5
Mexico Super CF 3/60P - 3/140P -
Installation
GENERAL
LOCATION OF BOILER
The boiler must be installed on a flat and level floor, capable of
adequately supporting the weight of the boiler and any
ancillary equipment.
The boiler may be fitted on a combustible floor.
Insulation is not necessary, unless required by the local
authority.
The boiler must not be fitted outside.
The boiler must not be installed in a bedroom or in a room
containing a bath or shower.
Timber Framed Buildings
If the boiler is to be fitted in a timber framed building it should
be fitted in accordance with the Institute of Gas Engineering
document IGE/UP/7:1998.
Compartment Installations
A compartment used to enclose the boiler MUST be designed
and constructed specially for this purpose.
An existing cupboard or compartment may be used, providing it
is modified for the purpose.
Details of essential features of cupboards /compartment
design, including airing cupboard installation, are to conform to
the following:
z
z
z
z
z
BS. 6798.
z
z
z
z
z
The position selected for installation MUST allow
adequate space for servicing in front of the boiler
and for air circulation around the boiler.
Side clearance is only necessary for installation. The
amount of side clearance will depend upon the type of
connection used.
z
This position MUST also permit the provision of a
satisfactory flue and an adequate air supply.
z
For the minimum clearances required for safety, and
subsequent service, see Frame 2.
GAS SUPPLY
The local propane supplier should be consulted, at the
installation planning stage, in order to establish the availability
of an adequate supply of gas.
Check that the appliance is suitable for the proposed gas
supply.
Installation pipes, cylinders and pressure regulators should be
fitted in accordance with BS. 5482.1.
Bulk tank installations must comply with the Home Office code
of practise for the storage of liquified petroleum gas at fixed
installations.
The complete installation MUST be tested for gas soundness
and purged as described in the above code.
GAS SAFETY
Gas Safety (Installation and Use) Regulations 1994,
amendments 1996 or rules in force.
It is law that
all
gas appliances are installed by a CORGI
registered installer (identified by
) in accordance with the
above regulations. Failure to install appliances correctly could
lead to prosecution. It is in your own interest, and that of safety,
to ensure the law is complied with.
The installation of the boiler MUST also be in accordance with
the latest I.E.E. (BS 7671) Wiring Regulations, local building
regulations, bylaws of the local water authority, the Building
Regulations and Building Standards (Scotland) and any
relevant requirements of the local authority.
Detailed recommendations are contained in the following
British Standard Codes of Practice:
BS. 6891
Low pressure installation pipes.
BS. 6798
Installation of gas fired hot water boilers of rated
input not exceeding 60 kW.
BS. 5449:1
Forced circulation hot water systems (small bore
and microbore domestic central heating systems).
BS. 5546
Installation of gas hot water supplies for domestic
purposes (2nd Family Gases).
BS. 5440: 1
Flues for gas appliances of rated input not
exceeding 60 kW.
BS. 5440: 2
Ventilation for gas appliances of rated input not
exceeding 60 kW.
BS 7593
Treatment of water in Domestic Hot Water Central
Heating Systems.
Health and Safety Document No. 635.
The Electricity at Work Regulations, 1989.
Manufacturer’s notes must NOT be taken in any way as
overriding statutory obligations.
IMPORTANT.
These appliances are certificated by the British Standards
Institution for safety and performance. It is important, therefore,
that no external control devices, e.g. flue dampers,
economisers etc., are directly connected to these appliances
unless covered by these Installation and Servicing Instructions
or otherwise recommended by
Caradon Plumbing Ltd.
in
writing. If in doubt please enquire.
Any direct connection of a control device not approved by
Caradon Plumbing Ltd.
could invalidate the BSI Certification
and the normal appliance warranty. It could also infringe the
Gas Safety Regulations and the above regulations or other
statutory requirements.