background image

Innovative Circuit Technology Ltd.

 

digital voltmeter. If a battery is connected install the external fuse and close the 
disconnect switch. 
 
On units with the battery back-up option connected switch off the ac power, and 
use a hand held digital voltmeter to verify that the battery voltage is provided to 
the output load terminal. Switch AC power back on, and verify the output supply 
voltage rises to the normal output rating as the battery charges. 
 
The  unit  can  now  be  left  operating  normally.  As  long  as  the  external  back-up 
battery voltage is greater than the low voltage disconnect (LVD) level the battery 
will be connected directly to the supply output and will instantly power the load 
in case of an AC power failure. With AC power off the battery will then gradually 
be  discharged  by  the  load.  When  the  battery  voltage  drops  below  the  LVD 
disconnect  level the internal  relay will open, preventing the battery from being 
excessively discharged.  
 
When  AC  power  returns  the  supply  will  close  the  LVD  relay  and  charge  the 
battery  to  bring  the  voltage  back  up  to  the  float  voltage  level.  Battery  charge 
current is limited to the maximum rate determined by the charge current setting 
of SW 3 and 4 (see table on page 5), while the output voltage will be determined 
by the battery state of charge, and will rise to the output float voltage over time. 
The battery will be maintained at the supply output (float) voltage level until AC 
power is removed. 
 
Batteries connected directly to the supply output (not using the LVD option BAT 
terminal) will be charged to the supply output voltage level with a current limited 
to the maximum supply output rating. 
 
The  remote  shutdown  input  may  be  used  to  disable  the  supply  output  by 
applying a voltage from 2.5 to 16V, and the form-C alarm contacts can be used to 
remotely monitor fault conditions per the Status Indicators and Alarms table. 

 

PARALLEL OPERATION 

Up  to  3  matching  units  without  the  optional  battery  backup  capability  may  be 
connected  in  parallel  to  power  higher  current  loads.  The  unit  with  the  highest 
output voltage will initially provide most of the load current, and as load current 
increases the current supplied will tend to balance between the parallel units. 

 
 

CAUTION 

Risk of damage to equipment! 

 

Ensure battery current supplied through the optional internal LVD contactor 
cannot exceed the current rating of the unit 

 

Do not use the internal LVD contactor for parallel applications where load 
current can exceed the maximum rating of a single unit 

Summary of Contents for ICT690-12S

Page 1: ...ly INSTRUCTION MANUAL 855 343 001 Models ICT690 12S ICT690 12SB ICT690 24S ICT690 24SB ICT690 48S ICT690 48SB ICT1190 12S ICT1190 12SB ICT1190 24S ICT1190 24SB ICT1190 48S ICT1190 48SB DC Power Soluti...

Page 2: ...n to ensure installation and service is done with the battery de energised Use wire and connectors rated for the maximum load current and size of battery fuse or circuit breaker Ensure battery polarit...

Page 3: ...Innovative Circuit Technology Ltd 3 Table of Contents INTRODUCTION 4 CHECK and CONFIGURE UNIT 4 INSTALLATION 6 OPERATION 7 Status Indicators and Alarms 9 PRODUCT SPECIFICATIONS 10 LIMITED WARRANTY 12...

Page 4: ...n B Remote on off control input for external control of the output Floating Form C alarm contact output supports remote monitoring of unit operation Model 1 Output Voltage V Max Output Current A Conti...

Page 5: ...r BAT terminal if required Do not ground both the load and battery as this may bypass the internal LVD circuitry AC input wiring to the Pro Series unit must be protected using an outlet with a branch...

Page 6: ...cording to the following chart LVD Setting 12V 24V 48V BAT SW1 Setting BAT SW2 Setting Disconnect V Default 11 5 23 46 x 1 Disconnect V low setting 10 5 21 42 x 0 Reconnect V Default 12 5 25 50 1 x Re...

Page 7: ...nal LVD contactor is always connected to the battery positive as shown NOTE Do not ground the battery POS terminal as this may bypass the internal LVD relay Connect the remote on off control or unit f...

Page 8: ...d by the charge current setting of SW 3 and 4 see table on page 5 while the output voltage will be determined by the battery state of charge and will rise to the output float voltage over time The bat...

Page 9: ...rs when battery voltage falls below the LVD threshold OFF OFF ON System Fault Indicates internal circuit fault Clears when all fault conditions are cleared Battery power only Enabled ON Dead or Discon...

Page 10: ...12 5A Output Power max 3 1200W 690W 1200W 690W 1200W 690W Output Noise max mVrms 30 30 30 30 40 40 Input Current max at 120Vac 12A 7A 12A 7A 12A 7A LVD Threshold V Default 11 5V 11 5V 23 0V 23 0V 46...

Page 11: ...in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to r...

Page 12: ...to ensure that ICT product manuals and promotional materials accurately describe ICT product specifications and capabilities at the time of publication However because of ongoing improvements and upda...

Reviews: