21
Henrad SE FF
- Installation
INSTALLATION
SIDE FLUE OUT
LET
28 MOUNTING THE BOILER
29 CONNECTING THE FLUE TO THE BOILER
1. Lift the boiler onto the wall mounting plate, as
shown.
2. Check the boiler alignment using a spirit level
and adjust as necessary with the jacking
screw.
3. Align the hole in the jacking plate with the pre-
drilled hole in the wall and fix in position with
the No.10 x 2" screw provided.
Note.
BEFORE fitting the flue turret, fill the condensate siphon
within the boiler by pouring a cupful of water into the flue
outlet A.
1. Insert the flue assembly through the prepared hole in the wall
far enough to allow the rubber seal to unfold completely and
form an adequate seal on the outside wall.
2. Pull the flue back and locate the flue turret on the top of the
boiler, ensuring that the seal is in place.
3. Secure the flue turret on top of the boiler by inserting the open
ends of the turret clamp under the 2 studs and
fixing it in the middle with the
single M5 x 10mm pozi-hex
screw provided.
4. Flues over 1 metre long.
Fix the flue support bracket to the
wall, using the wall plug and
wood screw.
For standard installations use
the short wood screw.
5. Now make good the inside wall
face around the flue.