DL-100-E / DL-101-E / DL-110-E / DL-120-E User Manual Version 1.1.3 Dec 2020
- 68 -
Address Description
Attribute
00001 ~
00002
Digital output value of channel 0 to 1
If relative humidity alarm is enabled, then the
digital output of channel 0 is used as its alarm.
If temperature alarm or dew point alarm are
enabled, then the digital output of channel 2 is
used as their alarm.
R/W
00129 ~
00130
Safe value of digital output channel 0 to 1
R/W
00161 ~
00162
Power on value of digital output channel 0 to 1
R/W
00227
Write 1 to reload default TCP settings and reboot
module
W
00234
Write 1 to reboot module
W
00280
Write 1 to clear all high latched analog input
values
W
00281
Write 1 to clear all low latched analog input
values
W
00289 ~
00293
Low alarm status of channel 0 to 4. Write 1 to
clear low latched alarm.
R/W
00305 ~
00309
High alarm status of channel 0 to 4. Write 1 to
clear high latched alarm.
R/W
00321 ~
00325
Enable/disable alarm of channel 0 to 4
R/W
00337 ~
00341
Alarm type, momentary or latched, of channel 0
to 4
R/W
00385 ~
00389
Write 1 to clear high latched analog input value of
channel 0 to 4
W
00417 ~
00421
Write 1 to clear low latched analog input value of
channel 0 to 4
W