2
Buccaneer GTE -
Installation & Servicing
GENERAL
Note
.
Fuel rates and flue gas data relate to maximum output ratings.
Gas firing data relates to the use of NATURAL GAS ONLY.
Details for the use of LPG are available on request from Caradon
Ideal Ltd.
Natural gas consumption is calculated using a calorific value of
38.7MJ/m
3
(1038Btu/ft
3
) gross or 34.9MJ/m
3
(935Btu/ft
3
) nett at
15
o
C and 1013.25mbar.
* The value is used in the UK Government's Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by a notified body.
Table 1 Performance Data
Boiler
GTE 4
GTE 5
GTE 6
Number of Sections
4
5
6
Maximum
kW
27
33
39
Heat Output
Btu/hx10
3
92.1
112.6
133.1
Minimum
kW
21
27
32
Heat Output
Btu/hx10
3
71.7
92.1
109.2
Hydraulic
mbar
5.3
7.9
10.9
Resistance at 11k
in w.g.
2.1
3.2
4.4
Hydraulic
mbar
1.6
2.4
3.3
Resistance at 20k
in w.g.
0.6
1.0
1.3
Combustion Chamber
mbar
0.23
0.23
0.22
Resistance (at zero draught)
in w.g.
0.01
0.01
0.01
Minimum Draught at Smokehood mbar
0.12
0.12
0.11
Outlet (for max. output)
in w.g.
0.048
0.048
0.044
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989
. The manufacturer's
notes must NOT be taken, in any way, as overriding statutory
obligations.
IMPORTANT
. These appliances are CE certified for safety and
performance. It is, therefore, important that no external control
devices, e.g. flue dampers, economisers etc., are directly
connected to these appliances unless covered by these
Installation and Servicing Instructions or as otherwise
recommended by
Caradon Ideal Limited
in writing. If in doubt
please enquire.
Any direct connection of a control device not approved by
Caradon Ideal Limited
could invalidate the certification and the
normal appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
Maximum Gross
l/h
3.11
3.80
4.48
Oil Rate
gal/h
0.683
0.836
0.986
Maximum Flue
m
3
/s
0.017
0.022
0.025
Gas Volume at 12% CO
2
ft
3
/min
36
47
53
Flue Gas CO
2
/ Temperature
% /
o
C
12 / 180
12 / 190
12 / 190
Oil
Maximum
m
3
/h
3.10
3.79
4.47
Gas Rate
ft
3
/h
109.4
133.9
158.0
Maximum Flue
m
3
/s
0.019
0.026
0.027
Gas Volume at 9% CO
2
ft
3
/min
40
49
57
Flue Gas CO
2
/ Temperature
% /
o
C
9 / 180
9 / 190
9 / 190
Gas
Part Load Efficiency (Gross)
%
86.0
85.0
84.4
*Seasonal Efficiency (SEDBUK)
[79.9]% Band D
[79.9]% Band D
[79.9]% Band D
Table 2 General Data
Flow Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
4
"
Return Connection
R 1
1
/
4
"
R 1
1
/
4
"
R 1
1
/
4
"
Maximum Operating Pressure
bar
4
4
4
Boiler Thermostat Setting
C
30 - 90
30 - 90
30 - 90
Safety Thermostat Setting
C
110
110
110
Nominal Flue
m m
125
125
153
Diameter
in.
5
5
6
Boiler Water
l
24.5
30
35.5
Content
gal
5.4
6.6
7.8
Boiler DRY Weight
kg
182
210
237.5
less Burner Unit
lb
401.5
463
523.5
Part Load Efficiency (Gross)
%
89.5
88.5
87.8
*Seasonal Efficiency (SEDBUK)
[85.7]% Band C
[85.7]% Band C
[85.7]% Band C