engineering assistance.
Do not suspend furnaces with straps or suspend furnaces from

roof decking.
For attic installations on a platform (See Figure 8):

1. Construct a platform from 3/4

in. (76 mm) (nominal

plywood), extending out 30 inches (762 mm) from the

front of each furnace.

2. Maintain all clearances to combustibles per the furnace

Installation, Start

up and Operating Instructions.

3. Follow all additional building codes.
4. Long truss spans may require additional support along

the bottom chord of the truss. Consult the truss

manufacturer’s guidelines for engineering assistance.

5. Long rafter or attic joist spans may require additional

support along the bottom of the rafter or joist. Consult

local or regional building codes for design and loading

requirements.

Summary of Contents for NAHA00601WK

Page 1: ...d safety codes In some instances these instructions exceed certain local codes and ordinances especially those that may not have kept up with changing residential construction practices We require the...

Page 2: ...ion The damper should not create undue restriction in the open position All furnaces must be installed to ensure sufficient return air to both furnaces S For upflow furnaces A combination of one full...

Page 3: ...nnot obstruct access to either furnace Example 2 8 MIN Common Return Air Plenum Return Air Plenum Return Air Plenum Twinned Furnace Common Supply Air Plenum A02223 Figure 2 Downflow Horizontal Ductwor...

Page 4: ...al CAUTION 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch a clean un...

Page 5: ...le Stage and Two Stage with PSC Blower Model Numbers A B C D FLUE CABINET WIDTH in mm OUTLET WIDTH in mm TOP AND BOTTOM FLUE COLLAR in mm BOTTOM INLET WIDTH in mm FLUE COLLAR in mm SHIP WT KG 0451408...

Page 6: ...approximately 1 in 25 mm below discharge flange from inside top of discharge opening and through both furnaces See Figure 6 Drill two 1 8 in holes approximately 1 in 25 mm below return air flange from...

Page 7: ...10 Drive 1 factory supplied No 6 X 3 4 in LG screw through each hole and tighten until furnaces are secure and foam strips have sealed gap between furnaces 11 Connect return and supply air ducts to f...

Page 8: ...drawing of twinned furnaces and their connection locations 1 Select 2 identical heating and airflow furnaces See Table 2 2 Remove outer door and blower access door 3 Remove bottom closure panels from...

Page 9: ...ace from left hand side to right hand side if required Refer to furnace installation instructions for complete details 13 Go to PROCEDURE 2A for Single Stage Furnaces or PROCEDURE 2B for Two Stage Fur...

Page 10: ...recommended for wood trusses unless approved by the truss manufacturer or other approved engineering methods 1 Furnaces may be suspended using two 2 pieces of 1 1 2 in x 1 1 2 in x 1 4 in thick cold r...

Page 11: ...e no connections between the R 24 vac connector in 1 furnace and the R 24 vac connector in other furnace WARNING See Electrostatic Discharge Precaution Section The twinning kit can be used for single...

Page 12: ...e Extension Harness 4 Install Auxiliary Limit Switch ALS S on Secondary furnace a Drill 1 8 in hole in blower housing 12 in 305 mm below blower shelf See Figure 13 b Position ALS S with terminals faci...

Page 13: ...16 B All Two Stage Models F8MTL G8MTL Two Speed Non Condensing HSI Furnaces with PSC Motors See Electrostatic Discharge Precaution Section The twinning kit can be used for single stage or two stage he...

Page 14: ...de by side route loose ends of 4 wire harness from Secondary furnace to Main furnace through snap bushings previously installed between furnaces f Connect Secondary 4 wire harness into 4 wire Main har...

Page 15: ...s the furnaces allowing them to operate as a single furnace The L1 black connection to each furnace must be connected to circuit breakers connected to the same service panel 115 vac phase leg On singl...

Page 16: ...6 101 on outside of blower access door of RH furnace blower door 5 Turn on power and gas to both furnaces 6 Reinstall blower access doors on both furnaces 7 Operate furnaces through 2 cycles in each m...

Page 17: ...443 06 2403 01 Specifications subject to change without notice Figure 16 Single Stage Furnace and A C Two Stage Thermostat Figure 17 Two Stage Furnaces and 1 Stage A C Unit One or Two Stage Thermosta...

Page 18: ...INALS HUM XFMR HUMIDIFIER TERMINAL 115 VAC 120 180 90 150 SPARE2 J2 JUMPER J2 HUM 24VAC BLW SPARE1 SPARE2 L2 NEUTRAL EAC 1 AMP IND HSI P2 L1 Figure 19 Two Stage Furnace Control SETUP SWITCHES THERMOST...

Page 19: ...t disconnect TKR yellow wire labeled TEST from LH furnace control TEST TWIN terminal After removing yellow wire component test can be initiated on each furnace individually as stated in Installation S...

Page 20: ...20 443 06 2403 01 Specifications subject to change without notice Figure 20 Wiring Diagram for Single Stage Non Condensing Furnaces...

Page 21: ...21 443 06 2403 01 Specifications subject to change without notice Figure 21 Wiring Diagram for Two Stage Non Condensing Furnaces...

Page 22: ...22 443 06 2403 01 Specifications subject to change without notice Copyright 2018 International Comfort Product S PO Box 128 S Lewisburg TN 37091 USA...

Reviews: