INSTALLATION
12
Buccaneer GT Range
- Installation
8
COMMISSIONING
CONTROL PANEL
Description
1.
On/Off switch
2.
Burner switch:
Used for switching OFF (summer position ) or switching ON (winter position ), by means of action
on the burner and the pump (the operation of the D. H. W. is not stopped). In case of fitting an SV-matic regulator or an
D. H. W. priority (SVR), this switch is put out of service by the regulator.
3.
Heating accelerator switch:
Used for switching OFF (summer position ) or switching ON (winter position ) the
accelerator.
In case of fitting a regulator or an SVR module, it must be set to the winter position .
4.
Boiler thermometer
5.
3 position switch:
Manual position, this position must be used for boilers which are not equipped with SV-matic regulation or
room temperature thermostats.
The temperature of the boiler is regulated by the boiler thermostat 7. This position can be used to test the
burner on an installation equipped with SV-matic regulation or with a room temperature thermostat.
AUTO
Automatic position, this position must be used for normal operation for boilers equipped with SV-matic
regulation or room temperature thermostats.
TEST STB:
Temporary action to test the safety thermostat
6.
Safety thermostat
With manual reset (factory setting - 100°C)
7.
Boiler thermostat:
It can be adjusted from 30 to 85°C. However, a factory fitted stop limits the temperature to 75°C.
This stop can be moved if necessary. The boiler thermostat must compulsorily be set at maximum in case an SV-matic
regulator or a room temperature thermostat is fitted.
8.
Fuse
4 AT
9.
Place for an SV-matic regulator or the SVR option
10. Place for the possible hour run meter