Page 19 of 28
Quick Start Guide Stabiliti™ Series PCS
MAN-00114, Rev D
the Converter within the 16-bit range of 0-65535 for unsigned and -32768 to 32767 for signed
values.
These scaling factors apply to re
ad only “measurement registers”, as well as read/write “setpoint
registers” used to set desired output voltage, current, or power levels. The setpoint registers are
generally not utilized in 30C stand-alone applications.
Table 4: Register Scaling Factors
In 30C3 applications,
a DC power command of +1500 on DC3 will deliver 15 kW of “export
power” (charging a battery). Conversely, a DC power command of -1000 on DC3 will deliver 10
kW of “import power” (discharging a battery).
The ramp rate command is a modifier of the power command defined above. It limits the port
ramp rate (power, current, or voltage depending on selected Control Method). A power ramp
rate setting of 300 limits the ramp up or ramp down of the commanded port to a 3 kW/second
rate.
Type
Scaling Factor
Register
Read/Write
Actual Value
AC / DC Port
Voltage
1 unit = 1.0 V
100
100 Vac / 100 Vdc
DC Port Current
1 unit = 0.1 A
100
10.0 A
DC Port Power
1 unit = 10 W
100
1000 W
AC Port Real
Power
1 unit = 10 W
100
1000 W
AC Port Reactive
Power
1 unit = 10 Var
100
1000 Var (1 kVar)
AC Port Voltage
Ramp Rate
1 unit = Volts per
second
100
100 V/second
DC Port Current
Ramp Rate
1 unit = 0.1 A per
second
100
10 A/second
AC/DC Port Power
Ramp Rate
1 unit = 10 W per
second
100
1000 W/second
Frequency
1 unit = 0.001 Hz
6000
60 Hz