EtherCAT to Modbus RTU Gateway
Copyright © 2017 ICP DAS CO., Ltd. All Rights Reserved.
-
13 -
2.5
Init/Normal Operating Mode
The ECAT-2610 module has two operating modes that can be selected, each of which will be
described in more detail below.
Init Mode
Init Mode should only be selected for
troubleshooting.
1. Power off the ECAT-2610 module, and connect
the ECAT-2610 to Host PC.
2. Short the TxD and RxD pins on the COM3 to Init mode.
3. Run the 7188ECAT.exe, and power on the ECAT-2610 module to verify that enter the init mode.
4. Disconnect the TxD and RxD pins on the COM3 to normal mode.
5. Erase the EEPROM and upload new configuration file to EEPROM.
6. Reboot the ECAT-2610 module to work in normal mode.
Refer to
Chapter 6 “Diagnostic Operation”
of how to perform the above procedure.
Normal Mode
Normal Mode is the default operating mode and
should be used in most cases.