SAFETY & WARNINGS

 

Read this manual carefully and understand all Warnings and Cautions before connections are 
made to the Inverter. If unsure about any aspects of the installation call ICT Technical Support 
at (604) 856-6303, 8:00AM to 4:30PM Pacific Standard Time.

4

WARNING:

 Check the battery polarity and voltage before connecting the unit. Incorrect 

polarity will damage the unit.

4

WARNING: 

Make sure that all the DC connections are tight. Loose connections could result 

in Overheating and can be a potential hazard.

4

WARNING: 

The AC neutral lead is internally bonded to chassis. The chassis must be 

bonded to earth ground through the external ground connector located at the back of the unit.

4

WARNING: 

Do not attempt to operate the Inverter from any power source other than a 

battery.
     The 12 Volt Inverter (ICT300-12SNV) must be connected to a 

12 Volt

 battery.

     The 24 Volt Inverter (ICT300-24SNV) must be connected to a 

24 Volt

 battery.

     The 48 Volt Inverter (ICT300-48SNV) must be connected to a 

48 Volt

 battery.

     Connecting the Inverter to any other battery may damage to unit.

4

WARNING:

 Calculate the total power consumption (W) of the output load. Make sure the 

total power consuption does not exceed the rated load capacity of the Inverter.

4

CAUTION:

 No user serviceable parts inside. Only ICT personnel are authorized to service 

the unit.

4

CAUTION:

 It is the installerʼs responsibility to ensure compliance with all applicable 

installation codes and regulations.

4

CAUTION:

 Before any connections are made to the unit or system, be sure to disconnect 

the battery terminals. Always disconnect the grounded battery terminal first. When 
reconnecting, connect ungrounded terminal first, and grounded terminal last.

4

CAUTION:

 Avoid mounting the unit near sources of moisture, flammable gases or fumes.

4

CAUTION:

 Do not block the fan opening on the front of the Inverter.

4

CAUTION:

 Follow the provided wire size recommendations provided in this manual. DC 

connection cables should be as short as possible and large enough to handle the required 
current in accordance with the electrical codes or regulations applicable to your installation. 
Cables that are not an adequate gauge, or are too long, will result in excessive voltage drop, 
decrease inverter performance, and possibly damage the unit.  

4

CAUTION:

 To ensure that the Inverterʼs safety features are not compromised, use the 

Inverter as specified in the manual and do not substitute parts or make any unauthorized 
modifications.

4

Install an in-line fuse (not supplied) in the positive lead from the battery to the Inverter (see 

    page 4).

1

Summary of Contents for SITE INVERTER 300

Page 1: ...ICT SITE INVERTER 300 855 131 001 INSTRUCTION MANUAL The Power of Reliability INNOVATIVE CIRCUIT TECHNOLOGY LTD ...

Page 2: ...not exceed the rated load capacity of the Inverter 4CAUTION No user serviceable parts inside Only ICT personnel are authorized to service the unit 4CAUTION It is the installerʼs responsibility to ensure compliance with all applicable installation codes and regulations 4CAUTION Before any connections are made to the unit or system be sure to disconnect the battery terminals Always disconnect the gr...

Page 3: ...ERTER 300 is designed specifically for communications site applications and includes the following features Two rear facing AC outlets for easy access to the equipment that needs to be powered Rear mounted DC input studs for connection to the DC battery source A grounding stud on the rear of the unit Front mounted power switch and LED indicator lights Thermo controlled ball bearing brushless cooli...

Page 4: ...6 Vdc for 24V Inverter 47 2 Vdc for 48V Inverter Over Voltage Protection The Inverter will shut down if the battery voltage exceeds 16 0 Vdc 32 0 Vdc for 24V Inverter 64 0 Vdc for 48V Inverter The Inverter will automatically restart when battery voltage drops below 15 0 Vdc 30 0 Vdc for 24V Inverter 60 0 Vdc for 48V Inverter Over Temperature Protection If the Inverter is subjected to higher ambien...

Page 5: ...d input wire sizes Ensure the positive terminal of the battery is connected to the Positive Input of the inverter and the negative terminal of the battery to the Negative Input of the inverter Incorrect polarity will blow the internal fuse and damage the unit 4 TO AC LOADS IN LINE FUSE BATTERY INVERTER EARTH GROUND Figure 3 ICT Inverter Wiring Diagram 5 Plug your AC loads into the AC Outlets locat...

Page 6: ... feet 4 AWG 52043 8 AWG 52041 10 AWG 34855 Note Use TE Connectivity Amp part number for Terminal Connector listed in brackets after the wire gauge size or equivalent OPERATION Turn the Power Switch located on the front panel to the ON position The Green LED below the Power Switch should turn on to indicate the inverter is operational Status of LED Indicator Lights AC Status LED Fault LED Status GR...

Page 7: ...lation if this happens PRODUCT SPECIFICATIONS ICT300 12SNV ICT300 24SNV ICT300 48SNV Input Voltage 10 5 16 0 Vdc 21 0 32 0 Vdc 42 0 64 0 Vdc Output Voltage 115 Vac 5V Output Waveform Pure Sine Wave Output Frequency 60 Hz 0 05 Hz Total Harmonic Distortion THD 3 THD Continuous Output Power 300 Watts Maximum Surge Power 600 Watts for 3 seconds No Load Power Consumption 4 Watts Efficiency full load 90...

Page 8: ...aterials accurately describe ICT product specifications and capabilities at the time of publication However because of ongoing improvements and updating of ICT products ICT cannot guarantee the accuracy of printed materials after the date of publication and disclaims liability for changes errors or omissions If this ICT product is not in good working order as outlined in the above warranty your so...