GENERAL
8
Concord CXSi/H -
Installation & Servicing
Limitations of Intended Operating Environment
These appliances are NOT suitable for installation where they will
be exposed to the elements.
A boiler room shall be constructed or adapted to meet the
requirements of BS 6644.
The maximum ambient temperature is 32 °C at 1.5 metres from the
floor with a maximum humidity of 90% RH.
FOR SMALL PIPE INSTALLATIONS;
BS. 6891:
Installation of low pressure pipework
FOR LARGE PIPE INSTALLATIONS
Gas Installations
IGE-UP-1:
Purging Procedures of Non-domestic Gas
Installations. Soundness Testing Procedures
for Industrial and Commercial.
IGE-UP-2:
Guidance notes on the Installation of Gas
Pipework, Boosters and Compressors in
Customer’s Premises Equal to or Greater than
25mm (Non-domestic).
IGE-UP-10:
Installation of Gas Appliances in Industrial and
Commercial Premises.
BS.6644:
Installation of Gas Fired Hot Water Boilers
70kW to 1.8MW (net).
BS 6880 Pt 1-3: Water Supply.
CP342:2:
Centralised Hot Water Supply.
Model Water Bye-laws
Manufacturers notes must not be taken, in any way, as overriding
statutory obligations.
The appliance must be installed in a room separated from living
rooms and provided with appropriate ventilation direct to the outside
- see Table 5.
automatic reset. In the event of shutdown both visual and
audible alarms may be necessary.
Pressure vessels used must comply with BS. 4814 and must
be sized on the basis of the total system volume and initial
charge pressure.
Initial minimum charge pressure should not be less than 0.5
bar (7.2 psi) and must take account of the static head and
specification of the pressurising equipment. The maximum water
temperatures permissible at the point of minimum pressure in
the system are specified in Guidance Note PM5.
When make up water is not provided automatically it will be
necessary to fit controls which shut down the plant in the event
of the maximum system pressure approaching to within 0.35
bar (5 psi) of the safety valve setting.
Other British Standards applicable to commercial sealed systems
are:-
BS. 6880: Part 2
BS. 1212
BS. 6281: Part 1
BS. 6282: Part 1
BS. 6283: Part 4
Working pressure 6.0 bar maximum.
Particular reference should be made to BS. 6644: Section 6
and Guidance note PM5 "Automatically controlled steam and
hot water boilers" published by the Health and Safety Executive.
The information and guidance given below is not intended to
override any requirements of either of the above publications or
the requirements of the local authority, gas or water undertakings.
In general commercial closed pressurised systems are provided
with either manual or automatic water make up.
On both instances it will be necessary to fit automatic controls
intended to protect the boiler, circulating system and ancillary
equipment by shutting down the boiler plant if a potentially
hazardous situation should arise.
Examples of such situations are low water level and operating
pressure or excessive pressure within the system. Depending
on circumstances, controls will need to be either manual or
evaporate a large portion of the system water capacity over a full
heating season.
There will always be corrosion within a heating or hot water system
to a greater or lesser degree, irrespective of water characteristics,
unless the initial fill water from the mains is treated. Even the water
in closed systems will promote corrosion unless treated.
For the reason stated
Caradon Ideal Limited
strongly recommend
that when necessary the system is thoroughly cleaned, prior to the
use of stable inhibitor, which does not require continual topping up
to combat the effects of hardness salts and corrosion on the heat
exchangers of the boiler and associated systems.
Caradon Ideal Limited
advise contact directly with specialists on
water treatment such as:
Fernox Manufacturing Co. Ltd.,
or
Sentinel Division,
Tandem House, Marlowe Way
Betz Dearborn Ltd.,
Croydon.
Widnes,
Surrey CRO 4XS
Cheshire, WA8 8UD
Tel 0870 601 5000
Tel. 0151 424 5351.
SAFE HANDLING OF SUBSTANCES
Care should be taken when handling the boiler insulation panels,
which can cause irritation to the skin. No asbestos, mercury or
CFCs are included in any part of the boiler.
INSTALLATION REQUIREMENTS
The appliance must be installed by a CORGI registered installer,
The installation of the boiler must be in accordance with the relevant
requirements of the Gas Safety Regulations, current I.E.E.
(BS.7671) Regulations, Model Water Bye-laws, local water
authority bye-laws and it should also comply with any relevant
requirements of the local gas supplier, local authority and the
relevant British Standard Codes of practice and building
regulations.
4
SEALED (PRESSURISED) SYSTEMS
157294-3.pmd
11/8/2005, 9:58 AM
8