13
INSTALLATION
Classic
Slimline FF
-
Installation & Servicing
REAR FLUE OUTLET
Note.
If the
terminal is to be
sited within 25-
40mm of a corner
or vertical pipe
(refer to Table 3)
then the hole
MUST be
accurately cut and
the rubber
weather seal
trimmed around
the groove
provided.
The terminal wall
plate need not be
fitted.
Note.
Check all of the hole positions BEFORE drilling
11 FLUE ASSEMBLY - Exploded View
LEGEND
1.
Terminal.
2.
Weather seal.
3.
Flue assembly.
4.
Boiler sealing ring.
5.
Flue extension tube.
1.
An optional flue
duct extension kit
is required for
wall thicknesses
greater than
600mm (23
1/2
")
Refer to Frame 10.
2.
When cutting the
ducts, always use
the cardboard
support rings
provided.
1.
Separate the templates.
2.
Tape the templates into the selected position.
3.
Ensure squareness by hanging a plumb line as shown.
4.
Mark onto the wall (if required) the following:
a.
The wall mounting plate screw positions (choose
one from each group).
Note.
Mark the centre of the
flue hole as well as the circumference.
b.
The position of the flue duct hole.
5.
Remove the templates from the wall.
IMPORTANT.
Ensure that, during the cutting operation,
masonry falling outside of the building does not cause damage
or personal injury.
1.
Cut the flue hole, preferably with a 125mm (5") core boring
tool, ensuring that the hole is square to the wall. If the hole
has been quite accurately cut with a drill then making good
the wall faces is not essential as seals are provided at both
ends of the flue. However, both wall faces immediately
around the cut hole should be flat; make good if necessary.
For less accurate holes make good to approximately
125mm (5") diameter at the 2 wall faces.
2.
Drill 2 holes for the wall mounting plate with an 8mm (
5/16
")
masonry drill.
3.
Drill 1 further hole above the flue hole for boiler fixing with
the same 8mm (
5/16
") drill.
4.
Insert the plastic plugs provided.
13 PREPARING THE WALL
12 WALL MOUNTING TEMPLATE