35
Concord CXC -
Installation
56 FAULT FINDING DIAGNOSTIC CHART
Change outside
sensor.
Press [COPY]
GAS VALVE
FAULT
BOILER
SENSOR
FAULT
OVERHEAT
FAULT
OUTSIDE
SENSOR
FAULT
Check pump
connections.
Press [COPY]
Press O/H reset
button.
Press [COPY]
Check wiring.
Press [COPY]
Check water
flow.
Press [COPY]
Replace o/h stat.
Press [COPY]
Check system.
Press [COPY]
Refer to
screens
Refer to
screens
STANDBY
BURNER
LOCK OUT
Check HT leads
and electrode
positions
Change pump.
Press [COPY]
Refer to
screens
Check wiring.
Press [COPY]
PUMP FAULT
R
E
F
E
R
T
O
I
D
E
A
L
B
O
I
L
E
R
S
Is there a
spark ?
NO
AIR FLOW
FAULT
Check fan
rotates.
Replace if
necessary
Refer to
screens
Check gas
pressure.
Press [COPY]
Replace faulty
solenoid.
Press [COPY]
Refer to
screens
Change
gas valve
or
solenoid.
Press
[COPY]
Observe the display. Take actions as
follows, depending upon the display:
Check system.
Press [COPY]
Replace sensor
Press [COPY]
Press
[COPY]
Check
gas
valve
wiring.
Press
[COPY]
YES
Replace
detection
probe
Boiler will not light
Do any external
controls call for
heat ?
Is 230V ± 10%
available at
appliance ?
Reset timer or
status as
appropriate
Reset external
controls as
appropriate
Carry out electrical
checks.
Check all fuses.
YES
NO
NO
NO
YES
YES
Check boiler
programme timer and
status, as described
in Frame 28.
Does programme
timer require heat ?
Press
[COPY]
Check gas.
Press
[COPY]
Check
pressure
switch.
Replace if
necessary
Check wiring.
Press
[COPY]
Check
detection
probe.
Press
[COPY]
Check wiring to
generator.
Press [COPY]
Replace
generator.
Press [COPY]
Press [1/O] button
FAULT FINDING
F
AUL
T FINDING
Summary of Contents for Concord CXC 116
Page 1: ......
Page 38: ...38 Concord CXC Installation NOTES ...