Electrical connection
6/24
4.2.
9-pole connector strip
Via the connector strip with the terminal numbers 6 to 14 the voltage supply/auxiliary power
of the device and the two relay outputs are connected.
Relay 1 (S1)
Auxiliary power
Relay 2 (S2)
6 7 8 9
10
11
12 13 14
Normally
open
Normally
closed
Com L
PE
N
Normally
open
Normally
closed
Com
4.3.
5- pole connector strip
Via the connector strip with the terminal numbers 1 to 5 the signal input for the standard
signals and the sensor supply are connected.
4.3.1.
Input for standard signals
The input signal is connected to terminals 3 to 5. The
AK-M2-VVR4C
has a voltage input
and a current input to which most conventional sensors with a standard signal output can
be connected. The input is galvanic isolated from the power supply (auxiliary voltage) and
the sensor supply.
Sensor Measuring
range
12
11
10
0...10 V
0...5 V
-12 V…+12 V
U+
U-
0...20 mA
4…20 mA
-24 mA…+24 mA
I+ I-
Examples for connecting different transmitters can be found in the section on
connecting
examples
.
4.3.2.
Sensor supply
The 24 VDC sensor supply is available at terminals 1 and 2. The sensor supply is galvanic
insulated from the measuring input. Current loop sensors (2-wire) and 3-wire and 4-wire
sensors can be operated via the sensor supply as long as their current consumption is not
higher than 50 mA (Power consumption < 1.2 VA).
1 2
Sensor
Sensor supply -