20 BURNER DRAWER ASSEMBLY
-
Put the combustion chamber (1) back in place as
indicated on the picture and fasten it onto the base
frame (2) on the front and on the back (start on the back)
using the H M8 x 16 serrated washers removed
during step 2.
-
Slide the tray (3) in the combustion chamber taking care to
have it resting on the lower edge of the combustion
chamber walls.
-
Put the burner drawer (4) back in place and fasten it onto
the combustion chamber using the 4 H M8 flanged nuts.
19 HYDRAULIC TEST
-
Screw the plugs into the pipes (1).
-
Screw a R2 to Rp 1/2 reduction into the
heating return (2).
-
Connect the test pump to this reduction
(3). Run the test for 10 minutes. The test
pressure must be equal to 9 bar. Any drop
in pressure indicates a leakage in the
boiler body. After the hydraulic test,
remove the pump, the reduction and the
plugs.