Innovative Circuit Technology Ltd.
41
To access the power system through a secure HTTPS connection, use
https://
at the start of the
unit’s
URL. (e.g.
IP address
192.168.0.180
, HTTPS port
8888
)
SNMP:
Configure these settings if you would like to use Simple Network Management
Protocol (SNMP) based monitoring. SNMP is an industry standard protocol for
network management software. Enabling the SNMP function on the power
system will allow standard SNMP management software to connect to the
SNMP agent running on the system and read real time system information such
as bus voltage, and channel currents. The system can send SNMP traps to the
external management software when an alarm or fault occurs.
The information available from the SNMP agent is described in a Management
Information Base (MIB) file, which can be downloaded from:
•
the link at the bottom of the SNMP box on this web-GUI page; or
•
on the web-
GUI’s
Help
page; or
•
can be downloaded from the ICT Website:
https://www.ict-power.com/tools-utilities/
The unique power system MIB file must then be imported into your external
SNMP management software.
Enable SNMP
: Check this box to enable the SNMP agent.
SNMP Version:
Sets the SNMP version supported by the SNMP agent. If
All
is selected, all SNMP versions will be supported simultaneously. The
appropriate settings for the selected SNMP version will need to be
configured.
•
v1/v2c
,
•
v3
, or
•
All
Enable SNMP Write Access:
Check this box to allow remote SNMP control
of the system output and individual LDM output channels. If this box is
unchecked, all information available from the SNMP agent will be read-
only.
SNMP Control Access:
Sets the level of device control that is allowed
through SNMP. This setting is only available if Enable SNMP Write Access is
enabled.
•
Output Control:
Allows remote SNMP control of the system
output and LDM channel outputs only.