Installation & Operations Manual SunDial
™ Series PV Inverter
Product Models: 30PV; 30PVF; 30PV+S; 30PVF+S
MAN-00117, Rev C
Page
11
of
31
AC Frequency and Voltage Fault Detection
The quality of the power delivered to the utility line must meet or exceed the
requirements as specified in IEEE 1547a. If the utility frequency or voltage shifts outside
the regulatory specified limits, the Inverter will automatically detect the condition and
shutdown. The Inverter is shipped from the factory with a default five (5) minute restart
counter for AC over/under Frequency limit faults and AC over/under voltage limit faults.
Regulatory Information
The 30PV; 30PVF; 30PV +S; 30PVF+S PV Inverters are certified to the following
standards for the North American market:
•
UL 1741
: Standard for Battery Inverters, Inverters, Controllers, and
Interconnection System Equipment for Use with Distributed Energy Resources
•
IEEE 1547a
: Distributed Resources Interconnection and Interoperability with the
Grid
•
UL 1998:
Software in Programmable Components
SECTION 3.0 System Specifications
Maximum AC Input Voltage
528 Vac
Maximum DC Input Voltage
1000 Vdc
AC Operating Voltage Range
422 to 528 Vac
DC Operating Voltage Range
100 to 1000 Vdc
DC Maximum Input Current
60 A (10 A per PV
string)
DC Minimum Start-up Current
1 A
AC Maximum Input Current
44 A
AC Minimum Start-up Current
1 A
Output Power Factor Range
0.95 Leading to 0.95
Lagging
Operating Frequency Range
57 to 64 Hz
Nominal AC Output Voltage
480 Vac
Nominal DC Output Voltage
750 Vdc
Nominal Output Frequency
60 Hz
Maximum AC Continuous Output Power
29.99 kW
Maximum DC Continuous Power
30 kW
Maximum AC output overcurrent protection (software) 44 A RMS
Maximum DC output overcurrent protection
(software)
60 A