SBE
®
& SBO
®
Connectors
Assembly instruction for SBE
®
80 & SBO
®
60 Series
two pole battery connectors with option for auxiliary contacts.
FOR INSTALLATION BY A QUALIFIED
ELECTRICIAN IN ACCOR
DANCE WITH NA-
TIONAL AND LOCAL ELECTRICAL CODES AND
THE FOLLOWING INSTRUCTIONS. THE SUIT-
ABILITY OF THIS TYPE OF TERMINATION MUST
BE EVALUATED BY UNDERWRITERS’ LABORA-
TORIES, INC. AND CANADIAN STANDARDS. AS-
SOCIATION FOR THE END USE APPLICATION:
Assemble contacts to the cables according to the
equipment manufacturer’s assembly instructions.
The following instructions are supplied as a refer-
ence. Please note: instructions are included with each
crimp tool for proper use.
Contains one (1) housing and two (2) contacts.
1. CONNECTOR RATINGS
2. TOOLING CHART
3. REDUCING BUSHING
4. CABLE STRIPPING DIMENSIONS FOR PRIMARY POWER CONTACTS
Max Cable Size
Series Amperes Volts AWG mm²
SBE80 80
150 #6 16
SBO60 60
600 #6 16
Bushing
Wire Size
For Use With
Part Number AWG (mm²) Contact Part Number
5910
#10-12 (5.3 - 3.3) 1339G1
5912
#8 (8.4)
1399G1
Connector
Strip “X” To
Series
Inches mm
SBE80 / SBO60
0.56
14
X
Contact
Wire
Pneumatic
Hand
Part Number” Size
Bench Tool + Die + Locator or Tool
1399G1
16 mm
1387G1
1388G6 1389G9
1309G4
5. RECOMMENDED SOLDERING TECHNIQUES
(
Use rosin flux solder only). Wrap cable strands, melt solder into well; heat and insert stripped
cable. Continue heating well until solder flows into wire being careful not to over flow onto
contact surfaces. DO NOT SOLDER DIP CONTACTS when contacts are soldered to
unsupported lead. Underwriters’ Laboratories, Inc. requires use of cable clamps, listed in table below.
6. CABLE / CONTACT & HOUSING ASSEMBLY
Observing polarity of markings, push each contact into rear of housing until notched side snaps
over spring, tug on cable to make sure contact is locked into place.
DISASSEMBLING CONNECTORS
Switch off power first. Remove contact by depressing spring with a small flat blade screwdriver
and pulling lightly on the cable.
CAUTION: Replace contacts individually on battery leads to reduce potential danger of shorting.
Connector
For Two Single
Series
Conductor Cables
SBE80 / SBO60 SBE80REDCLP-BK
HEADQUARTERS:
Anderson Power Products®, 13 Pratts Junction Road, Sterling, MA 01564-2305 USA T:978-
422-3600 F:978-422-0128 |
EUROPE:
Anderson Power Products® Ltd., Unit 3, Europa Court, Europa Boulevard,
Westbrook, Warrington, Cheshire, WA5 7TN United Kingdom T: +44 (0) 1925 428390 F: +44 (0) 1925 520203 |
ASIA
/ PACIFIC:
IDEAL Anderson Asia Pacific Ltd., Unit 922-928 Topsail Plaza, 11 On Sum Street, Shatin N.T., Hong Kong
T:+(852) 2636 0836 F:+(852) 2635 9036 |
CHINA:
IDEAL Anderson Technologies (Shenzhen) Ltd., Block A8 Tantou
Western Industrial Park, Songgang Baoan District, Shenzhen, PR. China 518105 T: +(86) 755 2768 2118 F: +(86) 755
2768 2218 |
TAIWAN:
IDEAL Anderson Asia Pacific Ltd., Taiwan Branch, 4F.-2, No.116, Dadun 20th St., Situn District,
Taichung City 407, Taiwan (R.O.C.) T: +(886) 4 2310 6451 F:+(886) 4 2310 6460 ”
www.andersonpower.com
All Data Subject To Change Without Notice 15515 1S6331 ASM-SBE/SBO REV 02