Innovative Circuit Technology Ltd.
21
allow standard SNMP management software to connect to the SNMP agent
running on the panel and read real time system information such as bus voltage,
and channel currents. The panel can send SNMP traps to the external
management software when an alarm or fault occurs.
The information available from the SNMP agent is described in a MIB
(Management Information Base) file, which can be downloaded from the panels
Help
page. The unique panel MIB file must then be imported into your external
SNMP management software.
Enable SNMP
: Check this box to enable the SNMP agent
Read Community
: Enter the community string/password for read-only SNMP
access. The default read community string is “public”.
Trap Community
: Assign the community string/password that will be sent
with all traps. Some trap receivers are able to filter based on Trap
Community
Trap IP Addresses
: Assign the IP address for up to two devices that will
receive SNMP traps from the panel.
Enable SNMP Write Access:
Check this box to allow remote SNMP control of
individual panel power outputs. If this box is unchecked information from
the panel will be read-only.
Write Community
: Enter the community string/password for read-write
SNMP access. The default write community is “write”.
NOTE:
The community strings should be changed to unique passwords before
enabling SNMP, as the defaults are well known.
SNMP Contact Information
: Assign contact information, such as an operator
name and phone number for the panel, which can be read via SNMP queries.
This information is optional.
E-mail Setup
Configure these settings to enable automatic e-mail notifications directly
from the panel. The information required for this is available from your
Network Administrator, or Internet Service Provider. (ISP)
E-mail: