Operation
7/24
4.4.
Connection examples
This section gives a few examples of practical connections. Other connection options can
be combined from the various examples.
Measuring a current signal (4-20 mA) from a 2-wire transmitter, using the sensor
supply.
Measurement of a voltage signal (0-5 V or 0-10 V) from a 3-wire transmitter using the
sensor supply 24 VDC. The ground is bridged via the sensor, which eliminates the
measuring error through the drop in voltage on the sensor supply wires
Measuring a current signal (0 … 20 mA) from a 3-wire transmitter using the sensor
supply 24 VDC. The voltage drop on the sensor supply wire is irrelevant, which is why
this can also be bridged directly on the indicator.