Innovative Circuit Technology Ltd.
5
ICT200DB-12
Standard Dual 100A Bus Breaker Distribution Panel for +/-12,
24 or 48VDC
INSTALLATION
Inspect your distribution panel to ensure it was not damaged in shipping, and has
all accessories:
4 black plastic boots to insulate main dc power connections (shipped
with unit)
4 M8 size nut/washer/split-washer sets for high current bus connector
studs (shipped on unit)
2 three pin alarm output connector plugs (shipped on unit)
1 ten pin site monitor alarm input connector plug (shipped on unit)
Instruction Manual
8 ICT-BLP Breaker blanking plugs (included with ICT200DB models only)
for installation in un-used breaker locations
To complete the installation you will also need appropriate fuses (FKS-ATO type)
or circuit breakers (available from ICT) for each distribution channel you plan to
use. Twelve 15A 80VDC FKS-ATO blade fuses are shipped with each ICT200DF-
12IRC panel, while circuit breakers need to be ordered separately per the
following list for use on the ICT200DB-12IRC panel:
Breakers:
ICT Model
Rating (65VDC) Mfg. Part Number
ICT-CB5
5A
CBI Electric BDG1ED-BOLXBS-0500X-1
ICT-CB15
15A
CBI Electric BDG1ED-BOLXBS-1500X-1
ICT-CB25
25A
CBI Electric BDG1ED-BOLXBS-2500X-1
Carling “M” series rocker handle circuit breakers with 0.25” tab terminals and
current ratings up to 25A may also be used, consult ICT for suitable part
numbers.
Fuses:
ICT Model
Rating (80V) Mfg. Part Number
ICT- 80VF15
15A
Little Fuse FKS-ATO fuse 166.7000.5156
For 12V and 24V systems standard 32VDC ATO style blade fuses may be used,
with current ratings up to 25A. These fuses are widely available from multiple
manufacturers.
CAUTION
Risk of personal injury or damage to equipment! Always observe the following:
Install unit in a restricted access location (such as an equipment rack) to limit
unintentional contact with terminals and wiring