Assembly instructions for KS-Tower Series
ASSEMBLY INSTRUCTIONS
Selection of fastening material:
Material and corrosion resistance:
the choice of material for the fasteners is
dependent on the installation environment
and operating conditions (e.g. galvanised,
stainless steel, etc.), strength grade 4.8 - 8.8
Type of screw:
depends on the substructure (e.g. hexagon
screws, T-head screws, rod threaded, etc.);
not included in delivery
Fastener diameter:
depends on the Cable Clamp
(dimension: metric screw thread [M])
Fastener Length:
depends on the number of stacked Cable
Clamps, the cable outer diameter and
type of substructure
Application with Elastic Inlays:
on-site fixing with any form of adhesive (e.g.
glue, silicone or paste) will void the warranty
immediately
Tighten nuts with an appropriate torque wrench alternately only up to the specified tightening torque.
Do not use self-securing/self-locking nuts, this prohibits a defined tightening torque.
List of individual components Double Tower:
Cable
Clamp type
Quantity of
Clamp type
Quantity of Universal
Adapter-Set (AS)
Outer diameter
of cable
Metric screw
thread (M)
Recommended
length of thread*
KS 25/36
2
1
25-36 mm
M10
220 mm + x
KS 33/46
2
1
33-46 mm
M10
250 mm + x
Tightening Torque: 15 Nm
Tightening Torque: 5 Nm
Only flat washers may be used.
No spring or snap rings!
2x
2x
2x
2x
2x
2x
Tightening Torque: 5 Nm
Tightening Torque: 5 Nm
* For maximum permited outer cable diameter (can be reduced accordingly for smaller diameters)
x
corresponds to the height of the substructur.
It is essential to respect the specified tightening torques, especially for the top part, to guarantee
perfect and reliable functioning of the cable installation for the long-term.**
îd-Technik GmbH
, Hohe Strasse 34-36, 68526 Ladenburg, Germany,
Tel.: +49 (0) 6203 107 95 88, Fax: +49 (0) 6203 107 95 52, www.id-technik.com, info@id-technik.com
Technical changes and errors reserved.
Page 2 of 2
Date 10/2020
** Contact îd-Technik for trailing cables (EPDM, rubber, etc.), please.