20
Optia HE
-
Installation & Servicing
INSTALLATION
SIDE FLUE OUTLET
cla7667
Downward
piping
bracket
Wall mounting
bracket
25 WALL MOUNTING PLATE
For flue lengths greater than 775mm refer to
Frames 28, 29 and 30 - Flue extension ducts.
1.
Measure and note the side flue length "Y" (refer to Frame
10).
2.
Add 143mm (5
5
/
8
") to dimension "Y" and measuring from
the ring, cut both outer and inner tube. Ensure support
clip is in position to facilitate cutting.
3.
To ensure the tube is cut square, mark the flue all the way
round.
4.
Cut to length and remove any burrs.
24 FITTING THE FLUE ASSEMBLY
1.
Insert the flue assembly through the hole.
2.
Ensure the flue terminal is in the correct position.
23 CUTTING THE FLUE - For flue lengths 270 to 775mm ONLY
1.
If downward routing of pipes is required then the
downward routing wall bracket supplied in the
downward piping kit should be fitted to the wall
now.
2.
Fix the mounting plate to the wall with the No. 14 x
50mm wood screws or to the downward piping
bracket with the M6 x 12 Hex hd screws provided.
3.
Check with a spirit level that the plate is horizontal.
cla7704
cla7841
201962-6.pmd
19/02/2008, 15:10
20