background image

 

 

 

NOTE:

  With burner relay contact open, the Riello 40-

BF will post-purge when 115 volt power is applied to the 
burner. 

 

 

2.2.3 

Sequence of operation - Beckett AFG and 
Riello 40-F, chimney venting 

 

1.  On the AFG burner, the T-T terminals have to be 

jumpered on the primary control of the burner; 

2.  Normally open contact (W-R) closes when thermostat 

calls for heat; 

3.  Burner motor starts. The burner motor fan pre-purges the 

combustion chamber and vent for 10 to 15 seconds, 
establishing the combustion air pattern. After the pre-
purge period, the solenoid valve opens, allowing oil to 
flow through nozzle. At the same time, the burner motor 
ignition coil produces a spark; 

4.  Spark ignites oil droplets; 

5.  Cad cell senses flame and burner continues to fire. 

Ignition transformer ceases sparking (Riello R40-F); 

6.  After Fan-Limit Control heats up to the factory set point, 

the circulating air blower starts; 

7.  The circulating air blower and burner motor remain on 

until the thermostat is satisfied; 

Thermostat is satisfied: 

8.  Relay contacts open, solenoid valve closes, burner fan 

motor shuts down and the ignition transformer ceases 
sparking; 

 

2.2.4 Sequence 

of 

operation 

DV-2000™ Venting system 

 

Normal operation 

 

1.  Before a call for heat, the contacts of the pressure switch 

are closed; 

2.  When the room thermostat calls for heat, the normally 

open contact W-R closes, the burner blower starts and 
creates suction in the intake piping circuit and pressure in 
the vent piping circuit; 

3.  The differential pressure set point of the pressure switch 

is not exceeded and the thermostat circuit remains closed 
until the call for heat has ended.  

 

Abnormal operation 

 

Start-up 

 

1.  When the room thermostat calls for heat, the normally 

open contact W-R closes, the burner blower starts and 
creates suction in the intake piping circuit and pressure in 
the vent piping circuit; 

2.  If there is a blockage in the intake or vent openings to 

cause a pressure differential beyond the set point of the 
pressure switch, then the thermostat circuit is opened and 
the burner will go into a 15 seconds post-purge and then 
shut down; 

3.  Once the burner blower shuts down, after the post-purge, 

the pressure switch contacts will re-close. If the call for 
heat remains, the burner will re-start. If the blockage still 
exists, the thermostat is again opened, and the burner 
post-purges again. The post-purge function thus becomes 
an inherent anti-short cycling device; 

4.  The unit will essentially go into a continuous re-

cycling/post-purge mode with no heat being supplied to 
the dwelling, which will prompt a service call; 

5.  If, during the re-cycling/post-purges, the blockage of the 

terminal is removed, the burner will immediately fire up at 
the end of the current post-purge cycle. 

 

During operation 

 

If the terminal vent or intake openings become blocked to the 
point where the set point of the pressure switch is exceeded 
during a firing cycle, the flame will shut down and the burner 
will go into the indefinite recycling post-purge mode as 
described above, until the blockage is removed. 

 

2.3 

CHECKS AND ADJUSTMENTS 

 

2.3.1 General 

 

During initial start-up and subsequent yearly maintenance 
calls, the furnace must be thoroughly tested.  

 

Open the oil bleed port screw and start the burner. Allow the 
oil to drain into a container for at least 10 seconds. The oil 
should flow absolutely free of white streaks or air bubbles to 
indicate that no air is being drawn into the suction side of the 
oil piping and pump. Then slowly close and tighten the bleed 
screw. Fire the burner. Adjust the oil pressure as indicated in 
Tables 4.1 to 4.3. 

 
 

IMPORTANT 

The burner must be put in operation for at least 10 
minutes before any test readings are taken. For new 
installations, set up the burner to the settings in Tables 
4.1 to 4.3

 

before firing. These are rough adjustments 

but they will ensure that the burner will start and run 
smoke-free in advance of the final adjustments to be 
made. 

 
 

2.3.2 

Restart after burner failure 

 

1. 

Set thermostat lower than the room temperature; 

2. 

Press the reset button on the burner primary control (relay); 

3. 

With side-wall venting and Riello burner, set thermostat higher 
than the room temperature for 10 seconds, then set lower than 
room temperature. This will start pre-purge cycle. Repeat twice; 

4. 

Set thermostat higher than the room temperature; 

5. 

If the burner motor does not start or ignition fails, turn off the 
disconnect switch and CALL A QUALIFIED SERVICE 
TECHNICIAN. 

 
 

CAUTION 

Do not attempt to start the burner when excess oil has 
accumulated, when the furnace is full of vapour, or 
when the combustion chamber is very hot. Always keep 
the supply valve closed if the burner is shut down for an 
extended period of time. 

 

17 

Summary of Contents for NOLF105A12D

Page 1: ...FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Pr...

Page 2: ...ith the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death bodily injury and or property damage WARNING Fire hazard The furnace...

Page 3: ...hen the furnace is side wall vented CAUTION Do not use any commercially available soot remover This furnace has a ceramic fibre type of combustion chamber Normal servicing of this unit does not requir...

Page 4: ...maximum efficiency and without the use of a side wall power vent The unit will operate at a positive overfire draft and flue draft 1 4 2 Chimney installations When set up for chimney venting this furn...

Page 5: ...all and the terminal is designed to fit through a minimum 2 x 8 joist space c Incorporates a vent blockage safety shutdown system If the vent or intake opening ever becomes partially or fully blocked...

Page 6: ...ion 6 7 3 4 of the NFPA 31 CAUTION Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances even if all other code requirem...

Page 7: ...ER SLEEVE BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 DRIVE THREE STAINLESS STEEL SCREWS STARTING NEAR TOP FIGURE 1 5 FIGURE 1 6 8...

Page 8: ...RE 1 7 FIGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 APPLY THE SEALANT TO THE TUBE END 9 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH SEALANT OUTF...

Page 9: ...EEVE TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL...

Page 10: ...to expose the corrugated stainless steel core 4 Cut the corrugated stainless steel core back by 76 mm 3 on the IFV Series vent You should now have about 76 mm 3 of insulation hanging out past the stai...

Page 11: ...sult in death or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate...

Page 12: ...and Solvent Cement ASTM D 2564 ABS Pipe and Fittings ASTM D 2235 Procedure for Cementing Joints ASTM D 2855 Additional parts required not included in VTK kit a 3 elbow fitting as required b 3 plastic...

Page 13: ...d a Remove drawer assembly or air tube combination b Install nozzle see specifications c Confirm electrode settings d Make the electrical connections e Complete oil line connections CAUTION Do not tur...

Page 14: ...5 Amp maximum to an Electronic Air Cleaner EAC Power will be available to the EAC at all times so it must incorporate a flow proving switch if it is to be wired into the furnace control box Most mode...

Page 15: ...t purges the combustion chamber and vent for a pre set time 15 seconds The ignition transformer also continues to spark for this time period 10 During the post purge cycle the Fan Limit Control cools...

Page 16: ...he blockage still exists the thermostat is again opened and the burner post purges again The post purge function thus becomes an inherent anti short cycling device 4 The unit will essentially go into...

Page 17: ...n air temperature from the supply air temperature 5 If the temperature rise exceeds the temperature specified in Tables 4 1 to 4 3 change to the next higher blower speed tap until the temperature rise...

Page 18: ...Smoke Test and allow for the 1 5 CO2 operating play required by the instructions 5 If the burner still does not shut down before a 1 smoke occurs check for a blockage of the pressure hose or at the h...

Page 19: ...ever if you notice scaling in the radiator you should remove it The wrap around radiator can now be cleaned entirely from the front inspection port The furnace also has external clean out ports so the...

Page 20: ...gn matter from the retention head and electrodes If a Beckett AFG burner has been installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one...

Page 21: ...elephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambie...

Page 22: ...Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0 85 70B 1 00 70B Pump pressure PSIG 130 140 160 130 130 130 Combustion air adjustment screw dial or dial only 3...

Page 23: ...From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 82 2 81 5 80 3 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0...

Page 24: ...m ASHRAE103 standard and US regulation 81 5 81 0 81 0 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W Pump pressure PSIG 130 140 160...

Page 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...

Page 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...

Page 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...

Page 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...

Page 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...

Page 30: ...COMPONENTS AND REPLACEMENT PARTS 31...

Page 31: ...PARTS LIST Model OLR105A12D B50031 B 32...

Page 32: ...pplication 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B30808 01 Electrical box cover 31 B30828 Electrical box box only 32 L07F003 Rocker switch SPST consta...

Page 33: ...PARTS LIST Model OLR160B20C B50032 C 34...

Page 34: ...e panel assembly 30 B30686 01 Right side panel insulation 31 B30668 01 Right bottom filter support 32 B30835 Right top filter support 33 B30782 01 Front panel assembly labels included without logo 34...

Page 35: ...PARTS LIST Model OUF105A12C B50033 B 36...

Page 36: ...r 23 F07O001 Hexagonal flange nut 3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 F06F005 Washer 3 8 AA zinc 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H00...

Page 37: ...PARTS LIST Model OUF160B18C B50034 D 38...

Page 38: ...nt panel assembly labels included 29 B30779 Front panel insulation 30 B30651 Blower door assembly labels included without logo 31 Z99F050 Door handle 32 F06F005 Washer 3 8 AA zinc 33 F07F024 Hexagonal...

Page 39: ...PARTS LIST Model OLF105A12C B50035 B 40...

Page 40: ...61 Sight glass 27 F07O001 Hexagonal flange nut 3 8 16NC brass 28A B30459 5 breech plate chimney application 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B308...

Page 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...

Page 42: ...ech plate direct vent application 28 B30415 02 Gasket heat exchanger 29 B30808 01 Electrical box cover 30 B30826 Electrical box box only 31 L07F003 Rocker switch SPST constant blower operation 32 R02I...

Page 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...

Page 44: ...3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 Z99F050 Door handle 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H009 Relay SPDT 24VAC 29 L01F009 Transforme...

Reviews: