EtherCAT to Modbus RTU Gateway
Copyright © 2017 ICP DAS CO., Ltd. All Rights Reserved.
-
53 -
A3. “Manually Configure and Upload”
ECAT-2610 module.
The ECAT-2610 will send command
01 0F 00 00 00 08 01 00 FE 95
to the M-7050 first, then read
response
01 0F 00 00 00 08 54 0D
from the M-7050. The
send_ then_read
process will not stop and
repeat one by one.
The hardware timing of one send/read is given as follows:
Send
01 0F 00 00 00 08 01 00 FE 95
is about 1 ms
Read
01 0F 00 00 00 08 54
is about 1 ms
The
send_then_read
is about 5 ms
The
read_N
to
1
is about 2 ms
One
send_read_cycle
is about 5+2=7 ms
Figure 7.1-3
Figure 7.1-2