FLUING
According to the output, the difference between the
temperature of the flue gas and the ambient temperature can
be as low as 160
o
C. The installer will have to respect all of the
usual precautions (dilution - piping - T for removal of
condensation) in order to prevent deterioration of the chimney.
30-45
500 minimum
buc5495
Boiler
FLUE SIZE
Refer to applicable regulations while determining the size
and height of the flue. Please note that GTE boilers have
pressurised and sealed combination chambers and that the
pressure at the outlet must not exceed 0 mbar.
Detailed recommendations relating to the design of flues for
GAS fired appliances are quoted in BS. 6644 and British Gas
Publication No. IM11, whilst BS. 5410 Pt. 1 similarly applies to
OIL fired boilers.
Boiler
Power
Required
Draught
Mass Flow of Flue Gases
kg/s
Natural Gas
9% CO
2
Flue Gas
Temperature
(1) (2)
Chimney:
Minimum Recommended
Dimensions
kW
mbar
o
C
Ø min
m m
Height
m
GTE 4
21-27
0.12
0.014
0.014
< 180
125
6.5
GTE 5
27-33
0.12
0.017
0.017
< 190
125
7
GTE 6
33-39
0.11
0.020
0.020
< 190
153
7
(1) : at boiler high power
(2) : Boiler temperature: 80
o
C (ambient temperature : 20
o
C)
Fuel Oil
12% CO
2
The table below contains the minimum dimensions of the flue
required for each boiler model in order to ensure sufficient
draught at the outlet.
However, care must be taken to comply with any applicable
national or local regulations.
285
392
F
Flue outlet
Boiler Dimension
F
GTE 4
50
GTE 5
50
GTE 6
99
buc5493
8
DIMENSIONAL INFORMATION REQUIRED FOR THE FLUE CONNECTION
Connection
The connection must be made in a competent manner with
airtight pipe in a material that is resistant to hot gases from the
combustion and possible acid condensation. This pipe must
be as short as possible, be removable and without any
sudden change in its section.
The diameter must always be at least equal to that of the boiler
outlet.
FLUE OUTLET