General Data Concord ES/H (140 - 380)
•
High/Low adjustable operation on all models
•
High, full and part load efficiencies -
meets Building Regulations 2006 (Part L2)
•
Assembled or unassembled
heat exchanger availability
•
Robust cast iron heat exchanger
•
Easy to install and service
•
Low return temperature capability
Model 140/H
160/H
180/H
200/H
220/H
260/H
300/H
340/H
380/H
Sections
8
9
10
11
12
14
16
18
20
Output (kW)
140
160
180
200
220
260
300
340
380
Height
1406
1406
1406
1406
1406
1406
1406
1406
1406
Width
970
1058
1146
1234
1322
1498
1674
1850
2026
Depth
1362
1362
1362
1362
1362
1412
1412
1412
1462
Flow/Return Connections (BSP)
R2
Gas Inlet (BSP)
RP1
RP1
RP1
RP1
RP1
RP1
1
/
4
RP1
1
/
4
RP1
1
/
4
RP1
1
/
2
Flue Size (mm)
250
250
300
300
300
350
350
350
400
Maximum Working Pressure (bar)
6
Water Content (L)
61
68
76
84
91
106
122
137
154
Approx Dry Weight (kg)
667
730
807
880
934
1096
1227
1364
1476
Front
(mm)
1000
Back
(measured from rear edge of jacket) (mm)
500
At sides Water connection side
(RH or LH) (mm)
400
At sides Non connection side
(RH or LH) (mm)
200
Boiler
Clearances
Concord ES/H
140 - 380kW
Option Kits
Boiler
ES/H
Hours run meter (1 or 2 hours)
✓
Flue gas thermometer
✓
13