Reverse Sequence Order: I
f this box is checked, the outputs will be enabled in reverse sequence
(Output #12 first, Output #1 last) when the
Enable All Outputs
button is pressed on the
Status &
Control
page.
NETWORK WATCHDOG
Watchdog Enabled:
Checking this box will enable the Network Watchdog feature. The Network
Watchdog will periodically Ping up to two remote IP address to check the network connection status. If
the remotes IP address stops responding, the Panel will power-cycle any outputs that have the
Power
Cycling
option enabled. This feature is useful for rebooting a modem or router following a crash that
has resulted in loss of IP connectivity. For the Network Watchdog to work, at least one output must have
the
Power Cycle
option enabled, and a time delay must be entered in the
Sequence / Cycle Delay
field.
Primary IP Address:
Enter the remote IP address you would like to monitor. This field is optional; if left
blank, the Network Watchdog will instead monitor the Gateway IP address listed on the
Network Setup
page.
Secondary IP Address:
An optional second remote IP address can be entered in this field. If entered,
the Network Watchdog will only trigger if both the Primary and Secondary IP Addresses fail to respond.
Watchdog Timeout:
Enter the time duration, in minutes, that the remote IP addresses must stop
responding to Ping requests before the Network Watchdog will trigger and power-cycle outputs. The
default setting is 10 minutes. The Watchdog Timeout can be changed to anything between 1 and 80
minutes. Make sure that the Watchdog Timeout value is set longer than the time it takes for your
network hardware to fully start up.
DATA LOGGING
Data Logging:
Allows you to enable data logging. With data logging enabled, the panel will record the
system voltage, system current, output currents, fuse status, and alarm input status at a sample rate of
1 sample per minute. To view the log while data logging is enabled, click on the
Download Log button
next to the data logging dialog box. This will download the log in Comma Separated Values (CSV)
format, which can be opened by most spreadsheet software applications such as Microsoft Excel. The
log will hold up to 30 days of data, with oldest log entries at the top of the log file.
12