OUTPUT UNDER-CURRENT ALARM
Under-Current Threshold:
If the current on the selected output drops below the value in this field, the
output under-current alarm will trigger.
The output current must remain below the under-current threshold for at least 5 seconds before the
alarm will be triggered.
To disable this alarm, set the value in this field to 0 Amps.
Activate Alarm Form C Contact:
If this box is checked, the Alarm Form “C” Contacts on the panel will
indicate a fault condition when the under-current alarm is triggered for the selected output.
Send E-mail:
If this box is checked, an e-mail alarm notification will be sent when the under-current
alarm is triggered for the selected output. The e-mail settings on the
E-mail Setup
page must be
configured correctly before e-mail notifications can be sent.