Error Code Indication

When the module attempts to register or communicate with the system controller a registration error can be
generated indicating that it was not successful.

Error Code Display

The following table is only valid if the

fault

indicator is

constantly on

and the

status

indicator is

flashing red

.

If the fault indicator is

flashing

the module requires a firmware update or is currently in firmware update mode.

The status indicator will

flash red

with the error code number. The error code number is shown with a 250ms on

and off period (duty cycle) with a delay of 1.5 seconds between each display cycle.

Flash

Error Description

1

Unknown Error Code

The error code returned by the system controller could not be understood by the module.

2

Firmware Version

The firmware version on the module is not compatible with the system controller. To clear this error,
update the module using the module update feature in the controller's web interface.

3

Address Too High

The module address is above the maximum number available on the system controller. To clear this
error change the address to one within the range set on the system controller, restart the module by
disconnecting the power.

4

Address In Use

The address is already in use by another module. To clear this error set the address to one that is not
currently occupied. Use the view network status command to list the attached devices, or the network
update command to refresh the registered device list.

5

Controller Secured Registration Not Allowed

The controller is not accepting any module registrations. To allow module registrations use the network
secure command to change the setting to not secured.

6

Serial Number Fault

The serial number in the device is not valid. Return the unit to the distributor for replacement.

7

Locked Device

The module or system controller is a locked device and cannot communicate on the network. Return
the unit to the distributor for replacement.

PRT-IO84-DIN | Protege DIN Rail 8 Input 4 Output Expander | Installation Manual

16

Summary of Contents for PRT-IO84-DIN

Page 1: ...PRT IO84 DIN Protege DIN Rail 8 Input 4 Output Expander Installation Manual...

Page 2: ...chanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo...

Page 3: ...ors 14 Status Indicator 14 Fault Indicator 14 Power Indicator 14 Output Indicators 14 Input Status Indicators 15 Error Code Indication 16 Error Code Display 16 Mechanical Diagram 17 Mechanical Layout...

Page 4: ...twork architecture allows large numbers of modules to be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distan...

Page 5: ...ements This equipment is to be installed in accordance with The product installation instructions The Local Authority Having Jurisdiction AHJ PRT IO84 DIN Protege DIN Rail 8 Input 4 Output Expander In...

Page 6: ...er wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installatio...

Page 7: ...Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings The Dialer s Earth Ground Connection applies...

Page 8: ...stalled in an electrical room communication equipment room secure cabinet or in an accessible area of the ceiling 1 Position the DIN rail module with the labeling in the correct orientation 2 Hook the...

Page 9: ...tage to all devices on the RS 485 network Warning The 12V N and N communication input must be supplied from only one point Connections from more than one 12V supply may cause failure or damage to the...

Page 10: ...hen a wire fault short circuit or a cut wire tampered in the line occurs When using the EOL resistor configuration the EOL resistor option must be enabled in the input programming so that the tamper a...

Page 11: ...tem and the trouble type and group that they activate Input Number Description Type Group ZXxxx 01 03 Reserved None None ZXxxx 04 Aux Failure Power Fault General ZXxxx 05 15 Reserved None None ZXxxx 1...

Page 12: ...shows the control of an external LED indicator Output Connection Output 2 Shown 1K5 OHM 12VAUX 0V LED V V NC C NO NC C NO Warning Switching inductive loads that can produce high back EMF voltages or...

Page 13: ...product Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When adding...

Page 14: ...normal operation Fault Indicator The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firm...

Page 15: ...the physical input number This allows for easy test verification of inputs without the need to view the inputs from a keypad or the Protege software State Description Fast flash Input is in a SHORT s...

Page 16: ...feature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the...

Page 17: ...m The mechanical diagram below outlines the essential details needed to help ensure the correct installation of the input output expander PRT IO84 DIN Protege DIN Rail 8 Input 4 Output Expander Instal...

Page 18: ...ils needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 156 80 44 68 Front 139 18 72 00 2x 4 67 Screw Hole 17 03 42 40 42 40 156 80 35 40 Back PRT I...

Page 19: ...Weight 310g 10 9oz Gross Weight 380g 13 4oz Operating Conditions Operating Temperature 10 to 55 C 14 to 131 F Storage Temperature 10 to 85 C 14 to 185 F Humidity 0 93 non condensing indoor use only r...

Page 20: ...General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT IO84 DIN Protege DIN Rail 8 Input 4 Output Expan...

Page 21: ...your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For b...

Page 22: ...ne input for masking To comply with EN 50131 1 Do not fit more than 10 unpowered detectors per input Do not fit more than one non latching powered detector per input Do not mix unpowered detectors and...

Page 23: ...General Product Statement The UKCA Compliance Label indicates that the supplier of the device asserts that it complies with all applicable standards PRT IO84 DIN Protege DIN Rail 8 Input 4 Output Exp...

Page 24: ...s device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHAN...

Page 25: ...s class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme la norme NMB 003 du Canada CAN ICES 3 A NMB 3 A PRT IO84 DIN Protege DIN Rail 8 Input 4 O...

Page 26: ...be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design a...

Page 27: ...aimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circumstances to...

Reviews: