background image

 

 

Side wall venting installation - DV-2000™ 

 
 

WARNING 

 

Cuts and abrasion hazard. 
 
Always wear protective gloves and eye protection 
when handling the vent material. 
 
The process of cutting and fitting the flexible 
venting material exposes the installer to sharp 
edges that could cause severe cuts to the skin. 

 
 

Connection to the furnace breach - DV-2000™ 

 
1. 

Remove the standard breach plate by removing the brass nuts; 

2. 

Determine which direction the venting will be routed from the 
furnace and then install the special side-wall venting breach plate 
provided in the VTK Series vent kit so that the breach plate test 
port will be accessible after vent installation. However, do not 
install the breach plate with the test port pointing downward. 
Tighten the brass nuts; 

3. 

The flexible venting has 4 pieces of corrugated spin sleeve that 
has been temporarily screwed on over top of it. Remove the spin 
sleeve completely by unscrewing it in a counter-clockwise 
direction; 

4. 

Using tin snips, cut the aluminium outer sleeve back by 127.0 
mm (5") on the IFV Series vent (see Figure 1.1). Ensure the 
snips are well adjusted and sharp or the cut end of the venting 
will be too jagged to start the threads of the spin sleeve (see 
Figure 1.1);  

5. 

Prepare the furnace breach end of the insulated flex vent by first 
screwing the spin sleeve onto the corrugated aluminium jacket 
(see Figure 1.2) until the trailing edge of the spin sleeve is about 
0.3 m (12") from the end of the vent (see Figure 1.3); 

6. 

Pull the insulation back to expose the corrugated stainless steel 
core; 

7. 

Cut the corrugated stainless steel core back by 76.2 mm (3") on 
the IFV Series vent. You should now have about 76.2 mm (3") of 
insulation hanging out past the stainless steel core (see Figure 
1.4); 

8. 

Push the stainless steel core onto the breach pipe as far as it will 
go (see Figure 1.5) and mechanically attach the vent to the 
breach using three of the #8 X 1/2” self-drilling screws provided 
with the VTK Series kit. The screws should be equally spaced 
around the circumference of the stainless steel core, starting with 
the first screw at top dead centre. Start the drill point of the 
screws in the valleys of the corrugations at 9.5 mm –15.8 mm 
(3/8”-5/8”) back from the end of the stainless steel core, so the 
screw heads can be properly sealed in the forthcoming 
operations (see Figure 1.6); 

9. 

With the stainless steel core now firmly attached to the breach, 
tear off one green gum-sealing strip from the backing. Wrap the 
seal strip around the joint, always keeping the centreline of the 
seal strip over the line where the corrugated stainless steel core 
makes the transition to the smooth outer surface of the breach 
pipe. In other words, the seal strip must be centred over the joint. 
After wrapping the seal strip around once, allow 12.7 mm (1/2”) 
overlap and tear off the residual length (see Figure 1.7); 

10.  Break the residual length of seal strip into 3 equal parts and stuff 

them onto the screw heads of the stainless steel self-drilling 
screws so that the screw heads are completely covered; 

11.  Two stainless steel band clamps are provided in the VTK Series 

kits. Position one stainless steel band clamp over the gum seal 
joint so that the edge of the clamp closest to the breach lines up 
with the edge of the gum seal that is closest to the breach. 
Ensure that the band will close with an action of one strip sliding 
over the other - not under the gear head of the draw clamp (see 
Figure 1.8). Tighten the band clamp with considerable torque to 
cause the gum seal to be squeezed into all crevices and to ooze 
out of the end of the clamp closest to the breach (see Figure 1.9). 
The gum will eventually become rubbery; 

12. The seal is permanent and should never need to be 

disconnected as the breach plate can be removed for cleaning 
and inspection using the 4-bolt joint; 

13.  Tuck the vent insulation into the breach collar; 

14.  Screw the spin sleeve tightly into the breach collar for a finished 

appearance. Wrap the other end of the spin sleeve with 
aluminium tape to cover any metal burrs that may be present 
(see Figure 1.10); 

15.  Bend the venting into the desired radius coming off the breach. 
 
 

Connection to the vent terminal - DV-2000™ 
 

1.  Prepare the terminal end of the insulated flex vent by first 

screwing the spin sleeve onto the corrugated aluminium jacket 
until the trailing edge of the spin sleeve is about 254.0 mm (10") 
from the end of the vent; 

2. 

Using sharp tin snips, cut the aluminium outer sleeve back by 
127.0 mm (5") on the IFV Series vent; 

3. 

Pull the insulation back to expose the corrugated stainless steel 
core; 

4. 

Cut the corrugated stainless steel core back by 76.2 mm (3") on 
the IFV Series vent. You should now have about 76.2 mm (3") of 
insulation hanging out past the stainless steel core; 

5. 

Push the stainless steel core onto the pipe on the back of the 
terminal as far as it will go and mechanically attach the vent to 
the terminal using three of the #8 X 1/2” self-drilling screws 
provided with the VTK Series kit. The screws should be equally 
spaced around the circumference of the stainless steel core, 
starting with the first screw at top dead centre. Start the drill point 
of the screws in the valleys of the corrugations at 9.5 mm-15.8 
mm (3/8”-5/8”) back from the end of the stainless steel core; 

6. 

With the stainless steel core now firmly attached to the terminal, 
tear off the other green gum-sealing strip from the backing. Wrap 
the seal strip around the joint, always keeping the centreline of 
the seal strip over the line where the corrugated stainless steel 
core makes the transition to the smooth outer surface of the 
terminal pipe. After wrapping the seal strip around once, allow 
12.7 mm (1/2”) overlap and tear off the residual length; 

7. 

Break the residual length of seal strip into 3 equal parts and stuff 
them onto the screw heads of the stainless steel self-drilling 
screws so that the screw heads are completely covered; 

8. 

Position the other stainless steel band clamp over the gum seal 
joint so that the edge of the clamp closest to the terminal lines up 
with the edge of the gum seal that is closest to the terminal. 
Tighten the band clamp with considerable torque to cause the 
gum seal to be squeezed into all crevices and to ooze out of the 
end of the clamp closest to the terminal (see Figure 1.11); 

9.  The seal is permanent and should never need to be 

disconnected as the end of the terminal can be opened for 
cleaning and inspection by removing the screened end-cone 
assembly. Tuck the vent insulation into the recess in the terminal 
body; 

10.  Screw the spin sleeve tightly into the recess for a finished 

appearance. Wrap the other end of the spin sleeve with 
aluminium tape to cover any metal burrs that may be present 
(see Figure 1.12); 

11.  Bend the venting into the desired radius coming off the terminal. 
 

445 01 4024 05

Summary of Contents for OCF105A12C

Page 1: ...CING OF THE UNIT AND KEEP THE DOCUMENT NEAR THE FURNACE FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFERENCE Printed in Canada Printed on 100 recycled paper OIL...

Page 2: ...s and test instruments Failure to carefully read and follow all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furna...

Page 3: ...ions regarding any brand or type of detector CAUTION Ensure that the area around the combustion air intake terminal is free of snow ice and debris CAUTION An air pressure switch MUST be used when the...

Page 4: ...ine or any other damaging chemicals Refer to Part 1 section 5 2 1 4 VENTING 1 4 1 General The furnaces can be vented in several ways Chimney Vented Using the Beckett AFG or Riello 40 F burner the furn...

Page 5: ...ected to a 20 foot tall clay lined masonry chimney the thermal resistance of this type of chimney is R2 which is less than R6 The actual firing rate at 156 psig is 1 25 x 60 75 Therefore this table sh...

Page 6: ...nal in accordance with all local and national codes The following requirements shall be considered to be minimum requirements that can be overridden by stricter local and national codes FIGURE 1 The v...

Page 7: ...hat the band will close with an action of one strip sliding over the other not under the gear head of the draw clamp see Figure 1 8 Tighten the band clamp with considerable torque to cause the gum sea...

Page 8: ...E BACK 5 THREAD SPIN SLEEVE BACK 10 CUT STAINLESS STEEL CORE BACK BY 3 9 FIGURE 1 3 FIGURE 1 4 FIGURE 1 1 FIGURE 1 2 FIGURE 1 5 FIGURE 1 6 INSERT STAINLESS STEEL CORE ONTO BREECH TUBE DRIVE THREE STAI...

Page 9: ...IGURE 1 8 SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT TERMINAL SEALANT OUTFLOW FIGURE 1 11 10 APPLY THE SEALANT TO THE TUBE END SEALANT OUTFLOW SEALANT FLOWING OUT FROM UNDER BAND CLAMP AT BREECH TWI...

Page 10: ...TIGHTLY INTO RECESS INSTALL STABILIZER SHROUD CAULK TO SEAL STABILIZER SHROUD TO THE WALL FIGURE 1 13 FIGURE 1 14 FIGURE 1 12 VENT TERMINAL PRESSURE SWITCH REFER TO WIRING DIAGRAM FOR ELECTRICAL CONNE...

Page 11: ...t 1 section 5 3 1 5 3 Outdoor Combustion Air Side wall Venting DV 2000 for a complete description 1 5 AIR FOR COMBUSTION WARNING Poisonous carbon monoxide gas hazard Comply with NFPA standards for the...

Page 12: ...two plastics Intake pipe length DV 2000 The DV 2000 venting system has been certified for 37 equivalent m 120 equivalent feet of 3 intake pipe Count a 90 elbow as 10 equivalent feet and a 45 elbow as...

Page 13: ...king Checking the air and turbulator settings Before starting the burner for the first time adjust the air and turbulator settings to those listed in Table 4 Once the burner becomes operational final...

Page 14: ...e heat exchanger Wire the thermostat and condensing unit contactor as indicated in the wiring diagram Figure 6 1 9 4 Ductwork and Filter Installation Design and install the air distribution system to...

Page 15: ...Fan Limit Control heats up to the factory set point the circulating air blower starts 7 The circulating air blower and burner motor remain on until the thermostat is satisfied Also the solenoid valve...

Page 16: ...shut down for an extended period of time 4 Set thermostat higher than the room temperature 5 If the burner motor does not start or ignition fails turn off the disconnect switch and CALL A QUALIFIED SE...

Page 17: ...flame should shut down before a 1 smoke reading occurs 3 Gradually block the vent outlet The burner flame should shut down before a 1 smoke reading occurs 4 If the burner does not shut down before 1...

Page 18: ...ly from the front inspection port Also the furnace has external clean out ports so the soot does not fall into the fan compartment during the cleaning operation IMPORTANT Do not vacuum the ceramic cha...

Page 19: ...een installed the burner will have to be removed to check the retention head 3 1 4 Nozzle Replace the nozzle with the one specified in Table 4 3 1 5 Oil filters Tank filter The tank filter should be r...

Page 20: ...hone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lbpsi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient t...

Page 21: ...3 3 4 5 AFUE From CSA B212 standard and Canadian regulation 81 5 81 0 80 3 AFUE From ASHRAE 103 standard and US regulation 81 5 81 0 80 3 RIELLO BURNER SIDE WALL INSTALLATION Burner tube insertion len...

Page 22: ...DNS 0589 Rev C FIGURE 5 Models ODH53F100LB 3MC OCF105A12C 23 445 01 4024 05...

Page 23: ...24 FIGURE 6 Wiring diagram ODH53F100LB 3MC OCF105A12C 445 01 4024 05...

Page 24: ...COMPONENTS AND REPLACEMENT PARTS 25 445 01 4024 05...

Page 25: ...PARTS LIST Model ODH53F100LB 3MC OCF105A12C B50030A 26 445 01 4024 05...

Page 26: ...gonal nut 3 8 16NC brass F07F024 32 Washer panel peep hole B30752 33 Hexagonal flange nut 3 8 16NC brass F07O001 34A 5 breech plate B30459 34B 3 breech plate B30515 35 Gasket breech plate B30415 02 36...

Reviews: