background image

 

 

 

 

PART 3 

MAINTENANCE 

 

 

3.1) GENERAL 

 

Preventive Maintenance 

 

"Preventive maintenance" is the best way to avoid 
unnecessary expense and inconvenience. Have your 
heating system and burner inspected at regular intervals 
by a qualified service technician. 

 

 

WARNING 

 

Electrical shock hazard. 

 

Turn OFF power to furnace before any disassembly 
or servicing. 

 

Failure to do so can result in bodily injury and/or 
death, property damage. 

 

 

A complete combustion test must be performed after each 
annual service inspection of the unit, to maintain optimum 
performance and reliability. 

 

Do not tamper with the unit or controls. Call a qualified 
service technician. 

 

Before calling for service, check the following  

a.  Check oil tank gauge and check if the valve is open; 

b.  Check fuse or circuit breaker; 

c. 

Check if shut-off switch is “ON”; 

d.  Set thermostat above room temperature; 

e.  If ignition does not occur, turn off the disconnect switch 

and call a qualified service technician. 

 

When ordering replacement parts, specify the complete 
furnace model and serial number. 

 

3.1.1) Heat 

exchanger 

 

The entire heat exchanger should be inspected annually for 
soot accumulation. If the burner is operating normally there 
should be very little soot accumulation. If the heat exchanger 
requires scale removal, use a wire brush first, to loosen the 
scale and then vacuum the soot and scale that has fallen into 
the secondary heat exchanger (radiator) section. You will find 
that a 36" long flexible hose attachment will be helpful to reach 
into the back of the radiator. A piece of 1/2" flexible gas 
connector, or a piece of 1/2" liquid-tight vinyl jacket metallic 
electrical conduit works well as a makeshift device.  

 

Cleaning the heat exchanger 

 

Remove the 4-bolt flange from the front of the furnace to 
expose the clean-out port and check for soot deposits. If there 
is very little soot in the radiator section visible from the clean-
out port, you will not need to clean it. However, if you notice 
scaling in the radiator, you should remove it. 

 

The wrap-around radiator can now be cleaned entirely from 
the front inspection port. The furnace also has external clean-
out ports so the soot does not fall into the fan compartment 
during the cleaning operation. 

 

IMPORTANT 

Do not vacuum the ceramic chambers—they are easily 
damaged. 

 

Soot will have collected in the first sections of the heat 
exchangers only if the burner was started after the combustion 
chamber was flooded with fuel oil, or if the burner has been 
operating in a severely contaminated condition.  

 

3.1.2) Refractory 

firepot 

 

Remove the burner and check the firepot.  

 

IMPORTANT 

This furnace has a fibre type refractory combustion 
chamber. Normal servicing of this unit does not require 
cleaning of the combustion chamber.  
If cleaning of the pot should be required, use extreme 
care. After firing, the pot becomes very fragile. Do not 
use any commercially available soot removers.  

 

If the pot is damaged, it must be replaced. A damaged pot 
could lead to premature heat exchanger failure. Cracking of 
the firepot is normal, however, replace the pot only if the 
cracks have propagated more than 2/3 the way through the 
wall thickness. The average wall thickness of the firepot is 19 
mm (3/4"). 

 

Flooding of the firepot 

 

Flooding can occur when the oil primary control has been 
reset a number of times in a no-heat situation. Each time oil is 
fired into the pot and does not ignite, it is absorbed into the 
pot. Even if the burner is removed and the pot is felt for 
wetness, it is difficult to assess the degree of oil absorption by 
the pot. 

 

There is only one way to properly service a flooded firepot, 
and that is to replace it. 

 

CAUTION 

If you observe the red warning light on the burner, push 
ONLY once to try and restart. If the burner does not 
start, call a qualified service technician. Do NOT press 
the button again. 

 

 

Self-aligning firepot 

 

The primary heat exchanger of the furnace is comprised of an 
upper and lower half. The lower half is essentially a “can” that 
contains a self-aligning firepot. The firepot fits into the bottom 
half in one direction only. 

20 

Summary of Contents for NOLF105A12D

Page 1: ...FOR THE INSTALLATION AND SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Pr...

Page 2: ...ith the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death bodily injury and or property damage WARNING Fire hazard The furnace...

Page 3: ...hen the furnace is side wall vented CAUTION Do not use any commercially available soot remover This furnace has a ceramic fibre type of combustion chamber Normal servicing of this unit does not requir...

Page 4: ...maximum efficiency and without the use of a side wall power vent The unit will operate at a positive overfire draft and flue draft 1 4 2 Chimney installations When set up for chimney venting this furn...

Page 5: ...all and the terminal is designed to fit through a minimum 2 x 8 joist space c Incorporates a vent blockage safety shutdown system If the vent or intake opening ever becomes partially or fully blocked...

Page 6: ...ion 6 7 3 4 of the NFPA 31 CAUTION Most codes have a notwithstanding clause that states that products of combustion shall not enter the dwelling under any circumstances even if all other code requirem...

Page 7: ...ER SLEEVE BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 DRIVE THREE STAINLESS STEEL SCREWS STARTING NEAR TOP FIGURE 1 5 FIGURE 1 6 8...

Page 8: ...RE 1 7 FIGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 APPLY THE SEALANT TO THE TUBE END 9 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH SEALANT OUTF...

Page 9: ...EEVE TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL...

Page 10: ...to expose the corrugated stainless steel core 4 Cut the corrugated stainless steel core back by 76 mm 3 on the IFV Series vent You should now have about 76 mm 3 of insulation hanging out past the stai...

Page 11: ...sult in death or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate...

Page 12: ...and Solvent Cement ASTM D 2564 ABS Pipe and Fittings ASTM D 2235 Procedure for Cementing Joints ASTM D 2855 Additional parts required not included in VTK kit a 3 elbow fitting as required b 3 plastic...

Page 13: ...d a Remove drawer assembly or air tube combination b Install nozzle see specifications c Confirm electrode settings d Make the electrical connections e Complete oil line connections CAUTION Do not tur...

Page 14: ...5 Amp maximum to an Electronic Air Cleaner EAC Power will be available to the EAC at all times so it must incorporate a flow proving switch if it is to be wired into the furnace control box Most mode...

Page 15: ...t purges the combustion chamber and vent for a pre set time 15 seconds The ignition transformer also continues to spark for this time period 10 During the post purge cycle the Fan Limit Control cools...

Page 16: ...he blockage still exists the thermostat is again opened and the burner post purges again The post purge function thus becomes an inherent anti short cycling device 4 The unit will essentially go into...

Page 17: ...n air temperature from the supply air temperature 5 If the temperature rise exceeds the temperature specified in Tables 4 1 to 4 3 change to the next higher blower speed tap until the temperature rise...

Page 18: ...Smoke Test and allow for the 1 5 CO2 operating play required by the instructions 5 If the burner still does not shut down before a 1 smoke occurs check for a blockage of the pressure hose or at the h...

Page 19: ...ever if you notice scaling in the radiator you should remove it The wrap around radiator can now be cleaned entirely from the front inspection port The furnace also has external clean out ports so the...

Page 20: ...gn matter from the retention head and electrodes If a Beckett AFG burner has been installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one...

Page 21: ...elephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambie...

Page 22: ...Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0 85 70B 1 00 70B Pump pressure PSIG 130 140 160 130 130 130 Combustion air adjustment screw dial or dial only 3...

Page 23: ...From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 82 2 81 5 80 3 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W 0 75 70B 0...

Page 24: ...m ASHRAE103 standard and US regulation 81 5 81 0 81 0 BECKETT BURNER SIDE WALL INSTALLATION Burner tube insertion lenght inches Nozzle Delavan 0 50 60W 0 50 60W 0 60 60W Pump pressure PSIG 130 140 160...

Page 25: ...DNS 0571 Rev C DNS 0573 Rev C FIGURE 5 1 Model OLR105A12D FIGURE 5 2 Model OLR160B20C 26...

Page 26: ...FIGURE 5 3 Model OUF105A12C FIGURE 5 4 Model OUF160B18C DNS 0572 Rev D DNS 0568 Rev C 27...

Page 27: ...FIGURE 5 5 Model OLF105A12C DNS 0570 Rev C FIGURE 5 6 Model NOUF105A12D DNS 0674 Rev E 28...

Page 28: ...FIGURE 5 7 Model NOLF105A12D DNS 0676 Rev D 29...

Page 29: ...FIGURE 6 Wiring diagram OLR105A12D OLR160B20C OUF105A12C NOUF105A12D OUF160B18C OLF105A12C NOLF105A12D 30...

Page 30: ...COMPONENTS AND REPLACEMENT PARTS 31...

Page 31: ...PARTS LIST Model OLR105A12D B50031 B 32...

Page 32: ...pplication 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B30808 01 Electrical box cover 31 B30828 Electrical box box only 32 L07F003 Rocker switch SPST consta...

Page 33: ...PARTS LIST Model OLR160B20C B50032 C 34...

Page 34: ...e panel assembly 30 B30686 01 Right side panel insulation 31 B30668 01 Right bottom filter support 32 B30835 Right top filter support 33 B30782 01 Front panel assembly labels included without logo 34...

Page 35: ...PARTS LIST Model OUF105A12C B50033 B 36...

Page 36: ...r 23 F07O001 Hexagonal flange nut 3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 F06F005 Washer 3 8 AA zinc 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H00...

Page 37: ...PARTS LIST Model OUF160B18C B50034 D 38...

Page 38: ...nt panel assembly labels included 29 B30779 Front panel insulation 30 B30651 Blower door assembly labels included without logo 31 Z99F050 Door handle 32 F06F005 Washer 3 8 AA zinc 33 F07F024 Hexagonal...

Page 39: ...PARTS LIST Model OLF105A12C B50035 B 40...

Page 40: ...61 Sight glass 27 F07O001 Hexagonal flange nut 3 8 16NC brass 28A B30459 5 breech plate chimney application 28B B30515 3 breech plate direct vent application 29 B30415 02 Gasket heat exchanger 30 B308...

Page 41: ...PARTS LIST Model NOLF105A12D B50037 B 42...

Page 42: ...ech plate direct vent application 28 B30415 02 Gasket heat exchanger 29 B30808 01 Electrical box cover 30 B30826 Electrical box box only 31 L07F003 Rocker switch SPST constant blower operation 32 R02I...

Page 43: ...PARTS LIST Model NOUF105A12D B50036 B 44...

Page 44: ...3 8 16NC brass 24 F07F024 Hexagonal nut 3 8 16NC brass 25 Z99F050 Door handle 26 L05F011 Terminal strip 6 positions 27 B30808 01 Electrical box cover 28 L01H009 Relay SPDT 24VAC 29 L01F009 Transforme...

Reviews: