09
EVO S 50 - 135kW
GENERAL DATA
MODEL
50
70
95
115
135
Gas Supply
G20 to G31
G20
Gas Supply Connection
G1
”
Flow Connection
G1
¼”
Return Connection
G1
¼”
Max Pressure (sealed system)
Bar (psi)
4.0 (58)
Electricity Supply
230V - 50Hz
Power Consumption
W
138
96
160
206
263
IP Rating
IP24D
Nominal Flue Size (concentric)
mm
80/125
100/150
Condensate Drain
mm
24
Water Content
l
5.0
9.0
10.2
12.8
15.3
Dry Weight
Kg
60
90
95
100
125
Noise emission @1m: @maximum modulation
dB(A)
59.7
57.3
58.5
61.6
59.3
Noise emission @1m: @minimum modulation
dB(A)
35.8
33.5
34.3
35.4
36.8
OPTIONAL KITS
BOILER
EVO S
Modulating Sequencer kit
Programmable Room Thermostat kit
Outside sensor kit
Tank Sensor kit
Room sensor kit
Multi boiler low height frame & header kits
Clip In kit: +1 circuit, up to 2 per Boiler
LPB Bus Communication Module