Auto Sentry® Petro - Installation Guide
7
Site Layout
Grounding
The Auto Sentry® Petro and peripheral equipment must be properly grounded.
Recommended and Accepted Grounding Methods
Proper system grounding is an extremely important part of the system installation. Grounds for all
system devices should be wired to the breaker panel ground bus bar which, in turn, should be
grounded to a ground rod. A conduit ground does not provide a sufficient ground. It is
recommended that the neutral and ground bus bars be bonded together when it is not
prohibited by local codes.
The universal ground symbol identifies the grounding terminal located in the upper chamber,
near terminal blocks.
IMPORTANT: Improper grounding will void equipment warranty.
!
WARNING:
Ground wire must be connected to the
ground lug. Failure to properly ground
the unit could result in unit failure and/or
bodily injury.