Installation

5

GENERAL

Boiler Size

Cold Feed

Open Vent

CX 40 - 50

3/4

"

1"

CX 60 -100

1"

1/4

"

Sealed system filling point - refer to Frame 8

Flow and return connections are 2" BSP.

A 1" BSP tapping is provided in the redundant return flange for
the cold feed or expansion vessel connection.

Safety Valve

A safety valve must be sized and fitted in accordance with BS.
6644 for every type of system.  The valve should be set at 0.7
bar (10 lb/in.

2

) above the operating pressure in the boiler.  The

maximum safety valve setting is 0.7 bar (10 lb/in.

2

) above the

maximum design operating pressure of 4.5 bar (65 lb/in.

2

).

Cold Feed/Open Vent

The independent cold feed and the open vent must comply
with BS. 6644 and be of the following minimum size.

1

WATER CONNECTIONS

Control is by a slow opening combination gas control incorporating
a thermocouple flame failure device and mains voltage gas valve.
The control box has a terminal plug connection for mains input.

ELECTRICAL CONTROLS

The basic boiler is supplied with 2 printed circuit boards; designated
board No. 1C and board No. 6A.

Board No. 1C contains an adjustable electronic boiler thermostat
and board No. 6A contains a fixed setting pump overrun timer.  A
preset overheat thermostat is also provided.

OPTION KITS

Controls option

Three L.E.D.s are fitted to the boiler upper front panel fixing
indicating:

z

Boiler on

z

Overheat thermostat operation

z

Pilot failure (Lockout)

The facility for wiring remote indication of the above 3 conditions
is also provided.

An L.C.D. screen gives digital information of water flow and of
water flow  temperature.

Four additional ‘plug-in’ printed circuit boards; ‘No. 2, ‘No. 3', ‘No.
5’, and ‘No. 21’ are contained in this kit for fitting in the upper
control panel.

Pressure gauge kit

In addition to the above control kit, an optional pressure gauge
is also available for the range of boilers.  Details for fitting are
included with the pressure gauge.

Downdraught thermostat kit

This kit is optional when used on a single CX installation, but
mandatory when used on a multiple boiler installation.

DUTY

The range of boilers is suitable for: Combined indirect pumped
domestic hot water 

and

 central heating systems;  Independent

indirect pumped domestic hot water 

or

 central heating systems.

Fully pumped systems may be open vented or sealed.

The range of boilers is NOT suitable for:

1.

Gravity DHW systems.

2.

Gravity heating systems.

3.

Direct domestic hot water supply.

WATER CIRCULATION SYSTEM

Due to the compact nature of the boiler the heat stored within the
castings at the point of shutdown of the burner must be dissipated
into the water circuit in order to avoid the overheat thermostat
tripping. In order to allow pump operation after burner shutdown
the boiler control box incorporates a pump overrun facility which
operates for approximately 6 minutes after burner shutdown and,
in order to make use of this, the pump must be wired to the
appropriate terminal L

2

 (pump) in the boiler control box.

1.

The minimum flow rate as given in Table 4 must be
maintained whenever the boiler is firing and during the pump
overrun period.

2.

During the period of pump overrun there must be an open
circuit of adequate water volume and/or load.  The minimum
size of this circuit is given by the use of Graph 1.

Examples shown on Graph 1

a.

For the 

CX100 and CX 90

 the minimum circuit during pump

overrun could be a load of 6 kW with a volume of 31 litres or
any other combination given by the relevant line.

b.

For the 

CX 80 and CX 70

 the minimum circuit during pump

overrun could be a load of 2 kW with a volume of 45 litres or
any other combination given by the relevant line.

The above circuit capacity during pump overrun may be

Summary of Contents for Concord CX40

Page 1: ......

Page 2: ...2 Concord CX Installation CAUTION To avoid the possibility of injury during the installation servicing or cleaning of this appliance care should be taken when handling edges of sheet steel components...

Page 3: ...the law is complied with The Concord CX40 100 range of boilers has been tested and certified by British Gas to prEN656 for use with Natural gas only Multiple boiler installations The Concord CX range...

Page 4: ...in BSP 2 x 2 at rear Return tappings Rc in BSP 2 x 2 at rear Maximum static head metres feet 45 7 150 Maximum pressure bar p s i 4 5 65 Gas inlet connection Rc in BSP 3 4 3 4 1 1 Minimum dynamic mbar...

Page 5: ...auge kit In addition to the above control kit an optional pressure gauge is also available for the range of boilers Details for fitting are included with the pressure gauge Downdraught thermostat kit...

Page 6: ...learance should be given at the rear of the boiler for connection of gas and water pipework Additional clearance is required for access at either end of the installation 2 CLEARANCES DIMENSIONS Boiler...

Page 7: ...n will depend upon the particular characteristics of the system Pumping over of water into the expansion cistern must be avoided achieved either by provision of an adequate bypass circuit or by ensuri...

Page 8: ...setting Other British Standards applicable to commercial sealed systems are BS 6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 Working pressure 4 5 bar maximum Particular reference s...

Page 9: ...em which may be common or individual in the case of twin or multiple boiler installations must be capable of the complete evacuation of combustion products at all times The effective height of the chi...

Page 10: ...ngs 5 End section 6 Gas cock 13 Section bolt 14 Distribution tube 15 Tie rods 16 Thermostat pocket 17 Spillage skirt 18 Flueway baffles 19 Gas pipe 7 Drain cock 8 NOx duct 9 Front plate 10 Burner mani...

Page 11: ...g 2 BSP handling bars 9 Using the handling bars manoeuvre the boiler forwards on the packaging base and slide over collapsing base on to the floor Note Before manoeuvring the boiler into its final pos...

Page 12: ...er lower rear connection using the gasket and M10 x 25mm screws and washers provided 3 Temporarily screw the 2 handling bars 2 pipe into the top tappings and manoeuvre the boiler into position 4 Compl...

Page 13: ...e the flue connection 2 The boiler is designed to accept flues to BS 835 and should be sealed with an approved boiler putty 11 GAS CONNECTION 1 Connect the gas supply to the gas inlet pipe at the rear...

Page 14: ...e temperature sensing probe through the cable clips provided and into the thermostat pocket adjacent to the flow connection Fit the plastic Heyco bush over the sensor lead at the line shown and insert...

Page 15: ...cal supply such as a double pole switch having a 3mm 1 8 contact separation in both poles or a plug and socket serving only the boiler and system controls The means of isolation must be accessible to...

Page 16: ...atisfy the conditions in the foregoing paragraph If not all zones can do this then consider other means of control detailed on other sheets Normal operation When any thermostat is satisfied while othe...

Page 17: ...ls for heat its thermostat will open Zone 1 valve via the normally open contacts of the relay IMPORTANT Terminal L2 may control the appropriate pump s directly provided that the total running or start...

Page 18: ...groove in square head in line with the pipe 5 Press the overheat thermostat reset button 2 6 Push in and retain fully depressed the grey button 4 on the gas control 5 At the same time repeatedly push...

Page 19: ...ilitate speedy approximate adjustment of the gas rate After setting to the indicated pressure allow the boiler to operate for about 15 minutes to stabilise then check the gas rate by reference to a wa...

Page 20: ...the minimum flow rate given in Table 4 when that part of the system intended to be used for dissipation of residual heat only is in operation 26 HANDING OVER ROUTINE OPERATION Full instructions coveri...

Page 21: ...sitioned 3 The ignition electrode and lead are clean undamaged secure and correctly dimensioned Refer to diagram in Frame 28 4 The thermocouple tip is NOT burned or cracked 5 The thermocouple terminal...

Page 22: ...front plate fits behind the burner retaining returns when it is replaced Refit the flue baffles cleanout cover NOx duct casing top panel and casing door PILOT BURNER Check that 1 The pilot flame cover...

Page 23: ...ble in reverse order checking that the spark gap is as shown in Frame 28 SERVICING SERVICING To facilitate the replacement of components remove and replace the lower front panel NOx duct and the burne...

Page 24: ...ge connection 7 Test for gas soundness 35 MAIN BURNER 1 Remove the NOx duct and burner front plate as previously described in Frame 27 2 Both left and right hand burners can be removed by sliding each...

Page 25: ...in injector 3 off 9 Gas inlet manifold 10 Pilot gas pipe 11 Overheat thermostat piezo generator mounting bracket 12 O ring seal 13 Thermocouple 14 Spark electrode 15 Pilot draught shield 16 Pilot burn...

Page 26: ...ing in the clips provided Detail of Printed Circuit Board Support SERVICING 40 CONTROL BOX Basic Boiler Exploded View 41 CONTROL SENSOR 1 Remove the lower front panel Refer to Frame 27 2 Remove the se...

Page 27: ...OMBUSTION CHAMBER INSULATION REPLACEMENT The insulation boards used in the combustion chambers of these products contain man made fibres refractory fillers organic and inorganic binders and as such ar...

Page 28: ...mocouple and pilot gas pipe connections at the gas valve must be removed and the igniter lead pulled off at the igniter 4 The centre burner may now be removed by pushing it back to clear the injector...

Page 29: ...oming apart 8 Repeat the above procedure for all of the remaining sections until the assembly is complete 9 Fit the 4 tie rods through the holes in the sides of the end sections and fit a flat steel w...

Page 30: ...ical checks to be carried out during a fault finding procedure On completion of any service fault finding task which has required the breaking and remaking of electrical connections Check that the gap...

Page 31: ...ling for heat if necessary withdraw the sensor from the thermostat pocket NO NO 49 PILOT LIT BUT NO MAINS GAS NO NO Have you confirmed that the system controls are calling for heat YES FAULT FINDING Y...

Page 32: ...racket VERNITRON 60080 002 1 003 939 32 Ignition electrode and H T lead assembly VERNITRON 1 130 947 33 Thermocouple HONEYWELL Q 309 A 2762 1200mm long 1 002 937 34 Thermocouple interrupter lead assem...

Page 33: ...1 111 651 CX 70 1 111 652 CX 80 1 111 652 CX 90 100 1 111 653 50 Jacket top panel white stove enamel CX 40 1 111 293 CX 50 1 111 294 CX 60 1 111 295 CX 70 1 111 296 CX 80 1 111 297 CX 90 100 1 111 298...

Page 34: ...ursues a policy of continuing improvement in the design and performance of its products The right is therefore reserved to vary specification without notice Technical Training The Caradon Plumbing Lim...

Page 35: ...giving away a free boiler for the five best ideas every year to be selected by our Technical Director Please complete this form using extra sheets if required and post it or fax it to us on 01482 498...

Page 36: ...lease arrange for me to join an Ideal factory tour Range guides required The Ideal Guide a specifier s and installer s introduction to the Ideal domestic boiler range The Ideal Householders Guide to a...

Reviews: